2-4 CHECK ITEM

FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND CHECK 
AFTER INSTALLATION IS FINISHED.

Items to be checked after completion of work

Also review the “SAFETY PRECAUTIONS”.

3. BEFORE INSTALLATION

Do not throw away accessories required for installation work until the installation of the product is completed.

Carry the product to the place of installation without unpacking. Be careful not to damage the units if it is 
unavoidable to unpack them in advance.

4. SELECTING INSTALLATION SITE

〈〈

When moving the unit while removing it from the carton box, be sure to lift it by holding on to the 

four lifting lugs without exerting any pressure on other parts, especially, the refrigerant piping.
When it may exceed 30

°

C and RH80% in the ceiling or fresh air is inducted into the ceiling, an addi-

tional insulation (Thickness 10mm or more of glasswool or polyethylene form) is required.

〉〉

(1) Select an installation site where the following conditions are fulfilled and that meets your cus-

tomer’s approval.

• Install the product in buildings that use gypsum boards (9.5mm thick or more) for ceiling materials because 

the product generates the flowing sound of refrigerant. It is recommended to install the product away from 
places or rooms where the sound is annoying. Refer to the following sketch to select a suitable place of 
installation.

• Indoors, places not exposed to rain or direct sunlight, places with little dust, or places with an ambient 

temperature of 60°C or below.

• Where is resistible against weight of BEV unit.
• Where the false ceiling is not noticeably on an incline.
• Where there is no risk of flammable gas leakage.
• Where sufficient clearance for maintenance and service can be ensured.
• Where the total piping length involving indoor unit and outdoor unit is below the allowable piping length.

(See the installation manual included with the outdoor unit for “

7-4 PIPING CONNECTIONS

”.)

• Locations where a maintenance hole can be installed. 

(Refer to Fig. 1)

Items to be checked

If not properly done, what is likely to occur

Check

Are the indoor and outdoor unit fixed firmly?

The units may drop, vibrate or make noise.

Is the gas leak test finished? 

It may result in insuffcient cooling.

Is the insulation complete? (Refrigerant piping)

Water leaking or burn.

Does the power supply voltage correspond to that shown on the name plate?

The unit may malfunction or the components burn out.

Are wiring and piping correct?

The unit may malfunction or the components burn out.

Is the unit safely grounded?

Risk of electric shock at electric leakage.

Is wiring size according to specifications?

The unit may malfunction or the components burn out.

Are refrigerant piping length and additional refrigerant charge noted down?

The refrigerant charge in the system is not clear.

0.1m

Xm

Gypsum board (9.5mm thick)
ISO6308 conforming product

• Location of microphone

(B.G.N. is already rectified)

• Overall (dB)

35

5.0m

37

3.0m

40

1.5m

SCALE A

Distance from BEV

X

01_EN_3P233622-3F.fm  Page 4  Monday, December 22, 2008  10:59 AM

Summary of Contents for BEVN125AV1

Page 1: ...DE MAIN POUR REFERENCE ULTERIEURE LEA CUIDADOSAMENTE ESTAS INSTRUCCIONES ANTES DE INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE...

Page 2: ...urata Manager Quality Control Department 1st of October 2008 DAIKIN TCF 024C19 07 2008 T V Rheinland EPS B V 0510260101 RXYN10AY1 FXSN20AV1 FXSN25AV1 FXSN32AV1 FXSN40AV1 FXSN50AV1 FXSN63AV1 FXSN100AV1...

Page 3: ...nnel to carry out installation work Do not attempt to install the air conditioner yourself Improper installation may result in water leakage electric shocks or fire Install the air conditioner in acco...

Page 4: ...an earth leakage breaker Failure to install an earth leakage breaker may result in electric shocks or fire CAUTION Install the BEV units power cord and connecting wires at least 1 meter away from tele...

Page 5: ...5 9mm Use sockets sold as optional accessories Elbows Use products sold as optional accessories Installation instruments that must withstand high pressures such as charge hoses and pressure gauges Use...

Page 6: ...not exposed to rain or direct sunlight places with little dust or places with an ambient temperature of 60 C or below Where is resistible against weight of BEV unit Where the false ceiling is not noti...

Page 7: ...ing refrigerant and wiring including both power supply and transmission wiring up to the piping and wiring connections in the unit See 7 REFRIGERANT PIPING WORK and 8 ELECTRIC WIRING WORK for details...

Page 8: ...oduct withstanding 12 3 MPa Pipe wall thickness examples length mm Be sure to use pipes with clean outer and inner surfaces free of contaminants such as sulfides oxides dust chip oil and fat and moist...

Page 9: ...giving an adverse influence on a variety of valves and the compressor in the refrigerant system and obstructing the normal operation of the air con ditioner At the time of brazing with nitrogen being...

Page 10: ...tting 3 upward Use a clamp 2 to tighten both ends of the insulation for fitting Refer to Fig 4 Attached to the root Insulation for fitting 3 accessory Insulation for fitting 3 accessory Attached to th...

Page 11: ...r unit and BEV unit are properly matched If wiring and piping between the outdoor unit and an indoor unit and BEV unit are mismatched the system may cause a mal function A circuit breaker capable of s...

Page 12: ...he outdoor unit to ter minals F1 and F2 for the outdoor side of the first BEV unit 1 Model Units Power supply Hz Voltage Min Max MCA MFA BEVN32AV1 BEVN50AV1 BEVN125AV1 50 230 207 253 0 1 15 Model Powe...

Page 13: ...ground wire so that the cup washer will come out of the cutout part Otherwise the effect of grounding may be lost due to the insufficient contact of the ground wire Transmission wiring can be branche...

Page 14: ...supply wires into the equipment along with the ground wire through the wiring through hole and bundle and fix the wires securely with the accessory clamp 1 Clasp Clasp Clasp Ground terminal EL COMPO B...

Page 15: ...MPO BOX lid pay the utmost attention so that the wires will not be caught between the EL COMPO BOX lid After the wires are connected seal the wiring extraction part with putty or heat insulation mater...

Page 16: ...0901 HT 3P233622 3F EM08A070B...

Reviews: