Test Run and Final Check
1.
Trial operation and testing.
1-1 Measure the supply voltage and make sure that it falls in the specified range.
1-2 Trial operation should be carried out in either cooling or heating mode.
For heat pump
• In cooling mode, select the lowest programmable temperature; in heating mode, select the highest programmable
temperature.
1) Trial operation may be disabled in either mode depending on the room temperature.
2) After trial operation is complete, set the temperature to a normal level (26°C to 28°C in cooling mode, 20°C to 24°C in
heating mode).
3) For protection, the system disables restart operation for 3 minutes after it is turned off.
For cooling only
1) Trial operation in cooling mode may be disabled depending on the room temperature.
2) After trial operation is complete, set the temperature to a normal level (26
C to 28
C).
3) For protection, the unit disables restart operation for 3 minutes after it is turned off.
1-3 Carry out the test operation in accordance with the operation manual to ensure that all functions and parts,
such as louver movement, are working properly.
• The air conditioner requires a small amount of power in its standby mode. If the system is not to be used for some
time after installation, shut off the circuit breaker to eliminate unnecessary power consumption.
• If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original operation
mode when the circuit breaker is opened again.
2.
Test items.
Test items
Symptom
(diagnostic display on RC)
Check
Indoor and outdoor units are installed properly on solid bases.
Fall, vibration, noise
No refrigerant gas leaks.
Incomplete cooling/heating
function
Refrigerant gas and liquid pipes and indoor drain hose extension are
thermally insulated.
Water leakage
Draining line is properly installed.
Water leakage
System is properly earthed.
Electrical leakage
The specified wires are used for interconnecting wire connections.
Inoperative or burn damage
Indoor or outdoor unit’s air intake or exhaust has clear path of air.
Stop valves are opened.
Incomplete cooling/heating
function
Indoor unit properly receives remote control commands.
Inoperative
Summary of Contents for ARXN25N5V1B9
Page 2: ......
Page 62: ...1 R410A...
Page 63: ...2 70 A A 1 1 B...
Page 64: ...3 1 2 3 4 5 6 7 3 3 8 9 1 2 3 4...
Page 65: ...4 1 5 20 250 9 5 6 4 20 10 20 10 1 5 1 5 470 96 300...
Page 66: ...5 1200 8 10 20 1 1 2 2 1 2 30 3 50 100 1200 50 50 100 150 300 50 150 20 16...
Page 68: ...7 5 1 R410A 2 3 R410A 4 R410A 4 1 2 Lo Hi 3 0 1 76 1 4 Lo 2 5 6 90 5 7 8...
Page 69: ...8 1 2 2 4 6 R410A 1 R410A 20 10 R410A GWP 2087 5 GWP R410A...
Page 71: ...10 1 2 3 4 3 5 1 20 2 1 2 3 1 2 3 L N 16 10 2 0 H05RN 50 220 240 2 0 1 2 3 1 2 3 1 3 A B A B...
Page 73: ...12 1 1 1 1 2 1 2 26 C 28 C 20 C 24 C 3 3 1 2 26 C 28 C 3 3 1 3 2...
Page 86: ...11 1 1 1 2 1 1 24 20 28 26 2 3 3 1 28 26 2 3 3 3 1 2 RC...
Page 88: ...1 2 3 1 2 3 L N 16 10 2 0 H05RN 2 0 1 2 3 1 2 3 l 1 3 A B A B 9 1 2 3 4 5 1 2 50 240 220...
Page 89: ...8 1 1 2 3 15 1 2 3 4 30 1 2...
Page 91: ...5 6 R410A a b R410A c R410A d 1 2 MPa 76cmHg 10 1 3 4 2 5 90 6 5 7 8 1 2 4 20 10...
Page 93: ...100 1200 20 16 4 1200 50 50 50 100 150 150 300 50 M10 M8 20 1 1 2 2 1 2 3 3 1 2 3 4 5...
Page 94: ...O D 9 5 20 20 470 96 300 3 1 5 10 10 O D 6 4 1 5 20...
Page 95: ...dB A 70 1 2 3 4 5 6 7 8 9 1 2 3 4 2...
Page 96: ...8 R410A 1...
Page 97: ......
Page 98: ......
Page 99: ......