8
|
Electrical installation
Installer reference guide
40
CTXM-A, FTXM-A, ATXM-A
Daikin room air conditioner
4P518023-17P – 2023.06
8.1.3 Specifications of standard wiring components
Component
Interconnection cable
(indoor↔outdoor)
Voltage
220~240 V
Wire size
Only use harmonized wire
providing double insulation and
suitable for applicable voltage
4-core cable
Minimum 1.5 mm²
Earth leakage circuit
breaker / residual
current circuit breaker
MUST comply with national wiring regulation
8.2 To connect the electrical wiring to the indoor unit
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small
animals. Small animals that make contact with electrical parts can cause
malfunctions, smoke or fire.
NOTICE
▪
Keep the power line and transmission line apart from each other. Transmission
wiring and power supply wiring may cross, but may NOT run parallel.
▪
In order to avoid any electrical interference, the distance between both wirings
should ALWAYS be at least 50 mm.
Electrical work should be carried out in accordance with the installation manual
and the national electrical wiring rules or code of practice.
1
Set the indoor unit on the mounting plate hooks. Use the " " marks as a
guide.
d
c
b
a
a
Mounting plate (accessory)
b
Piece of packing material
c
Interconnection cable
d
Wire guide
INFORMATION
Support the unit using a piece of packing material.
Example: