6
NOTE
The SECOND CODE NO. is factory set to "01".
Do not use any settings not listed in the table.
For group control with a wireless remote controller, initial set-
tings for all the indoor units of the group are equal. (For group
control, refer to the installation manual attached to the indoor
unit for group control.)
6.
TEST OPERATION
• Perform test operation according to the instructions in the
installation manual attached to the indoor unit.
• After refrigerant piping, drain piping, and electric wiring,
operate according to the table to protect the unit.
CAUTION
1. Refer to a malfunction code in the installation manual
attached to the outdoor unit if it does not operate.
2. Refer to the installation manual attached to the outdoor
unit for individual operation system types.
MODE
NO.
FIRST
CODE
NO.
SECOND CODE NO.
01
02
03
10
0
Light
Approx.
2,500 hours
Heavy
Approx.
1,250 hours
—
Approx. 200
hours
Approx. 100
hours
3
Display
Do not display
—
12
(VRV
system)
1
Forced OFF input
ON/OFF
—
2
2°F
1°F
—
Order
Operation
(1)
Open gas side stop valve.
(2)
Open liquid side stop valve.
(3)
Electrify crank case heater for 6 hours.
(4)
Set to cooling with the remote controller and push “
”
button to start operation.
(5)
Push “
” button twice and operate in TEST OPER-
ATION MODE for 3 minutes.
(6)
Push “
” button and confirm its operation.
(7)
Push “
” button and operate normally.
(8)
Confirm its function according to the operation manual.
ON/OFF
TEST
SWING
TEST