Maintenance

Remove dust as necessary from the holes in the top and bottom . 

Clean the display with a soft, damp cloth and mild soap .

Specifications

BACnet Thermostat specifications are subject to change 

without notice .

Supply Voltage:

24 volts AC (-15%, +20%)
50-60 Hz, 12 VA,
Class 2 only

Inputs:

0-12 volts DC with internal 10kΩ pull-up resistors

Relay Outputs:

SPST, 24 volts, 1 amp AC or DC
Maximum for all relay outputs is 3 amps

Analog Outputs:

Short protected 10mA 0-12 VDC

Environmental Limits:

Operating 34 to 125°F (1 .1 to 51 .6°C)
Shipping -40 to 140°F (-40 to 60°C)
Humidity 0 to 95% RH (non-condensing)

Regulatory:

UL 916 Energy Management Equipment
FCC Class A, Part 15 Subpart B and complies with 

Canadian ICES-003 Class A

This device complies with part 15 of the FCC Rules . Operation 

is subject to the following two conditions: (1) This device may 

not cause harmful interference, and (2) this device must accept 

any interference received, including interference that may 

cause undesired operation .

Additional Resources

For detailed specifications, installation, operating, application, 

and system integration information, see 

IM 1234 BACnet 

Thermostat

 Installation and Operation Manual .