6
English
〈
Hanging bracket: For supporting the connection pipe
〉
•
Be sure to support the connection piping around the unit using hanging brackets that are kept within
1 meter of the body side surface. Hanging excessive weight on the BS unit hanging bracket could cause the
unit to fall and injure someone.
5. BS UNIT INSTALLATION
Use only accessories and parts which are of the designated specification when installing.
(1)
Attach the hooks to the suspension bolts.
Be sure to use the nuts (M8 or M10: 3 pcs, 4 locations) and washers
(For M8: Outside diameter dimension 24 to 28mm, For M10: Outside
diameter 30 to 34mm: 2 pcs, 4 locations) (field supply) from both the
top and bottom sides of the hanging bracket and make sure they are
tightened correctly.
NOTES
•
The BS unit has a top and a bottom, so install it so that the diagonal
lines in the figure 4 are where the top is.
(Failing to do so may prevent the unit from operating properly and increase the volume of the operating
noise.)
<Suspension bolt pitch>
<Example installation>
Note: All the above parts are part to be procured in the field.
Fig. 3
A
495
Anchor
Hanging
bracket
Suspension
bolt
Long nut or
turnbuckle
1m or less
1m or less
Unit proper
Slab
BS unit
A
BSV4Q100PV1
1102
BSV6Q100PV1
1626
(mm)
Washer
(Field supply)
Nut
(Field supply)
BS unit
proper
Hanging
bracket
10 – 15mm
Nut
(Double nut)
(Field supply)
Suspension bolt
(Field supply)
Fig. 4