OH12-01
Remote Controller (Wireless Type)
Control Systems
175
2
3P107423-1B
English
4
2. Setting the address of wireless remote controller (It is factory set to “ 1 ” )
“Setting from the remote controller”
1.
Hold down the
button and the
button for at
least 4 seconds to get the Field Set mode.
(Indicated in the display area in the figure at right.)
2.
Press the
button and select a multiple setting (A/
b). Each time the button is pressed the display switches
between “A” and “b”.
3.
Press the “
”
button and “
”
button to set the
address.
Address can be set from 1 to 6, but set it to 1 ~ 3 and to
same address as the receiver. (The receiver does not work
with address 4 ~ 6.)
4.
Press the
button to enter the setting.
5.
Hold down the
button for at least 1 second to quit
the Field Set mode and return to the normal display.
Multiple settings A/b
When the indoor unit is being operating by outside control (central remote controller, etc.), it sometimes does
not respond to ON/OFF and temperature setting commands from this remote controller. Check what setting
the customer wants and make the multiple setting as shown below.
3.
Stick the Unit No. label on the air outlet of the
decoration panel and the back of the wireless
remote controller.
[PRECAUTIONS]
Set the Unit No. of the receiver and the wireless
remote controller to be equal. If the settings differ,
the signal from the remote controller cannot be
transmitted.
Remote controller
Movement when the operation is controlled by the
other air conditioners and equipment
Multiple setting
Remote controller display
A: Standard
All items displayed.
When operation changeover, temperature setting or
the like is carried out from the remote controller, the
indoor unit rejects the instruction.
(Signal receiving sound “peeh” or “pick-pick-pick”)
As a result, a discrepancy between the operation
state of the indoor unit and the indication of the
remote controller display occurs.
b: Multi System
Operations remain dis-
played shortly after exe-
cution.
Since the indication of the remote controller is turned
off, no discrepancy such as mentioned above occurs.
MODE
TIMER
RESERVE CANCEL
DOWN
UP
/TEST
SWING
FAN
TIME
TEMP
ON
OFF
SETTING
Mode
3
2
4
1
Address
Multiple setting
5
/TEST
FAN
UP
DOWN
1
2
3
4
5
6
RESERVE
/TEST
Unit No. label
Wireless remote controller
Decoration
panel
1
.8
B
R
C
7
E
5
3
0
W
/
B
R
C
7
E
5
3
1
W