background image

3P257556-2A        English

12

Make field settings according to the installation manual of the 
remote controller. (Settings in bold cells are made before shipping.)

Setting 

item

Mode

No.

FIRST
CODE

NO.

SECOND CODE NO.

01

02

03

04

Display 
Dust 
Collection 
sign 1

10 

(20)

(3) Display

No display

Dust 
quantity 
settings

14 

(24)

(9)

Standard 
quantity of 
dust

Large 
quantity of 
dust

Panel 
indicator 
(green)  
on/off

14 

(24)

(4)

On while in 
air-conditioning 
operation and 
filter cleaning 
operation.

Possible to 
turn on while 
in filter 
cleaning 
operation only.

Off while in 
air-conditioning 
operation and filter 
cleaning operation.
 *  Factory  settings

11. Test Operation

Perform the test operation of the Self Cleaning decoration panel 
after the test operation of the indoor unit is finished.
The test operation of the Self-Cleaning Decoration Panel is not 
possible while the indoor unit is in operation.

Note

Perform the test operation of the product after referring to "a. Test 
items on completion of work".

11-1  Check that the control box covers of the 

indoor unit, outdoor unit, and self-clean 

panel, respectively, are closed

11-2  Turn the indoor unit power on

The panel will go into initialization operation after the power is 
turned on.

11-3  Conduct the test operation of the panel 2 

minutes after the power is turned on

Confirm the cleaning operation of the filter with the remote 
controller.

Test operation method with remote controller

1. Stop the operation of the panel if the panel is in air-conditioning 

operation.

2. Continue pressing the Cancel button at least 4 seconds while the 

backlight is lit. The service settings menu will appear.

3. Select 

 Test 

Fi

lter Auto Clean 

 from the service settings menu, 

and press the Menu/Enter button.

4. " 

 " will appear on the basic screen.  

The display will disappear when the test operation is finished. 
The required test operation time is approximately 10 minutes (in 
the case of setting the standard quantity of dust).

1.
2.

Cool

Set to

Cool

83

°F

Press and hold 
Cancel button for 
4 seconds or 
longer during 
backlight lit.

3.

Return

Setting

Service Settings

Indoor Unit Status
Outdoor Unit Status
Forced Fan ON
Switch Main Sub Controller
Filter Indicator            OFF

Test Filter Auto Clean 

2/3

Press Menu/Enter 
button.

4.

Cool

Set to

Cool

83

°F

Collect dust

Backlight for LCD

Press any button and the backlight will be lit for approximately  
30 seconds.
Perform the operation of buttons while the backlight is lit (except the 
On/Off button).

Test items on test operation

Test items

Remedy

Check 

result

Is the filter rotating?

Check the 
connector 
connections.

Are the flaps fixed horizontally?
Is  "  

 " displayed on the screen of 

the remote controller?

 

* The remote controller will display "AH" if the self-clean panel has 

an error.

Note

After the test operation of the product is finished, refer to "b. Test 
items before delivery" in the installation manual.

3P257556-2A.indb   12

12/16/2013   4:28:10 PM

Summary of Contents for BYCQ125BGW1

Page 1: ...Decoration Panel Provided with Filter Auto cleaning Function Self Cleaning Decoration Panel INSTALLATION MANUAL BYCQ125BGW1 3P257556 2A 3P257556 2A indb 1 12 16 2013 4 27 52 PM ...

Page 2: ... carry the product Do not carry the package with the polypropylene band on the package held which will be dangerous because the polypropyl ene band may be deformed Do not touch the fin of the heat exchanger Touching the fin improperly may result in injury Do not turn the product power off immediately after the operation of the product comes to a stop Always wait for at least 5 minutes before turni...

Page 3: ...r Panel 4 6 Preparations for Indoor Unit 5 7 Attaching Panel to Indoor Unit 6 8 Attaching Suction Grille and Decoration Corner Covers 9 9 Operation Mode Settings 11 10 Field Settings 11 11 Test Operation 12 The English text is the original instruction Other languages are translations of the original instructions 3P257556 2A indb 1 12 16 2013 4 27 52 PM ...

Page 4: ...s Result Was the test operation of the air conditioner finished Did you explain the operation method of the air conditioner to the customer while showing the customer the operation manual Did you make mode settings for filter auto cleaning automatic control operation settings or timer operation settings with an operation time zone specified and provide information on the set mode operation of the ...

Page 5: ...lighting applies to exposed models e g models of inverted mountain type and there are no restrictions on embedded models with no protrusion from the ceiling surface 3 If the air discharge outlet is closed or the wind direction of the swing flaps are changed to block the wind the space marked with the asterisk will be 20 in 500 mm or over The space will be 8 in 200 mm or over if the air discharge o...

Page 6: ...tective corrugated cardboard Protective corrugated cardboard top The accessories are on the backside Protective corrugated cardboard bottom Note Do not impose force on the swing flap brush unit or air filter when handling the panel Panel Brush unit Air filter Swing flap 5 2 Removal of decoration corner covers Panel Decoration corner cover Decoration corner cover Decoration corner cover Decoration co...

Page 7: ... after installing the indoor unit Install the indoor unit according to the installation manual provided with the indoor unit 6 1 Attaching spacer accessory 1 1 Remove the bypass hole closing cap 1 2 1 Indoor unit 2 Remove the bypass hole closing cap 2 Peel off the release paper of the double stick tape on the backside of the spacer accessory 1 3 Attach the spacer accessory 1 on the air bypass hole...

Page 8: ... panel on the internal circumference side to the hooks of the indoor unit Note Let go your hands after confirming through the check window that the temporary latching brackets are engaged with the hooks 2 Remove from the harness opening as described in 6 Preparations for Indoor Unit on page 5 Pull out the lead wires disconnected from the decoration cover in the corner carefully so that lead wries ...

Page 9: ...e seal of panel 2 Insert the seal until the seal comes in contact with the clamp 3 Clamp 4 Sealing accessory 6 2 Draw the harness and lead wires on the panel side Panel Harness Harness Lead wire on the panel side Lead wire on the panel side 3 Connect the connector of the lead wires and move the glass tube to cover the connector part Lead wire on the panel side Harness Connector Be sure to connect ...

Page 10: ...illustration 1 2 3 4 5 1 Clasp 2 Hooked fall prevention cord 3 Panel 4 Fall prevention cord 5 Dust box 2 Attach the dust box in the order opposite to the procedure in 5 3 Removal of dust box on page 4 Note Make sure that the fall prevention cord is not caught by the exhaust opening on the dust box when attaching the dust box Otherwise the dust box may not function normally 3 Turn the fixing knobs ...

Page 11: ...vention cord 3 Connect the flexible hose accessory 2 onto the panel side The flexible hose accessory 2 has no directionality constraint Flexible hose junction on the panel side Flexible hose accessory 2 Flexible hose junction on the panel side Fit the clamps into the hooks in two points securely Hooks 2 points Note Check that the clamps are engaged securely Otherwise a dust collection failure may ...

Page 12: ...flexible hose accessory 2 has no directionality constraint Flexible hose junction on the panel side Fit the clamps into the hooks in 2 points securely Flexible hose accessory 2 Flexible hose junction on the panel side Hooks 2 points Note Check that the clamps are engaged securely Otherwise a dust collection failure may result 4 Press fit the flexible hose connected in 3 into the panel Make sure th...

Page 13: ...owing operation modes can be selected for the filter auto cleaning of the self clean panel Operation mode Description 1 Scheduled timer operation Performs filter auto cleaning during the designated period selected from eight periods 2 00 00 to 03 00 operation Performs filter auto cleaning during the factory set period of time 00 00 to 03 00 3 Auto control operation Performs filter auto cleaning ac...

Page 14: ...th the remote controller Test operation method with remote controller 1 Stop the operation of the panel if the panel is in air conditioning operation 2 Continue pressing the Cancel button at least 4 seconds while the backlight is lit The service settings menu will appear 3 Select Test Filter Auto Clean from the service settings menu and press the Menu Enter button 4 will appear on the basic screen...

Page 15: ...3P257556 2A indb 13 12 16 2013 4 28 10 PM ...

Page 16: ...3P257556 2A EM13A021 1401 FS 3P257556 2A indb 1 12 16 2013 4 28 11 PM ...

Reviews: