3. SELECTING INSTALLATION SITE
Select an installation site where the following conditions are satisfied and that meets with your customer’s
approval.
•
Where is resistible against weight of BS unit.
•
Locations where the wall is not significantly tilted.
•
Where sufficient clearance for maintenance and service can be ensured. (
Refer to Fig. 1, Fig. 2
)
•
Locations where an inspection hole (
Refer to Fig. 1
) can be installed to EL. COMPO. BOX side (*1).
•
Where the total piping length involving indoor unit and outdoor unit is below the allowable piping length.
(See installation manual attached to outdoor unit.)
•
Where the sound of passing refrigerant does not cause problems. Never install the BS unit on the opposite
side of the ceiling of the living room.
NOTES
•
Study if the installation location is strong enough to hold the weight of the unit, and if necessary reinforce
the area with a beam or other member and then install suspension bolts. Use the suspension bolts to install
the unit. (Refer to “
4. PREPARATIONS BEFORE INSTALLATION”
)
•
Install the BS unit and its power cord and connecting wires at least 1 meter away from televisions and radios
to prevent picture interference and noise. (Depending on the incoming signal strength, a distance of 1 meter
may not be sufficient to eliminate noise.)
4. PREPARATIONS BEFORE INSTALLATION
Refer the figure 3 and install the suspension bolts and hanging brackets.
〈
Suspension bolts: For supporting the product
〉
•
Use M8-M10 suspension bolts.
•
When holes are to be made anew, used embedded inserts and embedded foundation bolts. When holes
are already provided, use hole-in-anchors or the like.
Install the BS unit so that its weight can be withstood.
(*1) Be sure to install the inspection hole on the EL. COMPO. BOX side. Another opening is required in the case of taking down
the product.
(*2) Secure the service space for the local piping.
(*3) The space is required to locate the top plate of the BS unit at the time of servicing.
300 or
more
300 or
more
300 or
more
300 or
more
Top of
BS unit
Top of
BS unit
(600)(*3)
(600)(*3)
Inspection hole 450(*1)
Inspection hole 450(*1)
In the case of BSV4Q100PV1
In the case of BSV6Q100PV1
50 or
more
250 or
more
Indoor
unit side
(two pipes)
(*2)
(mm)
(mm)
Fig. 1
Fig. 2