background image

10

www.daikincomfort.com

SS-DC96VE

SS-DC96VE

www.daikincomfort.com

11

Accessories

Model

Description

DC96VE 

0403BNA

1

DC96VE 

0603BNA

1

DC96VE 

0803BNA

1

DC96VE 

1005CNA

1

CVENT-2

Concentric Vent Kit (2”) 

CVENT-3 

Concentric Vent Kit (3”) 

CFSB17

Downflow Sub-Base 17.5"

---

CFSB21

Downflow Sub-Base 21"

---

---

---

CFSB24

Downflow Sub-Base 24"

---

---

---

---

RF000142

Drain Kit -Horizontal Left Vertical Flue

EFR01

EFR02

---

---

---

---

0170K00000S

Flush Mount Vent Kit - 3" or 2" 

0170K00001S

Flush Mount Vent Kit - 2"

AFE18-60A

Fossil Fuel (Duel Fuel) Kit 

High-Altitude Natural Gas Kit

HASFK-1

HASFK-1

HASFK-2

HASFK-2

High-Altitude LP Gas Kit

TBD

TBD

TBD

TBD

LPLP03

Low LP Gas Pressure Switch

LPM-08

LP Conversion Kits (Gas Valve)

NOTE: 

1

Twinning kit is not required, but the furnace is capable of twinning. See details in the unit IO manual. 

Summary of Contents for DC96VE

Page 1: ...ober 1 2019 AHRI Certified ETL Listed Cabinet Features Designed for multi position installation DC96VE Counter flow horizontal left or right Certified for direct vent 2 pipe or non direct vent 1 pipe Easy to install top venting with optional side venting Convenient left or right connection for gas and electrical service Cabinet air leakage QLeak 2 Heavy gauge steel cabinet with durable finish Full...

Page 2: ... Initial Release B 1st Revision AFUE 97 97 98 AFUE 92 92 AFUE NOx 96 96 AFUE N Low Nox 40ng J Gas Valve Cabinet Width M Modulating H Convertible Two Stage B 17 V Two Stage S Single Stage C 21 D 24 Motor C Variable Speed ECM Communicating Maximum CFM E Multi Speed ECM S Multi Speed PSC 2 800 CFM 3 1200 CFM MBTU h 4 1600 CFM 040 40 000 BTU h 100 100 000 BTU h 5 2000 CFM 060 60 000 BTU h 120 120 000 ...

Page 3: ...reduce input rating by 4 for each 1000 above 4500 altitude DOE AFUE based upon Isolated Combustion System ICS Vent and combustion air diameters may vary depending upon vent length Refer to the latest editions of the National Fuel Gas Code NFPA 54 ANSI Z223 1 in the USA and the Canada National Standard of Canada CAN CSA B149 1 and CAN CSA B142 2 in Canada Minimum Circuit Ampacity 1 25 x Circulator ...

Page 4: ...28 C 6 6 11 14 14 25 3 2 2 1 2 23 14 1 1 1 E D Unfolded Flanges 18 Unfolded Flanges 20 Folded Flanges 2 1 2 6 2 Front View Right Side View Low Voltage Electrical Outlet Alternate Gas High Voltage Electrical Outlet Standard Drain Trap Drain Trap Holes Alternate Gas Supply Alternate Vent High Voltage Electrical Outlet Right Side Exterior Drain Trap Holes Low Voltage Electrical Outlet Air Discharge A...

Page 5: ... Switches S2 2 S2 3 S2 4 Static 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 Tstat Call CFM CFM CFM CFM CFM CFM CFM CFM OFF OFF OFF G 743 688 628 572 515 459 408 364 ON OFF OFF G 939 894 846 806 759 706 661 614 ON ON OFF G 1137 1096 1056 1018 981 940 897 859 OFF ON OFF G 647 576 511 449 387 335 280 252 OFF OFF ON G 1229 1181 1150 1117 1078 1035 1002 964 OFF ON ON G 743 688 628 572 515 459 408 364 ON OFF ON G 7...

