background image

English

13

7-4 WIRING EXAMPLE

Here is shown a wiring example for one system transmission wiring.

Connect terminals F1 and F2 (TO IN/D UNIT) on the control PCB in the outdoor unit EL. COMPO. BOX and 
terminals F1 and F2 (TO OUT/D UNIT) of the control PCB (A1P) of the first BS unit A.

NOTES

1.

Connect cooling-dedicated air conditioners to terminals F1 and F2 (TO OUT/D UNIT) of the final BS unit.

2.

Use 2-core wire for the transmission wiring. Using a multi-core wire with 3 or more cores when two or more 
indoor units are used at once could cause abnormal stoppage. (Only use 3-core wire in the COOL/HEAT 
SELECTOR.)

3.

Absolutely do not connect the power supply wiring to the transmission wiring terminal block. Doing so 
could damage the entire system.

4.

For the transmission wiring, use wire that is within the following ranges. Exceeding these limits could 
cause a transmission error.

(1)

Between an outdoor unit and BS unit,
Between a BS unit and indoor unit, and
Between a BS unit and BS unit

Maximum wiring length: 1000m or less
Total wiring length: 2000 or less
Branch point max: 16 branch points

(2)

Between a BS unit and COOL/HEAT SELECTOR

Maximum wiring length: 500m or less

7-5 WIRING CONNECTIONS

Remove the EL. COMPO. BOX lid on the side and follow the directions to connect the wires.

Transmission wiring

Remove the EL. COMPO. BOX lid and connect the wires to F1 and F2 (TO IN/D UNIT: A~F) , F1 and F2 (BS 
UNIT) and F1 and F2 (TO OUT/D UNIT) transmission wiring terminals (control PCB (A1P)).
Indoor units E and F are BSV6Q models (PV1 only)
At this time, pass the wiring into the unit through the wiring through hole (right) and use the included clamps 
2) to securely hold the wires (in 2 places).

NOTE

Check that the piping line coincides with the transmission wiring.

Power supply wiring and ground wire

Remove the EL. COMPO. BOX lid and connect the power supply wiring to 
the power terminal block (X1M).
Also connect the ground wire to the ground wire terminal. Pass both the 
power supply wire and the ground wire together through the wire through 
hole (left) and into the EL. COMPO. BOX and use the included clamps 2) to 
securely hold the wires (in 2 places).
Be sure to wire the ground wire so that comes out of the slit in the cup washer.
(Not doing so could cause insufficient ground wire contact and causing the wire not to function as a ground.)

Absolutely do not 
connect the power 
supply wiring.

Use 3-core wires. 
(There is polarity. 
Match the terminal 
numbers.)

F1 F2

F1 F2

F1 F2

F1 F2

C B

C/H SELECTOR

A

C B

C/H SELECTOR

A

C B

C/H SELECTOR

A

C B

C/H SELECTOR

A

PC board

PC board

PC board

PC board

F1 F2

F1 F2

F1

F2

F1

F2

F1

F2

F1

F2

F1

F2

F1

F2

F1

F2

F1

F2

F1

F2

F1 F2

F1 F2

F1 F2

F1 F2

A

B

C

A

B

C

F1 F2

F1 F2

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor 
unit A

Indoor 
unit B

Indoor 
unit C

Indoor 
unit D

Outdoor 

unit

BS unit

BS unit B

BS unit A

Final BS unit

Use 2-core wires. 
(There is no polarity.)

