
15
|
Disposal
Installer reference guide
195
E EHFH03S18D
Daikin Altherma 3 R F
4P596806-1C – 2022.09
15 Disposal
NOTICE
Do NOT try to dismantle the system yourself: dismantling of the system, treatment of
the refrigerant, oil and other parts MUST comply with applicable legislation. Units
MUST be treated at a specialised treatment facility for reuse, recycling and recovery.
In this chapter
15.1 Overview: Disposal
Typical workflow
Disposing of the system typically consists of the following stages:
1
Pumping down the system.
2
Bringing the system to a specialized treatment facility.
INFORMATION
For more details, see the service manual.
15.2 To pump down
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage.
If you want to pump down the system, and there
is a leak in the refrigerant circuit:
▪
Do NOT use the unit's automatic pump down function, with which you can collect
all refrigerant from the system into the outdoor unit.
Possible consequence:
Self-
combustion and explosion of the compressor because of air going into the
operating compressor.
▪
Use a separate recovery system so that the unit's compressor does NOT have to
operate.
NOTICE
During pump down operation, stop the compressor before removing the refrigerant
piping. If the compressor is still running and the stop valve is open during pump
down, air will be sucked into the system. Compressor breakdown or damage to the
system can result due to abnormal pressure in the refrigerant cycle.
NOTICE
Before pump down.
Before using the unit's automatic pump down function, set
[C-07]=0 (or [A.2.1.7]:
>
Installer settings
>
System layout
>
Standard
>
Unit control method
=
LWT control
)
Pump down operation will extract all refrigerant from the system into the outdoor
unit (compressor module).
1
Remove the valve cap from the liquid stop valve and the gas stop valve.