
2/8
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
User settings
└─
Preset values
└─
Room temperature
7.4.1.1
R/W
[3-07]~[3-06], step: A.3.2.4
22°C
7.4.1.2
R/W
[3-07]~[3-06], step: A.3.2.4
18°C
7.4.1.3
R/W
[3-09]~[3-08], step: A.3.2.4
24°C
7.4.1.4
R/W
[3-09]~[3-08], step: A.3.2.4
28°C
└─
LWT main
7.4.2.1
[8-09]
R/W
[9-01]~[9-00], step: 1°C
35°C
7.4.2.2
[8-0A]
R/W
[9-01]~[9-00], step: 1°C
33°C
7.4.2.3
[8-07]
R/W
[9-03]~[9-02], step: 1°C
18°C
7.4.2.4
[8-08]
R/W
[9-03]~[9-02], step: 1°C
20°C
└─
Tank temperature
7.4.3.1
[6-0A]
R/W
30~[6-0E]°C, step: 1°C
60°C
7.4.3.2
[6-0B]
R/W
30~min(50, [6-0E])°C, step: 1°C
50°C
7.4.3.3
[6-0C]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
└─
Quiet level
7.4.4
R/W
1: Level 1
2: Level 2
3: Level 3
└─
Set weather dependent
└─
Main
└──────────────────
Set weather-dependent heating
7.7.1.1
[1-00]
Set weather-dependent heating
Low ambient temp. for LWT main zone heating
WD curve.
R/W
-40~5°C, step: 1°C
-10°C
7.7.1.1
[1-01]
Set weather-dependent heating
High ambient temp. for LWT main zone heating
WD curve.
R/W
10~25°C, step: 1°C
15°C
7.7.1.1
[1-02]
Set weather-dependent heating
Leaving water value for low ambient temp. for
LWT main zone heating WD curve.
R/W
[9-01]~[9-00], step: 1°C
35°C
7.7.1.1
[1-03]
Set weather-dependent heating
Leaving water value for high ambient temp. for
LWT main zone heating WD curve.
R/W
[9-01]~min(45, [9-00])°C, step: 1°C
25°C
└──────────────────
Set weather-dependent Cooling
7.7.1.2
[1-06]
Set weather-dependent Cooling Low ambient temp. for LWT main zone cooling
WD curve.
R/W
10~25°C, step: 1°C
20°C
7.7.1.2
[1-07]
Set weather-dependent Cooling High ambient temp. for LWT main zone cooling
WD curve.
R/W
25~43°C, step: 1°C
35°C
7.7.1.2
[1-08]
Set weather-dependent Cooling Leaving water value for low ambient temp. for
LWT main zone cooling WD curve.
R/W
[9-03]~[9-02]°C, step: 1°C
22°C
7.7.1.2
[1-09]
Set weather-dependent Cooling Leaving water value for high ambient temp. for
LWT main zone cooling WD curve.
R/W
[9-03]~[9-02]°C, step: 1°C
18°C
└─
Additional
└──────────────────
Set weather-dependent heating
7.7.2.1
[0-03]
Set weather-dependent heating
Low ambient temp. for LWT add zone heating
WD curve.
R/W
-40~5°C, step: 1°C
-10°C
7.7.2.1
[0-02]
Set weather-dependent heating
High ambient temp. for LWT add zone heating
WD curve.
R/W
10~25°C, step: 1°C
15°C
7.7.2.1
[0-01]
Set weather-dependent heating
Leaving water value for low ambient temp. for
LWT add zone heating WD curve.
R/W
[9-05]~[9-06]°C, step: 1°C
50°C
7.7.2.1
[0-00]
Set weather-dependent heating
Leaving water value for high ambient temp. for
LWT add zone heating WD curve.
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
35°C
└──────────────────
Set weather-dependent Cooling
7.7.2.2
[0-07]
Set weather-dependent Cooling Low ambient temp. for LWT add zone cooling
WD curve.
R/W
10~25°C, step: 1°C
20°C
7.7.2.2
[0-06]
Set weather-dependent Cooling High ambient temp. for LWT add zone cooling
WD curve.
R/W
25~43°C, step: 1°C
35°C
7.7.2.2
[0-05]
Set weather-dependent Cooling Leaving water value for low ambient temp. for
LWT add zone cooling WD curve.
R/W
[9-07]~[9-08]°C, step: 1°C
12°C
7.7.2.2
[0-04]
Set weather-dependent Cooling Leaving water value for high ambient temp. for
LWT add zone cooling WD curve.
R/W
[9-07]~[9-08]°C, step: 1°C
8°C
Installer settings
└─
System layout
└─
Standard
A.2.1.1
[E-00]
R/O
0~5
0: LT split
A.2.1.2
[E-01]
R/O
0
A.2.1.3
[E-02]
R/W (*1)
R/O (*2)
0: Reversible (*1)
1: Heating only (*2)
A.2.1.7
[C-07]
R/W
0: LWT control
1: Ext RT control
2: RT control
A.2.1.9
[F-0D]
R/W
0: Continuous
1: Sample
2: Request
A.2.1.A
[E-04]
R/O
1: Yes
A.2.1.B
R/W
0: At unit
1: In room
└─
Options
A.2.2.1
[E-05]
R/O
0~1
1. Yes
A.2.2.3
[E-07]
R/O
0~6
1: Integrated
A.2.2.4
[C-05]
R/W
0: -
1: 1 contact
2: 2 contacts
A.2.2.A
[D-02]
R/W
0: No
1: Secondary rtrn
2: Disinf. Shunt
A.2.2.B
[C-08]
R/W
0: No
1: Outdoor sensor
2: Room sensor
A.2.2.G
R/W
0: No
1: Yes
Pump operation mode
User interface location
Which type of DHW pump is installed?
LAN Adapter
DHW operation
DHW tank type
Thermostat Type
External sensor
Unit type
Compressor type
Indoor software type
Power saving possible
Eco (cooling)
Storage comfort
Storage eco
Reheat
Unit control method
Comfort (heating)
Eco (heating)
Comfort (cooling)
Field settings table
Installer setting at variance with
default value
Comfort (heating)
Eco (heating)
Comfort (cooling)
Eco (cooling)
4P596814-1B - 2022.09
(*1) Only applicable for models where cooling is possible
(*2) EHFH03S18D
▲
3V
▼