background image

4 Installation

Installation manual

9

EBLQ+07CAV3
Daikin Altherma low temperature monobloc
4P403578-1C – 2016.02

WARNING

Due  to  presence  of  glycol,  corrosion  of  the  system  is
possible.  Uninhibited  glycol  will  turn  acidic  under  the
influence  of  oxygen.  This  process  is  accelerated  by  the
presence  of  copper  and  high  temperatures.  The  acidic
uninhibited  glycol  attacks  metal  surfaces  and  forms
galvanic  corrosion  cells  that  cause  severe  damage  to  the
system. Therefore it is important that:

▪ the water treatment is correctly executed by a qualified

water specialist,

▪ a  glycol  with  corrosion  inhibitors  is  selected  to

counteract acids formed by the oxidation of glycols,

▪ no  automotive  glycol  is  used  because  their  corrosion

inhibitors  have  a  limited  lifetime  and  contain  silicates
which can foul or plug the system,

▪ galvanized pipes are NOT used in glycol systems since

the  presence  may  lead  to  the  precipitation  of  certain
components in the glycol's corrosion inhibitor.

Adding  glycol  to  the  water  circuit  reduces  the  maximum  allowed
water  volume  of  the  system.  For  more  information,  refer  to  the
chapter  "To  check  the  water  volume  and  flow  rate"  in  the  installer
reference guide.

4.3.3

To fill the water circuit

1

Connect the water supply hose to the drain and fill valve.

2

Open the drain and fill valve.

3

If  an  automatic  air  purge  valve  was  installed,  make  sure  it  is
open.

4

Fill  the  circuit  with  water  until  the  manometer  (field  supply)
indicates a pressure of ±2.0 bar.

5

Purge  as  much  air  as  possible  from  the  water  circuit.  For
instructions, see 

"6 Commissioning" on page 18

.

6

Refill the circuit until the pressure is ±2.0 bar.

7

Repeat steps 5 and 6 until no more air is purged and there are
no more pressure drops.

8

Close the drain and fill valve.

9

Disconnect the water supply hose from the drain and fill valve.

4.3.4

To insulate the water piping

The  piping  in  the  complete  water  circuit  MUST  be  insulated  to
prevent  condensation  during  cooling  operation  and  reduction  of  the
heating and cooling capacity.

To  prevent  the  freezing  of  the  outdoor  water  piping  during  winter
time, the thickness of the sealing material MUST be at least 13 mm
(with λ=0.039 W/mK).

If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher
than RH 80%, the thickness of the insulation materials should be at
least  20  mm  to  prevent  condensation  on  the  surface  of  the
insulation.

During  winter,  protect  the  water  piping  and  shut‑off  valves  against
freezing  by  adding  heat  tape  (field  supply).  If  the  outdoor
temperature  can  drop  below  –20°C  and  no  heat  tape  is  used,  it  is
recommended to install the shut‑off valves indoors.

4.4

Connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

4.4.1

To connect the electrical wiring on the
outdoor unit

1

Remove the switch box cover. See 

"4.1.1 To open the outdoor

unit" on page 5

.

2

Insert the wiring from the back of the unit:

a

b
c

≥25 mm

a

Low voltage

b

High voltage

c

Main power supply

NOTICE

The  distance  between  the  high  voltage  and  low  voltage
cables should be at least 25 mm.

Routing

Possible cables (depends on the installed options)

a

Low voltage

▪ User interface

▪ Interconnection cable to control box EKCB07CAV3

▪ Remote outdoor sensor (option)

Summary of Contents for Altherma EDLQ05CAV3

Page 1: ...Installation manual Daikin Altherma low temperature monobloc English Installation manual Daikin Altherma low temperature monobloc EBLQ05CAV3 EBLQ07CAV3 EDLQ05CAV3 EDLQ07CAV3...

Page 2: ...mi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputama 16 1...

Page 3: ...ture Overview installer settings 17 6 Commissioning 18 6 1 Checklist before commissioning 18 6 2 Checklist during commissioning 18 6 2 1 To perform an air purge 18 6 2 2 To perform a test run 19 6 2 3...

Page 4: ...o check the water volume and flow rate Minimum water volume If Then The system contains a backup heater The minimum water volume is 10 l a The system does NOT contain a backup heater The minimum water...

Page 5: ...75 mm d Cable section 0 75 mm till 1 25 mm maximum length 20 m e If valve kit EKMBHBP1 is part of the system then the required cable section is 0 75 mm If valve kit EKMBHBP1 is NOT part of the system...

Page 6: ...e unit Additionally make sure the unit is positioned at least 100 mm above the maximum expected level of snow mm 1 5 0 1 5 0 a 330 300 283 7 4 0 0 mm 100 a Maximum snowfall height It is possible to in...

Page 7: ...condensate may also form in the hydro part When providing drainage therefore make sure to cover the entire unit NOTICE If the unit is installed in a cold climate take adequate measures so that the eva...

Page 8: ...e piping from freezing Protection against freezing the glycol will prevent the liquid inside the piping from freezing Lowest expected outdoor temperature Prevent from bursting Prevent from freezing 5...

Page 9: ...ter circuit For instructions see 6 Commissioning on page 18 6 Refill the circuit until the pressure is 2 0 bar 7 Repeat steps 5 and 6 until no more air is purged and there are no more pressure drops 8...

Page 10: ...power supply 1 Connect the main power supply 1 2 3 X4M 2 3 1 1 GND 2 L 3 N 4 4 3 To connect the user interface INFORMATION If control box EKCB07CAV3 is NOT part of the system connect the user interfa...

Page 11: ...ted to the outdoor unit However if control box EKCB07CAV3 is present in the system you can also connect it to the control box To do this connect outdoor unit terminals X3M 1 2 to control box terminals...

Page 12: ...r more than 1 hour or press again for more than 4 seconds the installer permission level switches back to End user To set the user permission level to Advanced end user 1 Go to the main menu or any of...

Page 13: ...See also illustrations below Domestic hot water pump installed for Instant hot water Disinfection c f a g h b c h b a d f e g a Outdoor unit b Tank c Domestic hot water pump d Heater element e Non ret...

Page 14: ...nction between the detection of an alarm and the detection of a power failure See also table below Alarm output logic A 2 2 F 3 D 08 Optional external kWh meter 1 0 No NOT installed 1 Installed 0 1 pu...

Page 15: ...g water In case a minimum temperature difference is required for the good operation of the heat emitters in heating mode A 3 1 3 2 9 0A Cooling required temperature difference between entering and lea...

Page 16: ...cool down cycle 5 2 6 Domestic hot water control Code Description A 4 1 6 0D Domestic hot water Type 0 Reheat only Only reheat operation is allowed 1 Reheat sched Same as 2 but between the scheduled h...

Page 17: ...ones Pump operation mode Power saving possible User interface location Options DHW pump External sensor Control box Option box Leaving water Main Additional Delta T source Room thermostat Room temp ra...

Page 18: ...r heater Booster heater circuit breaker F2B on the switch box of the control box is turned ON The correct pipe size is installed and the pipes are properly insulated There are no water leaks inside th...

Page 19: ...eaving water temperature home page room temperature home page and domestic hot water home page are turned OFF 1 Set the user permission level to Installer See To set the user permission level to Insta...

Page 20: ...lation to maintaining the unit Explain the user about energy saving tips as described in the operation manual 7 1 About locking and unlocking If required it is possible to lock the buttons of the main...

Page 21: ...door unit See the internal wiring diagram supplied with the unit on the inside of the outdoor unit switch box cover The abbreviations used are listed below Position in switch box hydro switch box A1P...

Page 22: ...M L PCB3 PCB2 PCB1 GRN GRN GRN RED RED RED RED 1 S502 2 3 4 5 6 7 8 9 10 11 S503 1 2 3 4 5 S501 1 2 3 4 5 SW5 SW2 SW1 SW3 A 1 2 3 4 DB1 DB2 HL402 HN402 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 1 2 3 4 5 6 7...

Page 23: ...L1 HN1 30A V3 S10 3 2 1 MR30_A MR30_B 1 2 S20 S50 1 2 3 4 5 1 2 3 4 DP2 DP1 MR307 MR306 FU1 T3 15A V401 DB401 1 2 3 4 5 6 1 2 3 4 1 2 3 4 5 6 7 WHT YLW ORG BLU RED Y1E M S1NPH S60 S90 S40 R3T t R2T t...

Page 24: ...A X7A X21A K4R K6R X10A X14A X15A X18A 1 2 3 4 5 3 1 1 3 1 2 A1P TR1 M1P S1L N L GND PWM PE MS 3 t t t R3T R4T R1T X10A X1A X5M X3M X5Y A2P 4 3 4 3 2 1 2 1 X2M 23 X2M 22 X2M 21 X2M 20 X8M 9 X8M 8 X8M...

Page 25: ...onvector only for wireless On OFF thermostat 4D094176 1C_Page 8 User interface Remote user interface Option box DHW pump output Max load 2 A inrush 230 V AC 1 A continuous DHW pump Dual setpoint appli...

Page 26: ...PCB A3P On OFF thermostat PC power circuit A3P Heat pump convector A4P Extension PCB control optional A5P User interface PCB A7P Receiver PCB wireless On OFF thermostat B1L Flow sensor C110 C112 Capac...

Page 27: ...mistor air R1H A3P Humidity sensor R4T A1P Inlet water thermistor R5T Domestic hot water thermistor R6T A1P External outdoor ambient thermistor R6T A4P External indoor ambient thermistor S1L Flow swit...

Page 28: ...a 2 Only for heat pump convector Only for KRTR wireless room thermostat Only for KRTW wired room thermostat 2 core 3m included signal R2T External sensor floor or ambient Only for KRTETS External indo...

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ...4P403578 1C 2016 02 Copyright 2015 Daikin...

Reviews: