background image

4

Pre-Installation Instructions

Carefully read all instructions for the installation prior to 

installing product. Make sure each step or procedure is 

understood and any special considerations are taken into 

account before starting installation. Assemble all tools, 

hardware and supplies needed to complete the installation. 

Some items may need to be purchased locally. Make sure 

everything needed to install the product is on hand before 

starting. 

Location

NOTE: Airhandlers are designed for indoor 

installation only.

When installing this airhandler in an enclosed area, such 

as a garage/parking area, as with any carbon monoxide 

producing device (i.e. and automobile, space heater, water 

heater, etc.), insure that the area is properly ventilated.

The DAX airhandler is suitable for installation in multiple 

locations including:

• 

  Overhead (attic/mezzanine, etc.)

•   Closet/mechanical room

When installing this airhandler, consideration is to be given 

to minimize the length of refrigerant tubing. Also, do not 

install the airhandler in a location either above or below the 

condenser that violates the instructions provided with the 

condenser.

The clearance from a combustible surface to the unit may 

be 0”. However, service clearance is to take precedence. 

In addition allow a minimum of 36” in front of the unit for 

service clearance. Allow sufficient clearance to remove 

the heater elements for service or replacement in heat kits 

when utilized in application.

When installing in an area directly over a finished ceiling 

(such as an attic), an emergency drain pan is required 

directly under the unit. See local and state codes for 

additional requirements.

When installing this unit in an area that may become wet, 

elevate the unit with a sturdy, non-porous material.

In installations that may lead to physical damage 

(warehouse, industrial sites, etc.), it is advised to install a 

protective barrier to prevent such damage.

Ductwork

This DAX air handler is designed for a complete supply 

and return ductwork system.

CAUTION

Do not operate this product without all the ductwork 

attached.

In order to ensure optimum system performance, it 

is recommended that the ductwork is to be sized to 

accommodate 375-425 CFM per ton of cooling with 

the total external static pressure not to exceed .5” WC. 

Inadequate duct work that restricts airflow can result in 

improper performance and compressor or heater failure. 

Ductwork is to be constructed in a manner that limits 

restrictions and maintains suitable air velocity. Ductwork 

is to be sealed to the unit in a manner that will prevent 

leakage.

Supply Ductwork and Flanges

The supply ductwork flanges are shipped loose and 

required to be field installed. See the following sketch for 

further details: Dimensions are approximately 40” x 13-1/8”.

 

Return Ductwork

DO NOT TERMINATE THE RETURN DUCTWORK 

IN AN AREA THAT CAN INTRODUCE TOXIC, OR 

OBJECTIONABLE FUMES/ODORS INTO THE 

DUCTWORK. The return ductwork is to be introduced into 

the air handler bottom (upflow configuration). The cabinet 

dimensions are 48” x 24”.

Return Air Filters

Each installation must include a return air filter. This unit 

is factory equipped with disposable return air filters. To 

ensure optimum performance, frequent filter replacement 

is advised. See the following table for the factory installed 

filter sizes.

Model

Filter Size (in)

Qty.

DAX0904 and

DAX1204

16 x 20 x 2

2

20 x 20 x 2

2

Electric Heat

Refer to this manual in combination with the instructions 

provided with the heat kit for the correct installation 

procedure.

Summary of Contents for DAX Series

Page 1: ...suitable for Upflow and Horizontal Installations only do not use for downflow Installations ATTENTION INSTALLING PERSONNEL Prior to installation thoroughly familiarize yourself with this Installation...

Page 2: ...and a carbon monoxide producing device is operated therein there must be adequate direct outside ven la on CARBONMONOXIDE POISONING HAZARD Special Warning for Installa on of Furnace or Air Handling Un...

Page 3: ...ng the table Model Identification section check the equipment model number and voltage to ensure the unit is appropriately sized for the condenser unit s If an incorrect unit is supplied it must not b...

Page 4: ...g this unit in an area that may become wet elevate the unit with a sturdy non porous material In installations that may lead to physical damage warehouse industrial sites etc it is advised to install...

Page 5: ...00 23 31 31 30 3000 23 30 30 30 3100 21 29 29 30 3200 21 29 29 DAX0904 Temperature Rise Table F 7 5Ton DAX1204 Temperature Rise Table F KW CFM 208 240 480 15 3800 9 12 12 15 3900 9 12 12 15 4000 9 12...

Page 6: ...ipment Use the following check list when selecting the appropriate wire size for your unit Wire size must carry the Minimum Circuit Ampacity MCA Refer to the NEC USA or CSA Canada for wire sizing The...

Page 7: ...o a mating plug in the airhandler The high voltage connections are to be made at the air handler contactor These wires are to be routed through the pipe nipples supplied with the heater kit as shown i...

Page 8: ...quid lines are to be manifolded when matched with a single condenser heat pump See the following sketches for additional details On a 7 ton DAX unit you can use either one 7 ton condenser or two 4 ton...

Page 9: ...SPEED COOLING AC HP DEFAULT SPEED FOR ALL Y2 3 HIGH SPEED HEATING DEFAULT SPEED FOR HP OR AC HP WITH ELECTRIC HEAT 4 FAN ONLY 5 HIGH COOL HIGHER SPEED Prior to changing the torque settings refer to ai...

Page 10: ...51 0 5 3407 958 0 53 0 6 3310 987 0 54 0 7 3176 1021 0 56 0 8 3050 1058 0 58 HORIZONTAL SPEED TAP ESP In H2O SCFM RPM BHP T1 0 1 2125 552 0 06 0 2 1583 553 0 06 0 3 1132 591 0 07 0 4 911 653 0 07 0 5...

Page 11: ...02 0 89 0 6 4175 1124 0 91 0 7 4099 1148 0 93 0 8 4022 1171 0 95 HORIZONTAL SPEED TAP ESP In H2O SCFM RPM BHP T1 0 1 2576 618 0 16 0 2 2460 661 0 18 0 3 2328 702 0 19 0 4 2173 747 0 20 0 5 2016 789 0...

Page 12: ...SEQ SEQUENCER RELAY TB TERMINAL BLOCK TR TRANSFORMER 2 S1 S2 R C G W1 W2 Y1 Y2 O TB T1 T2 T3 T4 T5 4 3 2 1 5 PLF BM1 PLF BM2 GR YL PU WH BR GR YL PU WH BR GR YL PU WH BR 4 3 2 1 5 YL BR BR YL 5 3 4 T...

Page 13: ...NG DIAGRAM SHOWING DAX MODEL SERIES WITH FIELD CONNECTIONS THIS DIAGRAM IS TO BE INCLUDED IN INSTALLATION INSTRUCTIONS A SEPARATE WIRING DIAGRAM IS CONTAINED INSIDE THE CONTROL BOX FOR UNIT FACTORY WI...

Page 14: ...14 THIS PAGE LEFT INTENTIONALLY BLANK...

Page 15: ...15 THIS PAGE LEFT INTENTIONALLY BLANK...

Page 16: ...022 2023 19001 Kermier Rd Waller TX 77484 www daikincomfort com CUSTOMER FEEDBACK Daikin is very interested in all product comments Please fill out the feedback form on the following link https daikin...

Reviews: