4 Installation
Installation manual
6
C08AA
Daikin hybrid for multi heat pump – heat pump module
4P471756-1C – 2017.10
B (kg)
A (m
2
)
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 3.0 3.1 3.2 3.3 3.4 3.5
H=500, 600, 700 mm
H=800 mm
H=1000 mm
H=900 mm
H=1100 mm
H=1200 mm
H=1300 mm
H=1400 mm
H=1500 mm
H=1600 mm
H=1700 mm
H=1800 mm
A
Minimum floor area for hybrid unit (m
2
)
B
Total refrigerant charge in the system (kg)
H
The height measured from the floor to the bottom of the
casing. The graph is based on the height measured from
the floor to the flare nut.
▪ The indoor unit is designed for indoor installation only (in a
technical room or similar) and for ambient temperatures ranging
5~30°C in heating mode.
3.2
Preparing water piping
NOTICE
In case of plastic pipes, make sure they are fully oxygen
diffusion tight according to DIN 4726. The diffusion of
oxygen into the piping can lead to excessive corrosion.
3.2.1
To check the water volume and flow rate
Minimum water volume
Check that the total water volume in the installation is minimum
13.5 litre, the internal water volume of the indoor unit NOT included.
INFORMATION
In critical processes, or in rooms with a high heat load,
extra water might be required.
NOTICE
When circulation in each space heating/cooling loop is
controlled by remotely controlled valves, it is important that
the minimum water volume is guaranteed, even if all of the
valves are closed.
Minimum flow rate
Check that the minimum flow rate (required during defrost/backup
heater operation) in the installation is guaranteed in all conditions.
NOTICE
When circulation in each or certain space heating loops is
controlled by remotely controlled valves, it is important that
the minimum flow rate is guaranteed, even if all valves are
closed. In case the minimum flow rate cannot be reached,
a flow error 7H will be generated (no heating or operation).
See the installer reference guide for more information.
Minimum required flow rate
05+08 models
9 l/min
See the recommended procedure as described in
"6.2 Checklist
during commissioning" on page 20
.
3.3
Preparing electrical wiring
3.3.1
Overview of electrical connections for
external and internal actuators
Item
Description
Wires
Maximum
running
current
Outdoor unit and indoor unit power supply
1
Power supply for
outdoor unit
2+GND
(a)
2
Power supply and
interconnection cable to
indoor unit
3+GND
(g)
3
Power supply gas
boiler
2+GND
(c)
User interface
4
User interface
2
(f)
Optional equipment
5
3‑way valve
3
100 mA
(b)
6
Domestic hot water
tank thermistor
2
(d)
7
Room thermostat/heat
pump convector
3 or 4
100 mA
(b)
8
Outdoor ambient
temperature sensor
2
(b)
9
Indoor ambient
temperature sensor
2
(b)
Field supplied components
10
Shut-off valve
2
100 mA
(b)
11
Domestic hot water
pump
2
(b)
12
Alarm output
2
(b)
13
Changeover to external
heat source control
2
(b)
14
Space heat operation
control
2
(b)
15
Safety thermostat
2
(e)
(a)
Refer to name plate on outdoor unit.
(b)
Minimum cable section 0.75 mm².
(c)
Use the cable supplied with the boiler.
(d)
The thermistor and connection wire (12 m) are delivered
with the domestic hot water tank.
(e)
Cable section 0.75 mm² till 1.25 mm²; maximum length:
50 m. Voltage-free contact shall ensure the minimum
applicable load of 15 V DC, 10 mA.
(f)
Cable section 0.75 mm² till 1.25 mm²; maximum length:
500 m. Applicable for both single user interface and dual
user interface connection.
(g)
Cable section 1.5 mm
2
; maximum length: 50 m.
NOTICE
More technical specifications of the different connections
are indicated on the inside of the indoor unit.
4
Installation
4.1
Opening the units
4.1.1
To open the switch box cover of the
indoor unit
1
Remove the side panel at the right side of the indoor unit. The
side panel is fixed at the bottom with 1 screw.