3P257556-2A English
12
Make field settings according to the installation manual of the
remote controller. (Settings in bold cells are made before shipping.)
Setting
item
Mode
No.
FIRST
CODE
NO.
SECOND CODE NO.
01
02
03
04
Display
Dust
Collection
sign 1
10
(20)
(3) Display
No display
–
–
Dust
quantity
settings
14
(24)
(9)
Standard
quantity of
dust
Large
quantity of
dust
–
–
Panel
indicator
(green)
on/off
14
(24)
(4)
On while in
air-conditioning
operation and
filter cleaning
operation.
Possible to
turn on while
in filter
cleaning
operation only.
Off while in
air-conditioning
operation and filter
cleaning operation.
* Factory settings
–
11. Test Operation
Perform the test operation of the Self Cleaning decoration panel
after the test operation of the indoor unit is finished.
The test operation of the Self-Cleaning Decoration Panel is not
possible while the indoor unit is in operation.
Note
Perform the test operation of the product after referring to "a. Test
items on completion of work".
11-1 Check that the control box covers of the
indoor unit, outdoor unit, and self-clean
panel, respectively, are closed
11-2 Turn the indoor unit power on
The panel will go into initialization operation after the power is
turned on.
11-3 Conduct the test operation of the panel 2
minutes after the power is turned on
Confirm the cleaning operation of the filter with the remote
controller.
Test operation method with remote controller
1. Stop the operation of the panel if the panel is in air-conditioning
operation.
2. Continue pressing the Cancel button at least 4 seconds while the
backlight is lit. The service settings menu will appear.
3. Select
Test
Fi
lter Auto Clean
from the service settings menu,
and press the Menu/Enter button.
4. "
" will appear on the basic screen.
The display will disappear when the test operation is finished.
The required test operation time is approximately 10 minutes (in
the case of setting the standard quantity of dust).
1.
2.
Cool
Set to
Cool
83
°F
Press and hold
Cancel button for
4 seconds or
longer during
backlight lit.
3.
Return
Setting
Service Settings
Indoor Unit Status
Outdoor Unit Status
Forced Fan ON
Switch Main Sub Controller
Filter Indicator OFF
Test Filter Auto Clean
2/3
Press Menu/Enter
button.
4.
Cool
Set to
Cool
83
°F
Collect dust
Backlight for LCD
Press any button and the backlight will be lit for approximately
30 seconds.
Perform the operation of buttons while the backlight is lit (except the
On/Off button).
Test items on test operation
Test items
Remedy
Check
result
Is the filter rotating?
Check the
connector
connections.
Are the flaps fixed horizontally?
Is "
" displayed on the screen of
the remote controller?
* The remote controller will display "AH" if the self-clean panel has
an error.
Note
After the test operation of the product is finished, refer to "b. Test
items before delivery" in the installation manual.
3P257556-2A.indb 12