I
nsTallaTIon
G
uIde
– H
eaT
P
umP
www .DaikinApplied .com
5
IM 1248 • BACNET THERMOSTAT
Maintenance
Remove dust as necessary from the holes in the top and bottom .
Clean the display with a soft, damp cloth and mild soap .
Specifications
BACnet Thermostat specifications are subject to change
without notice .
Supply Voltage:
24 volts AC (-15%, +20%)
50-60 Hz, 12 VA,
Class 2 only
Inputs:
0-12 volts DC with internal 10kΩ pull-up resistors
Relay Outputs:
SPST, 24 volts, 1 amp AC or DC
Maximum for all relay outputs is 3 amps
Analog Outputs:
Short protected 10mA 0-12 VDC
Environmental Limits:
Operating 34 to 125°F (1 .1 to 51 .6°C)
Shipping -40 to 140°F (-40 to 60°C)
Humidity 0 to 95% RH (non-condensing)
Regulatory:
UL 916 Energy Management Equipment
FCC Class A, Part 15 Subpart B and complies with
Canadian ICES-003 Class A
This device complies with part 15 of the FCC Rules . Operation
is subject to the following two conditions: (1) This device may
not cause harmful interference, and (2) this device must accept
any interference received, including interference that may
cause undesired operation .
Additional Resources
For detailed specifications, installation, operating, application,
and system integration information, see
IM 1234 BACnet
Thermostat
Installation and Operation Manual .