Airflow Data — DC96VE1005CNA
Notes
•
All furnaces ship as high speed for cooling. Installer must adjust blower speed as needed.
•
For most jobs, about 400 CFM per ton when cooling is desirable.
•
INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.
COOLING
DIP Switches
S1-1 S1-2 S1-3
Static
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
Tstat Call CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
**OFF OFF OFF
Ylo
1637
1577
1528
1467
1410
1369
1307
1256
Y
2069
2009
1978
1932
1923
1876
1834
1773
ON OFF OFF
Ylo
1477
1422
1364
1301
1244
1190
1135
1078
Y
1637
1577
1528
1467
1410
1369
1307
1256
ON ON OFF
Ylo
1477
1422
1364
1301
1244
1190
1135
1078
Y
2069
2009
1978
1932
1923
1876
1834
1773
OFF ON OFF^
Ylo
1637
1577
1528
1467
1410
1369
1307
1256
Y
1300
1234
1175
1109
1052
992
928
866
OFF ON ON
Ylo
1637
1577
1528
1467
1410
1369
1307
1256
Y
1866
1817
1774
1729
1684
1637
1593
1552
ON OFF ON
Ylo
1477
1422
1364
1301
1244
1190
1135
1078
Y
1300
1234
1175
1109
1052
992
928
866
OFF ON OFF^
Ylo
1866
1817
1774
1729
1684
1637
1593
1552
Y
2069
2009
1978
1932
1923
1876
1834
1773
OFF ON OFF^
Ylo
1866
1817
1774
1729
1684
1637
1593
1552
Y
1477
1422
1364
1301
1244
1190
1135
1078
** Factory Default
SINGLE STAGE COOLING^
*NOT RECOMMENDED
CONTINUOUS FAN
DIP Switches
S2-2 S2-3 S2-4
Static
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
Tstat Call CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
**OFF OFF OFF
G
1300
1234
1175
1109
1052
992
928
866
ON OFF OFF
G
1866
1817
1774
1729
1684
1637
1593
1552
ON ON OFF
G
1477
1422
1364
1301
1244
1190
1135
1078
OFF ON OFF
G
1637
1577
1528
1467
1410
1369
1307
1256
OFF OFF ON
G
2069
2009
1978
1932
1923
1876
1834
1773
OFF ON ON
G
1300
1234
1175
1109
1052
992
928
866
ON OFF ON
G
1300
1234
1175
1109
1052
992
928
866
ON ON ON
G
1300
1234
1175
1109
1052
992
928
866
** Factory Default
HEATING
DIP Switches
S1-4 S2-1
Static
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
Tstat Call CFM
Rise
CFM
Rise
CFM
Rise
CFM
Rise
CFM
Rise
CFM
CFM
CFM
**OFF OFF
W1
1300
47
1234
50
1175
52
1109
56
1052
59
992
928
866
W2
1866
47
1817
48
1774
50
1729
51
1684
52
1637
1593
1552
ON OFF
W1
1477
42
1422
43
1364
45
1301
47
1244
49
1190
1135
1078
W2
1866
47
1817
48
1774
50
1729
51
1684
52
1637
1593
1552
ON ON
W1
1477
42
1422
43
1364
45
1301
47
1244
49
1190
1135
1078
W2
1637
54
1577
56
1528
58
1467
60
1410
62
1369
1307
1256
OFF ON
W1
1637
38
1577
39
1528
40
1467
42
1410
44
1369
1307
1256
W2
2069
43
2009
44
1978
44
1932
46
1923
46
1876
1834
1773
** Factory Default
SINGLE STAGE COOLING^
*NOT RECOMMENDED