8 Configuration
Installer reference guide
51
ERLQ004~008CA + 08S18CB
Daikin Altherma – Low temperature split
4P401676-1 – 2015.02
#
Code
Description
[A.4.7]
[0-0E]
[0-0D]
[0-0C]
[0-0B]
Weather-dependent curve
T
DHW
T
a
[0-0C]
[0-0B]
[0-0E]
[0-0D]
▪ T
DHW
: The desired tank temperature.
▪ T
a
: The (averaged) outdoor ambient
temperature
▪ [0-0E]:
low
outdoor
ambient
temperature: –40°C~5°C (default: –
10°C)
▪ [0-0D]:
high
outdoor
ambient
temperature:
10°C~25°C
(default:
15°C)
▪ [0-0C]: desired tank temperature when
the outdoor temperature equals or
drops
below
the
low
ambient
temperature: 45°C~[6‑0E]°C (default:
60°C)
▪ [0-0B]: desired tank temperature when
the outdoor temperature equals or
rises
above
the
high
ambient
temperature: 35°C~[6‑0E]°C (default:
55°C)
Limits on heat pump operation
In domestic hot water operation, following hysteresis values can be
set for the heat pump operation:
#
Code
Description
N/A
[6-00]
The temperature difference determining
the heat pump ON temperature.
Range: 2°C~20°C (default: 2°C)
N/A
[6-01]
The temperature difference determining
the heat pump OFF temperature.
Range: 0°C~10°C (default: 2°C)
Example:
t
T
DHW
T
HP ON
T
HP OFF
T
HP MAX
T
U
=
T
BUH OFF
[6-01]
[6-00]
T
U
= 60°C
T
HP MAX
= 50°C
[6-01] = 2°C
[6-00] = 2°C
HP
BUH
HP
5
10
20
30
40
46
48
50
60
BUH
Backup heater
HP
Heat pump. If heating up time by the heat pump takes too
long, auxiliary heating by the backup heater can take place
T
BUH OFF
Backup heater OFF temperature (T
U
)
T
HP MAX
Maximum heat pump temperature at sensor in domestic
hot water tank
T
HP OFF
Heat pump OFF temperature (T
HP MAX
−[6-01])
T
HP ON
Heat pump ON temperature (T
HP OFF
−[6-00])
T
DHW
Domestic hot water temperature
T
U
User set point temperature (as set on the user interface)
t
Time
Timers for simultaneous request space and domestic hot water
operation
#
Code
Description
N/A
[8-00]
Do not change. (default: 1)
N/A
[8-01]
Maximum running time for domestic hot
water operation. Domestic hot water
heating stops even when the target
domestic hot water temperature is NOT
reached. The actual maximum running
time also depends on setting [8‑04].
▪ When
system
layout
=
Room
thermostat control: This preset value is
only taken into account if there is a
request for space heating. If there is
NO request for space heating, the tank
is heated until the setpoint has been
reached.
▪ When
system
layout
≠
Room
thermostat control: This preset value is
always taken into account.
Range: 5~95 minutes (default: 30)
N/A
[8-02]
Anti-recycling time.
Minimum time between two cycles for
domestic hot water. The actual anti-
recycling time also depends on setting
[8‑04].
Range: 0~10 hours (default: 0.5) (step:
0.5 hour).
Remark:
The minimum time is 1/2 hour
even when the selected value is 0.
N/A
[8-04]
Additional running time for the maximum
running time depending on the outdoor
temperature [4‑02].
Range: 0~95 minutes (default: 95).
[8-02]: Anti-recycling time
t
1
0
1
0
[8-01]
[8-02]
[8-00]
1
Heat pump domestic water heating mode (1=active, 0=not
active)
2
Hot water request for heat pump (1=request, 0=no request)
t
Time
[8-04]: Additional running time at [4-02]/[F-01]
t
T
A
0
[8-01]
[5-03]
[4-02]
[8-02]
[8-01]+
[8-04]
T
A
Ambient (outdoor) temperature
t
Time
Anti-recycle time