6-2 Example for the whole system
Power supply
Indoor unit
Indoor unit
Remote controller
Remote controller
Remote controller
Power supply
Outdoor unit
Main
switch
Main
switch
Power supply wiring
Transmission wiring
Fuse or circuit
breaker in accordance
with local and national
codes
BSF4Q unit
BSF4Q unit
Cooling-only
indoor unit
6-3 Power supply circuit, safety device and cable requirements
•
A power supply circuit (refer to Table 6) must be provided for connection of the unit. The circuit must be
protected with safety devices in accordance with local and national codes i.e a fuse, a circuit breaker or a
GFCI.
•
When using residual current operated circuit breakers, be sure to use a high-speed type (0.1 second or
less) 30mA rated residual operating current.
•
Use copper conductors only.
•
Use insulated wire for the power supply.
•
Select the power supply cable type and size in accordance with relevant local and national regulations.
•
Use vinyl cord with sheath or cable (2 cores) of AWG 18 - 16 for transmission wiring.
•
The transmission wire lengths are as follows:
Between the Branch Selector unit and indoor units: Max. 3,280 ft. (1,000 m)
Between the Branch Selector unit and outdoor unit: Max. 3,280 ft. (1,000 m)
Between Branch Selector units: Max. 3,280 ft. (1,000 m)
Total wiring length: 6,560 ft. (2,000 m) or less
Table 6
Units
Power supply
Model
Type
Hz
Voltage
Voltage range
Min.
Max.
MCA
MOP
BSF4Q54TVJ
VJ
60
208/230
187
253
0.4
15
BSF6Q54TVJ
0.6
BSF8Q54TVJ
0.8
MCA: Minimum Circuit Ampacity (A); MOP: Maximum Overcurrent Protective Device (A)
NOTES
•
The above Table 6 of electrical characteristics refers to one Branch Selector unit.
18