4 Installation

Installation manual

9

EPGA11~16DAV3
Daikin Altherma – Low temperature split
4P556065-1 – 2018.10

If…

Then…

The system does NOT contain a
domestic hot water tank

You can use either propylene
glycol

(a)

 or ethylene glycol

(a)

Propylene glycol, including the necessary inhibitors,
classified as Category III according to EN1717.

WARNING

Ethylene glycol is toxic.

NOTICE

Glycol  absorbs  water  from  its  environment.  Therefore  do
NOT add glycol that has been exposed to air. Leaving the
cap  off  the  glycol  container  causes  the  concentration  of
water  to  increase.  The  glycol  concentration  is  then  lower
than  assumed.  As  a  result,  the  hydraulic  components
might freeze up after all. Take preventive actions to ensure
a minimal exposure of the glycol to air.

WARNING

Due  to  presence  of  glycol,  corrosion  of  the  system  is
possible.  Uninhibited  glycol  will  turn  acidic  under  the
influence  of  oxygen.  This  process  is  accelerated  by  the
presence  of  copper  and  high  temperatures.  The  acidic
uninhibited  glycol  attacks  metal  surfaces  and  forms
galvanic  corrosion  cells  that  cause  severe  damage  to  the
system. Therefore it is important that:

▪ the water treatment is correctly executed by a qualified

water specialist,

▪ a  glycol  with  corrosion  inhibitors  is  selected  to

counteract acids formed by the oxidation of glycols,

▪ no  automotive  glycol  is  used  because  their  corrosion

inhibitors  have  a  limited  lifetime  and  contain  silicates
which can foul or plug the system,

▪ galvanized pipes are NOT used in glycol systems since

the  presence  may  lead  to  the  precipitation  of  certain
components in the glycol's corrosion inhibitor.

Adding  glycol  to  the  water  circuit  reduces  the  maximum  allowed
water  volume  of  the  system.  For  more  information,  refer  to  the
chapter  "To  check  the  water  volume  and  flow  rate"  in  the  installer
reference guide.

NOTICE

If  glycol  is  present  in  the  system,  setting  [E-0D]  must  be
set to 1. If the glycol setting is NOT set correctly, the liquid
inside the piping can freeze.

Freeze protection by freeze protection valves

When no glycol is added to the water, you can use freeze protection
valves to drain the water from the system before it can freeze.

▪ Install freeze protection valves (field supply) at all lowest points of

the field piping.

▪ Normally closed valves (located indoors near the piping entry/exit

points)  can  prevent  that  all  water  from  indoor  piping  is  drained
when the freeze protection valves open.

NOTICE

When freeze protection valves are installed, do NOT select
a  minimum  cooling  setpoint  lower  than  8°C  (8°C=default).
If  lower,  freeze  protection  valves  can  open  during  cooling
operation.

Consult  the  installer  reference  guide  of  the  unit  for  more  detailed
information.

Heater tape (field supply)

1

Install heater tape to the outdoor field piping.

2

Provide external power supply for the heater tape.

NOTICE

▪ For the internal heater tape to operate, the power to the

unit MUST be ON. For this reason, during cold periods,
never  disconnect  the  power,  nor  turn  off  the  main
switch.

▪ In  case  of  a  power  failure,  power  to  the  heater  tape

(both  internal  and  external)  will  be  aborted  and  the
water circuit will NOT be protected. To guarantee a full
protection,  it  is  always  possible  to  add  glycol  to  the
water  circuit  or  to  use  freeze  protection  valves,  even
when installing heater tape to the outdoor field piping.

4.3.4

To insulate the water piping

The  piping  in  the  complete  water  circuit  MUST  be  insulated  to
prevent  condensation  during  cooling  operation  and  reduction  of  the
heating and cooling capacity.

Outdoor water piping

For  piping  in  free  air,  it  is  recommended  to  use  the  insulation
thickness  as  shown  in  below  table  as  a  minimum  (with  λ=0.039  W/
mK).

Piping length (m)

Minimum insulation thickness
(mm)

<20

19

20~30

32

30~40

40

40~50

50

For other cases the minimum insulation thickness can be determined
using the Hydronic Piping Calculation tool.

The  Hydronic  Piping  Calculation  tool  also  calculates  the  maximum
hydronic piping length from the indoor unit to the outdoor unit based
on the emitter pressure drop or the other way around.

The Hydronic Piping Calculation tool is part of the Heating Solutions
Navigator 

which 

can 

be 

reached 

via 

https://

professional.standbyme.daikin.eu

.

Please  contact  your  dealer  if  you  have  no  access  to  Heating
Solutions Navigator.

This  recommendation  ensures  good  operation  of  the  unit,  however,
local regulations may differ and shall be followed.

4.4

Connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

4.4.1

About electrical compliance

Only for EPGA11~16DAV3

Equipment  complying  with  EN/IEC  61000‑3‑12  (European/
International  Technical  Standard  setting  the  limits  for  harmonic
currents  produced  by  equipment  connected  to  public  low-voltage
systems with input current >16 A and ≤75 A per phase.).

Summary of Contents for Altherma EPGA11DAV3

Page 1: ...Installation manual Daikin Altherma Low temperature split English Installation manual Daikin Altherma Low temperature split EPGA11DAV3 EPGA14DAV3 EPGA16DAV3 ...

Page 2: ...HD HU mm A B C 500 100 A B C E 500 150 1000 500 500 D 500 500 D E 1000 500 B D 500 B D E 300 300 300 300 300 1000 150 150 150 150 150 150 150 1000 1000 1000 500 HD HU HD HU HB HU HD HU HB HU a b c d e eB eD A B C D E HB HU HD 1 ...

Page 3: ... с положениями 10 11 12 13 14 15 16 17 18 under iagttagelse af bestemmelserne i enligt villkoren i gitt i henhold til bestemmelsene i noudattaen määräyksiä za dodržení ustanovení předpisu prema odredbama követi a z zgodnie z postanowieniami Dyrektyw în urma prevederilor 19 20 21 22 23 24 25 ob upoštevanju določb vastavalt nõuetele следвайки клаузите на laikantis nuostatų pateikiamų ievērojot prasī...

Page 4: ...rin sallittu lämpötila TS TSmin Alhaisin matalapainepuolen lämpötila L C TSmax Suurinta sallittua painetta PS vastaava kyllästyslämpötila M C Kylmäaine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maximální přípustný tlak PS K bar Minimální maximální přípustná teplota TS TSmin Minimální teplota na nízkotlaké straně L C TSmax Saturovaná teplota odpoví...

Page 5: ...out this document Target audience Authorised installers Documentation set This document is part of a documentation set The complete set consists of Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer The original documentation is written in English All other languages are translations Technical engineering data A subset of the latest te...

Page 6: ...The outdoor unit is designed for outdoor installation only and for the following ambient temperatures Cooling mode 10 43 C Heating mode 28 35 C Special requirements for R32 The outdoor unit contains an internal refrigerant circuit R32 but you do NOT have to do any refrigerant field piping or refrigerant charging Mind the following requirements and precautions WARNING Do NOT pierce or burn Do NOT u...

Page 7: ...d greenhouse gases label 1 Fill in the label as follows RXXX d Contains fluorinated greenhouse gases kg tCO2eq GWP kg 1000 GWP XXX a b c a If a multilingual fluorinated greenhouse gases label is delivered with the unit see accessories peel off the applicable language and stick it on top of a b Total refrigerant charge c Greenhouse gas emissions of the total refrigerant charge expressed as tonnes C...

Page 8: ... the system before it can freeze NOTICE If you add glycol to the water do NOT install freeze protection valves Possible consequence Glycol leaking out of the freeze protection valves Freeze protection by glycol Adding glycol to the water lowers the freezing point of the water The required concentration depends on the lowest expected outdoor temperature and on whether you want to protect the system...

Page 9: ...ry exit points can prevent that all water from indoor piping is drained when the freeze protection valves open NOTICE When freeze protection valves are installed do NOT select a minimum cooling setpoint lower than 8 C 8 C default If lower freeze protection valves can open during cooling operation Consult the installer reference guide of the unit for more detailed information Heater tape field supp...

Page 10: ...ring at the back of the unit b c a a Power supply cable high voltage b Communication cable high voltage c Cable for bottom plate heater optional 3 Inside the unit route the wiring as follows b f a e e d c e e e a Power supply cable b Communication cable c Cable for bottom plate heater optional d Ferrite core e Tie strap f Compressor NOTICE To guarantee electromagnetic compatibility Make sure both ...

Page 11: ...pillary tube h Heat exchanger i Distributor j Service port 5 16 flare k 4 way valve l Muffler m Accumulator n Economiser heat exchanger o Inverter PCB heat sink p Plate heat exchanger E1H Crankcase heater M1C Compressor M1F Upper fan motor M2F Lower fan motor R1T Thermistor outdoor air R2T Thermistor compressor discharge R3T Thermistor compressor suction R4T Thermistor air heat exchanger liquid pi...

Page 12: ...end Legend Field supply Field supply English Translation Optional Optional Part n Part n Description Description A1P Printed circuit board main A2P Printed circuit board noise filter A3P Printed circuit board leakage current A4P Printed circuit board ACS BS1 BS4 A1P Push button switch C1 C4 A1PA2P Capacitor DS1 A1P Dipswitch E1H Crankcase heater E2H Bottom plate heater option E3H E5H Plate heat ex...

Page 13: ...ode V1R A1P IGBT power module V2R A1P Diode module V1T V3T A1P Insulated Gate Bipolar Transistor IGBT X1M Terminal strip Y1E Electronic expansion valve main Y3E Electronic expansion valve injection Y1S Solenoid valve 4 way valve Y2S Solenoid valve hot gas bypass Y3S Solenoid valve injection bypass Z1C Z11C Noise filter ferrite core Z1F Z6F A1P A2P Noise filter ...

Page 14: ......

Page 15: ......

Page 16: ...4P556065 1 2018 10 Copyright 2018 Daikin 4P556065 1 0000000P ...

Reviews: