Electrical installation
Installer reference guide
39
CTXM-A, FTXM-A, ATXM-A
Daikin room air conditioner
4P518023-17P – 2023.06
Method 2: Using round crimp-style terminal
1
Strip insulation from wires and slightly twist the end of each wire.
2
Install a round crimp-style terminal on the end of the wire. Place the round
crimp-style terminal on the wire up to the covered part and fasten the
terminal with the appropriate tool.
Use the following methods for installing wires:
Wire type
Installation method
Single-core wire
Or
Stranded conductor wire
twisted to "solid-like"
connection
c b
c
a
a
A
AA´
A´
a
Curled wire (single-core or twisted stranded
conductor wire)
b
Screw
c
Flat washer
Stranded conductor wire
with round crimp-style
terminal
c b
b
a
c
a
B
B
a
Terminal
b
Screw
c
Flat washer
Allowed
NOT allowed
▪
The earth wire between the wire retainer and the terminal must be longer than
the other wires.
1-3