8 Configuration
Installation and operation manual
26
EHYKOMB33A
Daikin Altherma hybrid heat pump – gas boiler module
4P353067-1K – 2020.10
Prerequisite:
Check the meaning of the error code (see
36]) and resolve the cause.
1
Press to restart the gas boiler.
Maximum space heating supply temperature
See the user reference guide of the indoor unit for more details.
Domestic hot water temperature
See the user reference guide of the indoor unit for more details.
Keep hot function
The reversible heat pump features a keep hot function that keeps
the heat exchanger hot continuously to prevent sweat from occurring
in the gas boiler switch box.
In case of heating only models, this function can be deactivated
through the parameter settings of the gas boiler.
INFORMATION
Do NOT deactivate the keep hot function if the gas boiler is
connected to a reversible indoor unit. It is recommended to
always deactivate the keep hot function if the gas boiler is
connected to a heating only indoor unit.
Frost protection function
The boiler is equipped with an internal frost protection function that
automatically operates when necessary, even if the boiler is turned
off. If the heat exchanger temperature drops too low, the burner will
switch on until the temperature is sufficiently high again. When frost
protection is active, is displayed on the service display.
To set the parameters via the service code
The gas boiler is factory set in accordance with the default settings.
Take into account the remarks in the table below when changing the
parameters.
1
Press simultaneously on
and
until appears on the main
and the service display.
2
Use the and buttons to set (service code) on the main
display.
3
Press the
button to set the parameter on the service display.
4
Use the and buttons to set the parameter to the desired
value on the service display.
5
When all settings are done, press
until appears on the
service display.
Result:
The gas boiler has now been reprogrammed.
INFORMATION
▪ Press the button to exit the menu without storing the
parameter changes.
▪ Press the
button to load the default settings of the
gas boiler.
Parameters on the gas boiler
Parameter
Setting
Range
Default
settings
Description
Service code
—
—
To access the installer settings, enter
the service code (=15)
Installation type
0~3
0
▪ 0=Combi
▪ 1=Heating only + external domestic
hot water tank
▪ 2=Domestic hot water only (no
heating system required)
▪ 3=Heating only
It is recommended not to modify this
setting.
Space heating pump continuous
0~3
0
▪ 0=Post purge period only
▪ 1=Pump continuously active
▪ 2=Pump continuously active with
MIT switch
▪ 3=Pump on with external switch
This setting has no effect.
Maximum space heating power set
~85%
70%
Maximum power in heating. This is a
percentage of the maximum set in
parameter . We strongly recommend
not modifying this setting.
.
Maximum capacity space heating
pump
—
80
There is no space heating pump in the
gas boiler. Changing this setting has
no effect.
Maximum domestic hot water power
set
(not applicable for Switzerland)
~100%
100%
Maximum power in instant domestic
hot water. This is a percentage of the
maximum set in parameter . Because
of the 2-digit display, the highest
displayable value is 99. It is however
possible to set this parameter to 100%
(default setting). We strongly
recommend not modifying this setting.