13 Disposal
Installer reference guide
70
ERLQ004~008CA + 08S18CB
Daikin Altherma – Low temperature split
4P401676-1 – 2015.02
Pump down operation will extract all refrigerant from the system into
the outdoor unit.
1
Remove the valve lid from liquid stop valve and gas stop valve.
2
Carry out the forced cooling operation.
3
After 5 to 10 minutes (after only 1 or 2 minutes in case of very
low ambient temperatures (<−10°C)), close the liquid stop valve
with a hexagonal wrench.
4
Check with the manifold if the vacuum is reached.
5
After 2-3 minutes, close the gas stop valve and stop forced
cooling operation.
a
c
b
d
d
e
a
Gas stop valve
b
Closing direction
c
Hexagonal wrench
d
Valve lid
e
Liquid stop valve
13.3
To start and stop forced cooling
Confirm that DIP switch SW2 is in COOL mode.
1
Press the forced cooling operation switch SW1 to begin forced
cooling.
2
Press the forced cooling operation switch SW1 to stop forced
cooling.
SW1
HEAT COOL
SW2
NOTICE
Take care that while running forced cooling operation, the
water temperature remains higher than 5°C (see
temperature read out of the indoor unit). You can achieve
this, for example, by activating all fans of the fan coil units.