6. BEV UNIT INSTALLATION

• Use only accessories and parts which are of the designated specification when installing.

(1) Temporarily install the BEV unit.

• Mount the hanging fittings to hanging bolts. Secure the 

hanging fittings on the top and the bottom with nuts (M8, 
field supplied) and washers (M8: Outside diameter size 
24 to 28mm) (field supplied).

(2) Adjust the height of the main unit with the nut.

(3) Check that the main unit is installed on the level.

(4) Tighten the nut on both the top and the bottom to fix securely.

7. REFRIGERANT PIPING WORK

To Piping Work Contractors

Do not use flux at the time of brazing and connecting refrigerant pipes. Use phosphorus-copper (BCuP-2) 
brazing alloy, which requires no flux.
(Chlorine-based flux causes piping corrosion. Furthermore, if fluoride is contained, the flux will have adverse 
influences on the refrigerant piping line, such as the deterioration of refrigerating machine oil.)

7-1 SELECTION OF PIPES

• Refer to the installation manual for the outdoor unit and decide on the size of each pipe and select a suitable 

refrigerant branching kit.

• Use the following type of refrigerant pipe.

Material: Phosphorus deoxidized seamless copper pipe (C1220T-1/2H or C1220T-H)
Pipe wall thickness: Product withstanding 12.3 MPa

Pipe wall thickness examples

(length: mm)

• Be sure to use pipes with clean outer and inner surfaces free of contaminants, such as sulfides, oxides, 

dust, chip, oil and fat, and moisture.
It is desirable that the adhesion oil in the piping system does not exceed 30mg per 10m.

• Conduct piping work within the maximum permissible length, permissible difference in height, and permis-

sible length after branching specified in “

7-6 PIPING CONNECTION PROCEDURE

”.

7-2 INSTALLATION TOOLS

Be sure to use dedicated tools so that the air conditioner will maintain proper pressure resistance and 
the contamination of impurities will be prevented.

Compatibility with conventional tools (other refrigerants)

Pipe size (outer diameter)

Quality of material

Minimum wall thickness

φ

6.4

1/2H

0.8

φ

9.5

1/2H

1.0

φ

12.7

1/2H

1.3

φ

15.9

1/2H

1.8

Name

Compatibility

Remarks

Pipe cutter

• Use a cutter suitable to the piping thickness.

Pipe bender

• Use a different elbow sold as an optional accessory if the bending radius needs to be 

reduced.

• Use a different elbow sold as an optional accessory for the bending portions of pipes 

with a diameter of 15.9mm.

Expander 
(pipe expansion tool)

• Use a different socket sold as an optional accessory for pipes with a diameter of 

15.9mm, however, due to difficulty in expanding them.

BEV main unit

Hanging fitting

Washer 
(field supplied)

Nut (field supplied)

Double nut 

(field supplied)

Hanging bolt 
(field supplied)

01_EN_3P233622-3F.fm  Page 6  Monday, December 22, 2008  10:59 AM

Summary of Contents for BEVN125AV1

Page 1: ...DE MAIN POUR REFERENCE ULTERIEURE LEA CUIDADOSAMENTE ESTAS INSTRUCCIONES ANTES DE INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE...

Page 2: ...urata Manager Quality Control Department 1st of October 2008 DAIKIN TCF 024C19 07 2008 T V Rheinland EPS B V 0510260101 RXYN10AY1 FXSN20AV1 FXSN25AV1 FXSN32AV1 FXSN40AV1 FXSN50AV1 FXSN63AV1 FXSN100AV1...

Page 3: ...nnel to carry out installation work Do not attempt to install the air conditioner yourself Improper installation may result in water leakage electric shocks or fire Install the air conditioner in acco...

Page 4: ...an earth leakage breaker Failure to install an earth leakage breaker may result in electric shocks or fire CAUTION Install the BEV units power cord and connecting wires at least 1 meter away from tele...

Page 5: ...5 9mm Use sockets sold as optional accessories Elbows Use products sold as optional accessories Installation instruments that must withstand high pressures such as charge hoses and pressure gauges Use...

Page 6: ...not exposed to rain or direct sunlight places with little dust or places with an ambient temperature of 60 C or below Where is resistible against weight of BEV unit Where the false ceiling is not noti...

Page 7: ...ing refrigerant and wiring including both power supply and transmission wiring up to the piping and wiring connections in the unit See 7 REFRIGERANT PIPING WORK and 8 ELECTRIC WIRING WORK for details...

Page 8: ...oduct withstanding 12 3 MPa Pipe wall thickness examples length mm Be sure to use pipes with clean outer and inner surfaces free of contaminants such as sulfides oxides dust chip oil and fat and moist...

Page 9: ...giving an adverse influence on a variety of valves and the compressor in the refrigerant system and obstructing the normal operation of the air con ditioner At the time of brazing with nitrogen being...

Page 10: ...tting 3 upward Use a clamp 2 to tighten both ends of the insulation for fitting Refer to Fig 4 Attached to the root Insulation for fitting 3 accessory Insulation for fitting 3 accessory Attached to th...

Page 11: ...r unit and BEV unit are properly matched If wiring and piping between the outdoor unit and an indoor unit and BEV unit are mismatched the system may cause a mal function A circuit breaker capable of s...

Page 12: ...he outdoor unit to ter minals F1 and F2 for the outdoor side of the first BEV unit 1 Model Units Power supply Hz Voltage Min Max MCA MFA BEVN32AV1 BEVN50AV1 BEVN125AV1 50 230 207 253 0 1 15 Model Powe...

Page 13: ...ground wire so that the cup washer will come out of the cutout part Otherwise the effect of grounding may be lost due to the insufficient contact of the ground wire Transmission wiring can be branche...

Page 14: ...supply wires into the equipment along with the ground wire through the wiring through hole and bundle and fix the wires securely with the accessory clamp 1 Clasp Clasp Clasp Ground terminal EL COMPO B...

Page 15: ...MPO BOX lid pay the utmost attention so that the wires will not be caught between the EL COMPO BOX lid After the wires are connected seal the wiring extraction part with putty or heat insulation mater...

Page 16: ...0901 HT 3P233622 3F EM08A070B...

Reviews: