SiBE12-908
Troubleshooting
Service Diagnosis
125
2.16
Outdoor Unit PCB Abnormality
Remote
Controller Display
E1
Outdoor Unit LED
Display
A
5
5
5
A
7
5
5
(zero-cross abnormality)
Method of
Malfunction
Detection
Detect within the programme of the microcomputer that the programme is in good running
order.
Detect input of zero-cross signal.
Malfunction
Decision
Conditions
When the programme of the microcomputer is in bad running order.
Zero-cross signal can not be detected.
Supposed
Causes
Out of control of microcomputer caused by external factors
z
Noise
z
Momentary fall of voltage
z
Momentary power loss
Defective outdoor unit PCB
Breakage of harness between PCBs
Troubleshooting
Replace the outdoor unit
PCB.
Carry out grounding work.
Zero-cross signal is fault.
Replace the outdoor unit
PCB.
Replace harness.
(R9437)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Power on again
NO
Dose the LED A
blink?
YES
Is harness in good
order?
NO
YES
Check to see that the machine is
grounded.
NO
Grounded?
YES