10

6.

Drain piping.

1) Connect the drain hose, as described right.

2) Remove the air filters and pour some water into the drain pan to check the water 

flows smoothly.

3) When drain hose requires extension, obtain an extension hose commercially avail-

able. 
Be sure to thermally insulate the indoor section of the extension hose.

4) When connecting a rigid polyvinyl chloride pipe 

(nominal diameter 13mm) directly to the drain 
hose attached to the indoor unit as with embed-
ded piping work, use any commercially available 
drain socket (nominal diameter 13mm) as a 
joint.

Refrigerant Piping Work

, install as described in the installation manual supplied with the Multi outdoor unit.

1.

Flaring the pipe end.

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing downward 

so that the chips do not enter the pipe.

3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.

WARNING

1) Do not use mineral oil on flared part.
2) Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
3) Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
4) Do never install a drier to this R410A unit in order to guarantee its lifetime.
5) The drying material may dissolve and damage the system.
6) Incomplete flaring may cause refrigerant gas leakage.

The drain hose should

be inclined downward.

No trap is permitted.

Do not put the end

of the hose in water.

 

  

φ

   

    

 

     

   

    

 

    

    

    

    

φ

With a multi indoor unit

Set exactly at the position shown below.

A

Flaring

Die

A

0-0.5mm

Clutch-type

Flare tool for R410A

1.0-1.5mm

Clutch-type (Rigid-type)

1.5-2.0mm

Wing-nut type (Imperial-type)

Conventional flare tool

(Cut exactly at

right angles.)

Remove burrs

Check

Flare’s inner

surface must

be flaw-free.

The pipe end must

be evenly flared in

a perfect circle.

Make sure that the

flare nut is fitted.

01_EN_3P212421-1.fm  Page 10  Wednesday, September 26, 2007  5:57 PM

Summary of Contents for ATXS20E2V1B

Page 1: ...an ais Nederlands Espa ol Italiano Portugues Installation manual R410A Split series Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montagehandleiding R410A Split s...

Page 2: ...6 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Dai...

Page 3: ...amping may cause terminal overheating or fire After connecting interconnecting and supply wiring be sure to shape the cables so that they do not put undue force on the electrical covers or panels Inst...

Page 4: ...m electronic ignition type fluorescent lamps inverter or rapid start type as they may shorten the remote control range 8 the unit is at least 1 metre away from any television or radio set unit may cau...

Page 5: ...ter 2 Remove the front grille 3 In front of the mark of the front grille there are 3 upper hooks Lightly pull the front grille toward you with one hand and push down on the hooks with the fingers of y...

Page 6: ...con trollers can be set for different addresses 1 In the same way as when connecting to an HA system remove the metal plate electrical wiring cover 2 Cut the address jumper JA on the printed circuit b...

Page 7: ...finishing tape from bottom to top Cut thermal insulation pipe to an appropriate length and wrap it with tape making sure that no gap is left in the insulation pipe s cut line Caulk pipe hole gap with...

Page 8: ...and Dimensions 80 100 400 135 450 283 47 5 141 5 50 5 46 5 44 5 131 5 87 44 5 110 60 130 220 50 60 110 800 65 65 Use tape measure as shown Position the end of a tape measure at Keep here the piece cu...

Page 9: ...e and refrigerant pipes through the wall hole then set the indoor unit on the mounting plate hooks by using the markings at the top of the indoor unit as a guide 4 Open the front panel then open the s...

Page 10: ...atch indoor unit press the bottom edge of indoor unit with both hands until it is firmly caught by the mounting plate hooks Secure indoor unit to the mounting plate with screws M4 12L 3 3 Wall embedde...

Page 11: ...rds or starburst connections as they may cause overheating electrical shock or fire 2 Do not use locally purchased electrical parts inside the product Do not branch the power for the drain pump etc fr...

Page 12: ...e pipe 5 Check that the flaring is properly made WARNING 1 Do not use mineral oil on flared part 2 Prevent mineral oil from getting into the system as this would reduce the lifetime of the units 3 Nev...

Page 13: ...efrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide in...

Page 14: ...turned off 1 3 Carry out the test operation in accordance with the Operation Manual to ensure that all functions and parts such as louver movement are working properly The air conditioner requires a...

Page 15: ...0710 HT 3P212421 1 M07B075 Two dimensional bar code is a code for manufacturing 00_CV_3P212421 1 fm Page 2 Friday July 20 2007 2 31 PM...

Reviews: