3 Preparation

Installation manual

6

EPGA11~16DAV3

Daikin Altherma – Low temperature split

4P556065-1 – 2018.10

(10.1 N·m)

2

a

b

c

4

3

1

3

Preparation

3.1

Preparing the installation site

WARNING

The  appliance  shall  be  stored  in  a  room  without
continuously  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater).

3.1.1

Installation site requirements of the
outdoor unit

Mind  the  spacing  guidelines.  See  figure  1  on  the  inside  of  the  front
cover.

The symbols can be interpreted as follows:

A,C

Right side and left side obstacles (walls/baffle plates)

B

Suction side obstacle (wall/baffle plate)

D

Discharge side obstacle (wall/baffle plate)

E

Top side obstacle (roof)

a,b,c,d,e

Minimum service space between the unit and obstacles A,
B, C, D and E

e

B

Maximum distance between the unit and the edge of
obstacle E, in the direction of obstacle B

e

D

Maximum distance between the unit and the edge of
obstacle E, in the direction of obstacle D

H

U

Height of the unit including the installation structure

H

B

,H

D

Height of obstacles B and D

H

Height of installation structure below the unit

The outdoor unit is designed for outdoor installation only, and for the
following ambient temperatures:

Cooling mode

10~43°C

Heating mode

–28~35°C

Special requirements for R32

The  outdoor  unit  contains  an  internal  refrigerant  circuit  (R32),  but
you  do  NOT  have  to  do  any  refrigerant  field  piping,  or  refrigerant
charging.

Mind the following requirements and precautions:

WARNING

▪ Do NOT pierce or burn.

▪ Do  NOT  use  means  to  accelerate  the  defrosting

process  or  to  clean  the  equipment,  other  than  those
recommended by the manufacturer.

▪ Be  aware  that  R32  refrigerant  does  NOT  contain  an

odour.

WARNING

The appliance shall be stored so as to prevent mechanical
damage and in a well-ventilated room without continuously
operating  ignition  sources  (example:  open  flames,  an
operating gas appliance or an operating electric heater).

WARNING

Make  sure  installation,  servicing,  maintenance  and  repair
comply  with  instructions  from  Daikin  and  with  applicable
legislation  (for  example  national  gas  regulation)  and  are
executed only by authorised persons.

4

Installation

4.1

Opening the units

4.1.1

To open the outdoor unit

DANGER: RISK OF ELECTROCUTION

DANGER: RISK OF BURNING

6

5

1

3

4

2

8

9

7

4.2

Mounting the outdoor unit

4.2.1

To provide the installation structure

Prepare  6  sets  of  anchor  bolts,  nuts  and  washers  (field  supply)  as
follows:

Summary of Contents for Altherma EPGA11DAV3

Page 1: ...Installation manual Daikin Altherma Low temperature split English Installation manual Daikin Altherma Low temperature split EPGA11DAV3 EPGA14DAV3 EPGA16DAV3 ...

Page 2: ...HD HU mm A B C 500 100 A B C E 500 150 1000 500 500 D 500 500 D E 1000 500 B D 500 B D E 300 300 300 300 300 1000 150 150 150 150 150 150 150 1000 1000 1000 500 HD HU HD HU HB HU HD HU HB HU a b c d e eB eD A B C D E HB HU HD 1 ...

Page 3: ... с положениями 10 11 12 13 14 15 16 17 18 under iagttagelse af bestemmelserne i enligt villkoren i gitt i henhold til bestemmelsene i noudattaen määräyksiä za dodržení ustanovení předpisu prema odredbama követi a z zgodnie z postanowieniami Dyrektyw în urma prevederilor 19 20 21 22 23 24 25 ob upoštevanju določb vastavalt nõuetele следвайки клаузите на laikantis nuostatų pateikiamų ievērojot prasī...

Page 4: ...rin sallittu lämpötila TS TSmin Alhaisin matalapainepuolen lämpötila L C TSmax Suurinta sallittua painetta PS vastaava kyllästyslämpötila M C Kylmäaine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maximální přípustný tlak PS K bar Minimální maximální přípustná teplota TS TSmin Minimální teplota na nízkotlaké straně L C TSmax Saturovaná teplota odpoví...

Page 5: ...out this document Target audience Authorised installers Documentation set This document is part of a documentation set The complete set consists of Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer The original documentation is written in English All other languages are translations Technical engineering data A subset of the latest te...

Page 6: ...The outdoor unit is designed for outdoor installation only and for the following ambient temperatures Cooling mode 10 43 C Heating mode 28 35 C Special requirements for R32 The outdoor unit contains an internal refrigerant circuit R32 but you do NOT have to do any refrigerant field piping or refrigerant charging Mind the following requirements and precautions WARNING Do NOT pierce or burn Do NOT u...

Page 7: ...d greenhouse gases label 1 Fill in the label as follows RXXX d Contains fluorinated greenhouse gases kg tCO2eq GWP kg 1000 GWP XXX a b c a If a multilingual fluorinated greenhouse gases label is delivered with the unit see accessories peel off the applicable language and stick it on top of a b Total refrigerant charge c Greenhouse gas emissions of the total refrigerant charge expressed as tonnes C...

Page 8: ... the system before it can freeze NOTICE If you add glycol to the water do NOT install freeze protection valves Possible consequence Glycol leaking out of the freeze protection valves Freeze protection by glycol Adding glycol to the water lowers the freezing point of the water The required concentration depends on the lowest expected outdoor temperature and on whether you want to protect the system...

Page 9: ...ry exit points can prevent that all water from indoor piping is drained when the freeze protection valves open NOTICE When freeze protection valves are installed do NOT select a minimum cooling setpoint lower than 8 C 8 C default If lower freeze protection valves can open during cooling operation Consult the installer reference guide of the unit for more detailed information Heater tape field supp...

Page 10: ...ring at the back of the unit b c a a Power supply cable high voltage b Communication cable high voltage c Cable for bottom plate heater optional 3 Inside the unit route the wiring as follows b f a e e d c e e e a Power supply cable b Communication cable c Cable for bottom plate heater optional d Ferrite core e Tie strap f Compressor NOTICE To guarantee electromagnetic compatibility Make sure both ...

Page 11: ...pillary tube h Heat exchanger i Distributor j Service port 5 16 flare k 4 way valve l Muffler m Accumulator n Economiser heat exchanger o Inverter PCB heat sink p Plate heat exchanger E1H Crankcase heater M1C Compressor M1F Upper fan motor M2F Lower fan motor R1T Thermistor outdoor air R2T Thermistor compressor discharge R3T Thermistor compressor suction R4T Thermistor air heat exchanger liquid pi...

Page 12: ...end Legend Field supply Field supply English Translation Optional Optional Part n Part n Description Description A1P Printed circuit board main A2P Printed circuit board noise filter A3P Printed circuit board leakage current A4P Printed circuit board ACS BS1 BS4 A1P Push button switch C1 C4 A1PA2P Capacitor DS1 A1P Dipswitch E1H Crankcase heater E2H Bottom plate heater option E3H E5H Plate heat ex...

Page 13: ...ode V1R A1P IGBT power module V2R A1P Diode module V1T V3T A1P Insulated Gate Bipolar Transistor IGBT X1M Terminal strip Y1E Electronic expansion valve main Y3E Electronic expansion valve injection Y1S Solenoid valve 4 way valve Y2S Solenoid valve hot gas bypass Y3S Solenoid valve injection bypass Z1C Z11C Noise filter ferrite core Z1F Z6F A1P A2P Noise filter ...

Page 14: ......

Page 15: ......

Page 16: ...4P556065 1 2018 10 Copyright 2018 Daikin 4P556065 1 0000000P ...