background image

IM 1248 • BACNET THERMOSTAT 4 

www .DaikinApplied .com

I

nsTallaTIon

 G

uIde

 – H

eaT

 P

umP

Connecting Outputs

 WARNING

Can cause equipment damage .

Improperly connecting loads or equipment to output terminals 

may damage the equipment . Connect only as shown in the 

following diagrams or application drawings . 

The BACnet Thermostat outputs are product dependent and 

are configured for specific applications.

• 

No field programming or set up is required or possible.

•  Depending on model and application, the BACnet 

Thermostat outputs are designed for either 24 volt AC or 

0-10 volt DC loads .

•  The outputs may represent analog or digital signals .

Figure 5: Heat Pump Output Terminals    

Connecting Power

The BACnet Thermostat requires an external, 24 volt AC 

power source . Use the following guidelines when choosing 

and wiring transformers .

•  Use only a Class-2 transformer of the appropriate size to 

supply power .

•  Daikin Applied recommends powering the BACnet 

Thermostat from a dedicated controls transformer .

• 

Connect the transformer’s neutral lead to the COM 

terminal .

•  Connect the AC phase lead to the 24VAC terminal .
•  Power is applied to the controller when the transformer 

is powered .

Figure 6: Wiring for BACnet Thermostat Power    