Page 6: ...49 1215 1170 1131 1085 1046 Y 782 629 547 469 396 333 N A N A Factory Default SINGLE STAGE COOLING NOT RECOMMENDED CONTINUOUS FAN DIP Switches S2 2 S2 3 S2 4 Static 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 Tstat Call CFM CFM CFM CFM CFM CFM CFM CFM OFF OFF OFF G 894 846 780 720 660 603 554 505 ON OFF OFF G 1328 1287 1249 1215 1170 1131 1085 1046 ON ON OFF G 782 629 547 469 396 333 290 251 OFF ON OFF G 1149...

Page 7: ...2 1088 1041 Y 750 644 569 507 442 388 328 N A Factory Default SINGLE STAGE COOLING NOT RECOMMENDED CONTINUOUS FAN DIP Switches S2 2 S2 3 S2 4 Static 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 Tstat Call CFM CFM CFM CFM CFM CFM CFM CFM OFF OFF OFF G 1221 1172 1128 1087 1049 1005 959 922 ON OFF OFF G 1311 1293 1249 1203 1172 1122 1088 1041 ON ON OFF G 750 644 569 507 442 388 328 288 OFF ON OFF G 894 842 784 72...

Page 8: ...29 1684 1637 1593 1552 Y 1477 1422 1364 1301 1244 1190 1135 1078 Factory Default SINGLE STAGE COOLING NOT RECOMMENDED CONTINUOUS FAN DIP Switches S2 2 S2 3 S2 4 Static 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 Tstat Call CFM CFM CFM CFM CFM CFM CFM CFM OFF OFF OFF G 1300 1234 1175 1109 1052 992 928 866 ON OFF OFF G 1866 1817 1774 1729 1684 1637 1593 1552 ON ON OFF G 1477 1422 1364 1301 1244 1190 1135 1078 O...

Page 9: ...T BTU HR x 1000 BTU OUTPUT vs TEMPERATURE RISE CHART TEMPERATURE RISE 600 CFM 700 900 1000 1100 1200 1400 1600 1800 2000 2200 2400 CFM FORMULAS BTU OUTPUT CFM x 1 08 x RISE RISE BTU OUTPUT 1 08 CFM 800 Temperature Rise Output BTU h x 1 000 Formulas BTU h Output CFM x 1 08 x Rise Rise BTU H Output CFM x 1 08 BTU Output Vs Temperature Rise Chart ...

Page 10: ... GND INTERNAL TO SWITCH PRESSURE HIGH FIRE PROT DEVICE INTEGRATED CONTROL PK PU PLUG CONNECTION L N BK C DOOR OPEN OPEN WHEN DOOR SWITCH COMPARTMENT BLOWER SWITCH TEMP GND 1 BLOWER CIRCULATOR JUNCTION OR 40 VA Ø 60 HZ DISCONNECT WHITE RODGERS GAS VALVE TWO STAGE OVERCURRENT CONNECTOR 2 CIRCUIT LOW VOLTAGE 24V YL GND WH CHASSIS GROUND 2 3 IGNITER SURFACE HOT 2 YL PU C 2 C BLOWER DRAFT INDUCED BK PM...

Page 11: ...Sub Base 24 RF000142 Drain Kit Horizontal Left Vertical Flue EFR01 EFR02 0170K00000S Flush Mount Vent Kit 3 or 2 0170K00001S Flush Mount Vent Kit 2 AFE18 60A Fossil Fuel Duel Fuel Kit High Altitude Natural Gas Kit HASFK 1 HASFK 1 HASFK 2 HASFK 2 High Altitude LP Gas Kit TBD TBD TBD TBD LPLP03 Low LP Gas Pressure Switch LPM 08 LP Conversion Kits Gas Valve NOTE 1 Twinning kit is not required but the...

Page 12: ...12 www daikincomfort com SS DC96VE Our continuing commitment to quality products may mean a change in specifications without notice 2020 Houston Texas Notes ...

Reviews: