IM 1248 • BACNET THERMOSTAT

Installing the BACnet Thermostat

To install the controller on a mounting base, do the following:

1 .  Turn the Allen screw in the base of the sensor clockwise 

until it clears the case (

Figure 2

) .

2 .  Swing the BACnet Thermostat away from the mounting 

base to remove it .

3 .  Route wiring for the BACnet Thermostat through the 

mounting base .

4 .  Position the base with the embossed UP toward the 

ceiling and fasten it directly to a vertical 2 × 4 inch 

electrical box . 

5 .  Connect the wires for the BACnet Thermostat to the 

terminals in the mounting base .

6 .  Place the top of the sensor over the top of the mounting 

base and swing it down over the Allen screw bracket . Be 

careful not to pinch any wiring .

7 .  Turn the Allen screw counterclockwise until it backs out 

of the mounting base and engages the case (

Figure 3

) .

Figure 2:  Removing Allen Screw from Base    

 

Figure 3: Reconnecting Allen Screw to Base     

Connecting Inputs

The inputs for the BACnet Thermostat are configured for 

specific functions and do not require set up in the field. Not all 

inputs are required for every application .

Figure 4: Heat Pump Inputs  

 

Remote Space Temperature Sensor (optional)

Connect a 10kΩ, Type II thermistor temperature sensor to 

the remote space temperature (RS) input and ground (GND) 

terminals . The input includes the internal pull-up resistor . 

Follow the instructions supplied with the sensor for installation . 
When a remote space temperature input is connected to the 

BACnet Thermostat, the remote temperature is used instead of 

the internal temperature sensor .

Fan Status Switch (optional)

Connect a Normally Closed Fan Status switch to the Discharge 

Air Temperature (DAT) input and ground (GND) terminals . 

The input includes the internal pull-up resistor . Follow the 

instructions supplied with the switch for installation .

Outside Air Temperature

Connect a 10kΩ, Type II thermistor temperature probe to the 

outside air temperature (OAT) input . The input includes the 

internal pull-up resistor . Follow the instructions supplied with 

the sensor for installation .

Discharge Air Temperature

Connect a 10kΩ, Type II thermistor temperature probe to the 

discharge air temperature (DAT) input . The input includes the 

internal pull-up resistor . Follow the instructions supplied with 

the sensor for installation .