![Daikin Altherma ERLQ004-006-008CA Reference Manual Download Page 101](http://html1.mh-extra.com/html/daikin/altherma-erlq004-006-008ca/altherma-erlq004-006-008ca_reference-manual_4121628101.webp)
5/8
Breadcrumb
Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
└─
Backup heater
A.5.1.1
[4-00]
R/W
0: Disabled
1: Enabled
2: Only DHW
A.5.1.2
R/W
0: Manual
1: Automatic
A.5.1.4
[5-01]
R/W
-15~35°C, step: 1°C
0°C
└─
System operation
└─
Auto restart
A.6.1
[3-00]
R/W
0: No
1: Yes
└─
Preferential kWh rate
A.6.2.1
[D-00]
R/W
0~3
0: None
2: BUH only
A.6.2.2
[D-05]
R/W
0: Forced off
1: As normal
└─
Pwr consumpt. Control
A.6.3.1
[4-08]
R/W
0: No limitation
1: Continuous
2: Digital inputs
A.6.3.2
[4-09]
R/W
0: Current
1: Power
A.6.3.3
[5-05]
R/W
0~50 A, step: 1 A
50 A
A.6.3.4
[5-09]
R/W
0~20 kW, step: 0,5 kW
20 kW
A.6.3.5.1
[5-05]
Amp. limits for DI
Limit DI1
R/W
0~50 A, step: 1 A
50 A
A.6.3.5.2
[5-06]
Amp. limits for DI
Limit DI2
R/W
0~50 A, step: 1 A
50 A
A.6.3.5.3
[5-07]
Amp. limits for DI
Limit DI3
R/W
0~50 A, step: 1 A
50 A
A.6.3.5.4
[5-08]
Amp. limits for DI
Limit DI4
R/W
0~50 A, step: 1 A
50 A
A.6.3.6.1
[5-09]
kW limits for DI
Limit DI1
R/W
0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.2
[5-0A]
kW limits for DI
Limit DI2
R/W
0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.3
[5-0B]
kW limits for DI
Limit DI3
R/W
0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.4
[5-0C]
kW limits for DI
Limit DI4
R/W
0~20 kW, step: 0,5 kW
20 kW
A.6.3.7
[4-01]
R/W
0~2
0: None
2: BUH
└─
Averaging time
A.6.4
[1-0A]
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
└─
Ext amb. sensor offset
A.6.5
[2-0B]
R/W
-5~5°C, step: 0,5°C
0°C
└─
Boiler efficiency
A.6.A
[7-05]
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
└─
Overview settings
A.8
[0-00]
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
35°C
A.8
[0-01]
R/W
[9-05]~[9-06]°C, step: 1°C
45°C
A.8
[0-02]
R/W
10~25°C, step: 1°C
15°C
A.8
[0-03]
R/W
-40~5°C, step: 1°C
-10°C
A.8
[0-04]
R/W
8
A.8
[0-05]
R/W
12
A.8
[0-06]
R/W
35
A.8
[0-07]
R/W
20
A.8
[0-0B]
R/W
35~[6-0E]°C, step: 1°C
55°C
A.8
[0-0C]
R/W
45~[6-0E]°C, step: 1°C
6
0°C
A.8
[0-0D]
R/W
10~25°C, step: 1°C
15°C
A.8
[0-0E]
R/W
-40~5°C, step: 1°C
-10°C
A.8
[1-00]
R/W
-40~5°C, step: 1°C
-10°C
A.8
[1-01]
R/W
10~25°C, step: 1°C
15°C
A.8
[1-02]
R/W
[9-01]~[9-00], step: 1°C
35°C
A.8
[1-03]
R/W
[9-01]~min(45, [9-00])°C , step: 1°C
25°C
A.8
[1-04]
R/W
1
A.8
[1-05]
R/W
1
A.8
[1-06]
R/W
20
A.8
[1-07]
R/W
35
A.8
[1-08]
R/W
22
A.8
[1-09]
R/W
18
A.8
[1-0A]
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
Operation mode
Emergency
Equilibrium temp.
Allowed heaters
Forced pump OFF
Mode
Type
Amp. value
kW value
Priority
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
--
--
--
--
Leaving water value for high ambient temp. for DHW WD curve.
Leaving water value for low ambient temp. for DHW WD curve.
High ambient temp. for DHW WD curve.
Low ambient temp. for DHW WD curve.
Low ambient temp. for LWT main zone heating WD curve.
High ambient temp. for LWT main zone heating WD curve.
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
--
--
--
--
--
--
What is the averaging time for the outdoor temp?
(*5) *04/08*
(*6) *16*
4P401673-1 - 2015.04