Transmission wiring

C/H SELECTOR

C/H SELECTOR

Outdoor unit

Cooling-dedicated 
air conditioner

TO IN/D UNIT TO OUT/D UNIT

TO IN/D UNIT TO OUT/D UNIT

COOL/HEAT

SELECTOR

COOL/HEAT

SELECTOR

COOL/HEAT

SELECTOR

COOL/HEAT

SELECTOR

COOL/HEAT

SELECTOR

COOL/HEAT

SELECTOR

IN / OUT OUT / OUT

Cooling/Heating selectable indoor unit

COOL/HEAT SELECTOR wiring

F1 F2

F1 F2

F1 F2

F1 F2

F1 F2

F1 F2

F1 F2

branch

Sub-branching

Cut out section

Cup washer

Ring-type crimp 
style terminal

01_EN_3P194121-4J.fm  Page 13  Wednesday, June 10, 2009  12:39 PM

Summary of Contents for BSV4Q100PV1

Page 1: ...ANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI ÄΙΑΒΑΣΤΕ ΠΡΟΣΕΚΤΙΚΑ ΑΥΤΕΣ ΤΙΣ ΟÄΗΓΙΕΣ ΠΡΙΝ ΑΠΟ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ ΕΧΕΤΕ ΑΥΤΟ ΤΟ ΕΓΧΕΙΡΙÄΙΟ ΕΥΚΑΙΡΟ ΓΙΑ ΝΑ ΤΟ ΣΥΜΒΟΥΛΕΥΕΣΤΕ ΣΤΟ ΜΕΛΛΟΝ LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLATIE BEWAAR DEZE HAN DLEINDING WAAR U HEM KUNT TERUGVINDEN VOOR LATERE NASLAG LEIA COM ATENÇÃO ESTAS INSTRUÇÕES ANTES DE REALIZAR A INSTALAÇÃO MANTENHA ESTE MANUAL AO SEU ...

Page 2: ...4PY1 RTSYQ16PY1 RTSYQ20PY1 RTSQ8PY1 RTSQ10PY1 RTSQ12PY1 RTSQ14PY1 RTSQ16PY1 BTSQ20PY1 REYQ8PY1 REYQ10PY1 REYQ12PY1 REYQ14PY1 REYQ16PY1 REYQ18PY1 REYQ20PY1 REYQ22PY1 REYQ24PY1 REYQ26PY1 REYQ28PY1 REYQ30PY1 REYQ32PY1 REYQ34PY1 REYQ36PY1 REYQ38PY1 REYQ40PY1 REYQ42PY1 REYQ44PY1 REYQ46PY1 REYQ48PY1 REYQ8PY1B REYQ10PY1B REYQ12PY1B REYQ14PY1B REYQ16PY1B REMQ8PY1 REMQ10PY1 REMQ12PY1 REMQ14PY1 REMQ16PY1 BS...

Page 3: ...in property damage or per sonal injury which may be serious depending on the circumstances WARNING Ask your dealer or qualified personnel to carry out installation work Do not attempt to install the air conditioner yourself Improper installation may result in water leakage electric shocks or fire Install the air conditioner in accordance with the instructions in this installation manual Improper i...

Page 4: ...pipes or other areas as there is a danger of frostbite CAUTION Install the BS units power cord and connecting wires at least 1 meter away from televisions or radios to pre vent picture interference and noise Depending on the incoming signal strength a distance of 1 meter may not be sufficient to eliminate noise Remote controller wireless kit transmitting distance can be shorter than expected in ro...

Page 5: ...efrigerant must be charged in its liquid state If the system is charged with refrigerant in its gaseous state due to com position change the system will not function normally The indoor outdoor unit is designed for R410A use See the catalogue for indoor outdoor unit models that can be connected Normal operation is not possible when connecting units that are originally designed for other refrigeran...

Page 6: ...ter installation is finished Completion check items Hand over check items Name 1 Accessory pipes 2 Clamp 3 Insulation tube Explanation Document Quantity 6 pcs 6 pcs 16 pcs 24 pcs 6 pcs 6 pcs 1 copy Shape 1 1 φ9 5 1 2 φ15 9 2 1 Small 2 2 Large 3 1 Small 3 2 Large Installation manual Model Total capacity of all downstreem indoor units Max number of all downstreem indoor units BSV4Q100PV1 A 400 20 BS...

Page 7: ...l the BS unit and its power cord and connecting wires at least 1 meter away from televisions and radios to prevent picture interference and noise Depending on the incoming signal strength a distance of 1 meter may not be sufficient to eliminate noise 4 PREPARATIONS BEFORE INSTALLATION Refer the figure 3 and install the suspension bolts and hanging brackets Suspension bolts For supporting the produ...

Page 8: ...ations field supply from both the top and bottom sides of the hanging bracket and make sure they are tightened correctly NOTES The BS unit has a top and a bottom so install it so that the diagonal lines in the figure 4 are where the top is Failing to do so may prevent the unit from operating properly and increase the volume of the operating noise Suspension bolt pitch Example installation Note All...

Page 9: ...such as air gets into the refrigerant piping If refrigerant gas leaks during the work ventilate the area The outdoor units are filled with refrigerant 6 1 PIPING MATERIAL SELECTION Use only pipes which are clean inside and outside and which do not accumulate harmful sulfur oxidants dirt cutting oils moisture or other contamination Foreign materials inside pipes including oils for fabrica tion must...

Page 10: ...eriorate adversely affecting the refrigerant piping system Use phosphor copper brazing BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux 6 4 PIPING SIZE SELECTION From Example of connection 1 and 2 below and Table 1 2 select the piping size between the outdoor unit refrigerant branch kit and BS unit and between the BS unit and the indoor unit refrigerant branch kit The closed ...

Page 11: ...oor units Piping size outer diameter minimum thickness Gas pipe Liquid pipe 20 25 32 40 50 φ12 7 0 80 φ6 4 0 80 63 80 100 φ15 9 0 99 φ9 5 0 80 mm BS unit Piping size outer diameter Gas pipe Liquid pipe BSV4Q100PV1 φ15 9 φ9 5 BSV6Q100PV1 Indoor unit Indoor unit Indoor unit Refrigerant branch kit Downstream Upstream BS unit Gas pipe Liquid pipe Liquid pipe Suction gas pipe HP LP gas pipe To refriger...

Page 12: ...20 C When reinforcing the insulation material for the installation environment also reinforce the insulation on the piping protruding from the unit and on the pipe connections Locally purchase the insulation required for the reinforcement work When one indoor unit with a capacity of 20 to 50 is connected downstream Suction gas pipe Site piping HP LP gas pipe Site piping Liquid pipe Site piping Uni...

Page 13: ... breaker capable of shutting down the power supply to the entire system must be installed This system consists of multiple BS units Mark each BS unit as unit A unit B and be sure the terminal board wiring to the outdoor unit and indoor unit are properly matched If wiring and piping between the out door unit BS unit and an indoor unit are mismatched the system may cause a malfunction Do not turn on...

Page 14: ...tions Specifications for local wiring are in compliance with IEC60245 Use wire type H05VV U3G for power supply wiring And the size must comply with local codes Use vinyl cord with sheath or cable 2 wire of 0 75 1 25mm 2 for transmission wiring Table 3 MCA Min Circuit Amps A MFA Max Fuse Amps A NOTES The above Table 3 of Electrical Characteristics refers to one BS unit See the Engineering data book...

Page 15: ...the included clamps 2 to securely hold the wires in 2 places NOTE Check that the piping line coincides with the transmission wiring Power supply wiring and ground wire Remove the EL COMPO BOX lid and connect the power supply wiring to the power terminal block X1M Also connect the ground wire to the ground wire terminal Pass both the power supply wire and the ground wire together through the wire t...

Page 16: ...ansmission wiring to pick up electric noise external noise and result in a malfunction or breakdown After the wiring working is complete use sealer field supply to seal closed the wire through hole Entry by small animals etc could cause a malfunction As shown on the right hand side wrap the transmission wiring between each BS unit and indoor unit with a finishing tape field supply together with th...

Page 17: ... BS unit For information regarding the setting method refer to Engineering data book The following table gives a list of the MODE NO FIRST CODE NO and SECOND CODE NO NOTES This setting is operated by the operation remote controller while the indoor unit power is turned on When the indoor unit outdoor unit and BS unit installation work is completed confirm that it is safe even with the power turned...

Page 18: ... 0907 HT 3P194121 4J EM09A001A 00_CV_3P194121 4J fm Page 2 Saturday May 23 2009 2 44 PM ...

Reviews: