3P257556-2A English
2
3. Accessory
Check that the following accessories provided with the air
conditioner are correct in number. See the following illustration,
which shows where the accessories are kept.
Backside of the protective
corrugated cardboard
A set of accessories
The accessories are
on the backside of the
protective corrugated
cardboard under
the suction grille.
Suction grille
Name
Spacer
(1)
Flexible
hose (2)
S-shaped
pipe (3)
Harness (4)
Clamp
(5)
Quantity
1 pc.
1 pc.
1 pc.
1 pc.
2 pcs.
Shape
Name
Seal (6)
Others
Quantity
1 pc.
Shape
•
Operation manual
•
Installation manual
Pay the utmost attention to the following items when
conducting installation work, and recheck the items on
completion of the work.
a. Test items on completion of work
Test items
In case of failure Result
Is the air conditioner free of wiring and
connection mistakes or omissions?
Operation failure
and wire burnout
Are you sure that there is no space
between the ceiling and ceiling material?
Water leakage
Are the fixing knobs (in 2 points) of the
dust box secured tightly?
Vibration, noise,
and dust
collection failure
Are the fixed knobs (in 5 points) of the
air filter secured tightly?
Vibration, noise,
and dust
collection failure
Is the fall prevention cord for the dust
box and grille hooked to the mounting
bracket?
Fall
Did you attach the control box cover,
dust box, flexible hose, S-shaped pipe,
suction grille, and decoration corner
covers?
Noise and dust
collection failure
* Be sure to recheck the items provided in the section "1. Safety
Considerations" on page i.
b. Test items before delivery
Test items
Result
Was the test operation of the air conditioner finished?
Did you explain the operation method of the air
conditioner to the customer while showing the customer
the operation manual? *
Did you make mode settings for filter auto-cleaning
(automatic control operation settings or timer operation
settings with an operation time zone specified) and
provide information on the set mode operation of the air
conditioner to the customer?
Did you deliver the operation manual to the customer?
(Be sure to hand the customer the operation manual as
well as the installation manual.)
*
Point of operation explanation
In addition to the general usage of the air conditioner, it is
necessary to explain the descriptions of the
WARNING and
CAUTION marked items in the operation manual and have
the customer read the descriptions carefully, because these
items indicate information that, if not heeded, is likely to result in
loss of life, serious injury, or property damage.
4. Installation Site
This product offers selectable air outlet directions. A closure kit (an
optional accessory) is required to achieve three-way flow patterns.
Two-way flow patterns are not available to this product.
4-1 Select the installation site that meets the
following conditions with the consent of the
customer
•
The surface of the ceiling is not inclined.
•
Installation and service workspace is secured (see the following
illustrations).
•
The panel indicators are seen with ease.
•
The indoor and outdoor units, power cord, transmission wiring,
and remote controller wiring are at least 1 m away from TV or
radio sets.
(The above is for the prevention of TV and radio interference.
Depending on the incoming signal strength, a distance of 1 m
may not be sufficient to eliminate noise.)
3P257556-2A.indb 2