Daikin BRC7E83 Installation Manual Download Page 6

6

NOTE

The SECOND CODE NO. is factory set to "01".
Do not use any settings not listed in the table.
For group control with a wireless remote controller, initial set-
tings for all the indoor units of the group are equal. (For group 
control, refer to the installation manual attached to the indoor 
unit for group control.)

6.

TEST OPERATION

• Perform test operation according to the instructions in the 

installation manual attached to the indoor unit.

• After refrigerant piping, drain piping, and electric wiring, 

operate according to the table to protect the unit.

CAUTION

1. Refer to a malfunction code in the installation manual 

attached to the outdoor unit if it does not operate.

2. Refer to the installation manual attached to the outdoor 

unit for individual operation system types.

MODE 

NO.

FIRST 
CODE 

NO.

SECOND CODE NO.

01

02

03

10

0

Light

Approx. 
2,500 hours

Heavy

Approx. 
1,250 hours

Approx. 200 
hours

Approx. 100 
hours

3

Display

Do not display

12 

(VRV 

system)

1

Forced OFF input 

ON/OFF

2

2°F

1°F

Order

Operation

(1)

Open gas side stop valve. 

(2)

Open liquid side stop valve.

(3)

Electrify crank case heater for 6 hours.

(4)

Set to cooling with the remote controller and push “

” 

button to start operation.

(5)

Push “

” button twice and operate in TEST OPER-

ATION MODE for 3 minutes.

(6)

Push “

” button and confirm its operation.

(7)

Push “

” button and operate normally.

(8)

Confirm its function according to the operation manual.

ON/OFF

TEST

SWING

TEST