The electrical characteristics of the airhandler, the electric 

heat kit, and the building power supply must agree.

The air handlers listed in this manual do not have factory 

installed electric heat. Electric heat is available as an 

accessory. If installing this option, the 

ONLY

 heat kits that 

can be used are the AHKD series.

AHKD MODEL

NUMBER

NOMINAL

KW

ELECTRICAL

CHARACTERISTICS

STAGES

AHKD15-3A

15

208-240/3/60

1

AHKD15-4A

15

480/3/60

1

AHKD20-3A

20

208-240/3/60

2

AHKD20-4A

20

480/3/60

2

AHKD30-3A

30

208-240/3/60

2

AHKD30-4A

30

480/3/60

2

For all supply voltages, use the correction factors in the 

following tables, multiplied by KW and (or) temperature rise 

to have corrected results.

KW Correction Factors (-3A Models)

Supply Voltage

240

230

220

210

208

Correction Factor

1

0.92

0.84

0.77

0.75

KW Correction Factors (-4A Models)

Supply Voltage

480

460

440

415

380

Correction Factor

1

0.92

0.84

0.75

0.63

The heating mode temperatures rise is dependent upon 

the system airflow, the supply voltage, and the heat kit size 

(KW) selected. Use the following table to determine the 

temperature rise (°F).

DAX0904 Temperature Rise Table (°F)

KW

CFM

208

240

480

15

2800

12

16

16

15

2900

12

16

16

15

3000

11

15

15

15

3100

11

15

15

15

3200

10

14

14

20

2800

16

22

22

20

2900

16

21

21

20

3000

16

21

21

20

3100

16

20

20

20

3200

15

20

20

30

2800

24

32

32

30

2900

23

31

31

30

3000

23

30

30

30

3100

21

29

29

30

3200

21

29

29

DAX0904 Temperature Rise Table (°F) - 7.5Ton

DAX1204 Temperature Rise Table (°F)

KW

CFM

208

240

480

15

3800

9

12

12

15

3900

9

12

12

15

4000

9

12

12

15

4100

9

12

12

15

4200

8

11

11

20

3800

12

17

17

20

3900

12

16

16

20

4000

12

16

16

20

4100

12

15

15

20

4200

11

15

15

30

3800

19

25

25

30

3900

18

24

24

30

4000

18

24

24

30

4100

17

23

23

30

4200

17

23

23

DAX1204 Temperature Rise Table (°F) - 10Ton

NOTE: Temperature rise tables are calculated 

with both stages of electric heat engaged (2 stage 

heat systems). 

Electrical Supply Wire and MOP

CAUTION

FIRE HAZARD!

To avoid the risk of property damage, personal injury or 

fire, use only copper conductors.

WARNING

HIGH VOLTAGE

Disconnect all power before servicing or 

installing this unit. Multiple power sources 

may be present. Failure to do so may cause 

property damage, personal injury or death. 

HIGH VOLTAGE!

To avoid property damage, personal injury or death due to 

electrical shock, this unit MUST have an uninterrupted, 

unbroken electrical ground. The electrical ground 

circuit may consist of an appropriately sized electrical 

wire connecting the ground lug in the unit control box 

to the building electrical service panel. Other methods 

of grounding are permitted if performed in accordance 

with the National Electric Code (NEC) / American National 

Standards Institute (ANSI) / National Fire Protection 

Association (NFPA) 70 and local/state codes. In Canada, 

electrical groundings is to be in accordance with the 

Canadian Electrical code (CSA) C22.1.

WARNING

Summary of Contents for DAX Series

Page 1: ...suitable for Upflow and Horizontal Installations only do not use for downflow Installations ATTENTION INSTALLING PERSONNEL Prior to installation thoroughly familiarize yourself with this Installation...

Page 2: ...and a carbon monoxide producing device is operated therein there must be adequate direct outside ven la on CARBONMONOXIDE POISONING HAZARD Special Warning for Installa on of Furnace or Air Handling Un...

Page 3: ...ng the table Model Identification section check the equipment model number and voltage to ensure the unit is appropriately sized for the condenser unit s If an incorrect unit is supplied it must not b...

Page 4: ...g this unit in an area that may become wet elevate the unit with a sturdy non porous material In installations that may lead to physical damage warehouse industrial sites etc it is advised to install...

Page 5: ...00 23 31 31 30 3000 23 30 30 30 3100 21 29 29 30 3200 21 29 29 DAX0904 Temperature Rise Table F 7 5Ton DAX1204 Temperature Rise Table F KW CFM 208 240 480 15 3800 9 12 12 15 3900 9 12 12 15 4000 9 12...

Page 6: ...ipment Use the following check list when selecting the appropriate wire size for your unit Wire size must carry the Minimum Circuit Ampacity MCA Refer to the NEC USA or CSA Canada for wire sizing The...

Page 7: ...o a mating plug in the airhandler The high voltage connections are to be made at the air handler contactor These wires are to be routed through the pipe nipples supplied with the heater kit as shown i...

Page 8: ...quid lines are to be manifolded when matched with a single condenser heat pump See the following sketches for additional details On a 7 ton DAX unit you can use either one 7 ton condenser or two 4 ton...

Page 9: ...SPEED COOLING AC HP DEFAULT SPEED FOR ALL Y2 3 HIGH SPEED HEATING DEFAULT SPEED FOR HP OR AC HP WITH ELECTRIC HEAT 4 FAN ONLY 5 HIGH COOL HIGHER SPEED Prior to changing the torque settings refer to ai...

Page 10: ...51 0 5 3407 958 0 53 0 6 3310 987 0 54 0 7 3176 1021 0 56 0 8 3050 1058 0 58 HORIZONTAL SPEED TAP ESP In H2O SCFM RPM BHP T1 0 1 2125 552 0 06 0 2 1583 553 0 06 0 3 1132 591 0 07 0 4 911 653 0 07 0 5...

Page 11: ...02 0 89 0 6 4175 1124 0 91 0 7 4099 1148 0 93 0 8 4022 1171 0 95 HORIZONTAL SPEED TAP ESP In H2O SCFM RPM BHP T1 0 1 2576 618 0 16 0 2 2460 661 0 18 0 3 2328 702 0 19 0 4 2173 747 0 20 0 5 2016 789 0...

Page 12: ...SEQ SEQUENCER RELAY TB TERMINAL BLOCK TR TRANSFORMER 2 S1 S2 R C G W1 W2 Y1 Y2 O TB T1 T2 T3 T4 T5 4 3 2 1 5 PLF BM1 PLF BM2 GR YL PU WH BR GR YL PU WH BR GR YL PU WH BR 4 3 2 1 5 YL BR BR YL 5 3 4 T...

Page 13: ...NG DIAGRAM SHOWING DAX MODEL SERIES WITH FIELD CONNECTIONS THIS DIAGRAM IS TO BE INCLUDED IN INSTALLATION INSTRUCTIONS A SEPARATE WIRING DIAGRAM IS CONTAINED INSIDE THE CONTROL BOX FOR UNIT FACTORY WI...

Page 14: ...14 THIS PAGE LEFT INTENTIONALLY BLANK...

Page 15: ...15 THIS PAGE LEFT INTENTIONALLY BLANK...

Page 16: ...022 2023 19001 Kermier Rd Waller TX 77484 www daikincomfort com CUSTOMER FEEDBACK Daikin is very interested in all product comments Please fill out the feedback form on the following link https daikin...

Reviews: