(4) Press the “

” button to enter the setting.

(5) Push the “

” button to quit the FIELD SET 

MODE and return to the normal display.

 <Multiple settings A/b> 

When the indoor unit is being operating by outside control (cen-
tral remote controller, etc.), it sometimes does not respond to 
ON/OFF and temperature setting commands from this remote 
controller. Check what setting the customer wants and make the 

multiple setting as shown below.

4-7. Stick the Unit No. label at the indoor unit and the back of 

the wireless remote controller.

CAUTION

Set the Unit No. of the receiver and the wireless remote con-
troller to be equal. If the settings differ, the signal from the 
remote controller cannot be transmitted.

5.

FIELD SETTING

If optional accessories are mounted on the indoor unit, the 
indoor unit setting may have to be changed. Refer to the instruc-
tion manual (optional hand book ) for each optional accessory.

Procedure

(1) When in the normal mode, press the “

” but-

ton for at least 4 seconds, and the FIELD SET MODE is  
entered.

(2) Select  the desired MODE NO. with the “

” button.

(3) Push the “

” button and select the FIRST CODE NO..

(4) Push the “

” button and select the SECOND CODE 

NO..

(5) Push the“

”button and the  present settings 

are set.

(6) Push the “

” button to quit the FIELD SET 

MODE and return to the normal display.

(Example) If the time to clean air filter is set to “Filter Con-

tamination-Heavy”, set Mode No. to “10”, FIRST 
CODE NO. to "0", and SECOND CODE NO. to 
“02”.

Remote controller

Indoor unit

Multiple setting

Remote control-
ler display

To control other 
air conditions 
and units

For other than 
on left

A: Standard

All items dis-
played.

Commands other 
than ON/OFF 
and temperature 
setting accepted. 
(1 LONG BEEP 
or 3 SHORT 
BEEPS emitted)

b: Multi System

Operations remain 
displayed shortly 
after execution

All commands accepted.
(2 SHORT BEEPS)

RESERVE

TEST

Unit No. label (7)

Wireless remote
controller (4)

MODE 

NO.

FIRST 
CODE 

NO.

DESCRIPTION OF SETTING

10

0

Filter Contamination-Heavy/Light 
(Setting for spacing time of display 
time to clean air filter) (Setting for 
when filter contamination is heavy, 
and spacing time of display time to 
clean air filter is to be halved)

Long-life type

Standard type

3

Spacing time of display time to clean air filter count 
(Setting for when the filter sign is not to be displayed)

12 

(VRV 

system)

1

ON/OFF input from outside (Set to enable starting/
stopping from remote.)

2

Thermostat differential changeover (Set when using 
remote controller thermostat sensor.)

MODE

TIMER

RESERVE CANCEL

DOWN

UP

 TEST

SWING

FAN

TIME

TEMP

ON OFF

SETTING

MODE NO.

SECOND CODE NO.

FIRST CODE NO.

FIELD SET MODE

(3)

(5)

(2)

(1) (6)

(4)

TEST

MODE

UP

DOWN

RESERVE

TEST