SiBE12-908
Troubleshooting
Service Diagnosis
137
Troubleshooting
Check No.16
Refer to P.168
Check No.29
Refer to P.171
Check No.14
Refer to P.166
YES
YES
Replace stop valve.
Replace
·Outdoor unit PCB
·Outdoor fan
·Humidification fan
·Four way valve coil
Replace the outdoor unit
PCB.
Connect properly.
*Inverter checker
Part No.: 1225477
Rectify the power supply or
replace the outdoor unit
PCB.
Replace the compressor.
Judge
Is there any LED
turned off?
(R9445)
Check No. 16
Discharge pressure check
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is it OK?
Check the voltage of electrolytic
capacitor
DC270±30V?
NO
Check No. 29
Short circuit check
Is the harness of
electric component or
compressor connected
properly?
NO
Turn off the power supply, and
disconnect U, V, and W
harnesses
Check the power supply
NO
YES
NO
YES
Check No.14
Check the inverter by the
inverter checker*