5 Configuration
Installation manual
16
EBLQ+07CAV3
Daikin Altherma low temperature monobloc
4P403578-1C – 2016.02
a
+[8-06]
−[8-06]
b
Ta
Tt
a
Weather-dependent curve
b
Minimum leaving water temperature setpoint required to
reach a stable condition on the comfort setpoint for the
room.
Leaving water temperature: Emitter type
#
Code
Description
[A.3.1.1.7]
[9-0B]
Reaction time of the system:
▪ 0: Quick.
Example:
Small water
volume and fan coils.
▪ 1: Slow.
Example:
Large water
volume, floor heating loops.
Depending on the system water volume
and the heat emitters type, the heat up
or cool down of a space can take
longer. This setting can compensate for
a slow or a quick heating/cooling
system by adjusting the unit capacity
during the heat up/cool down cycle.
5.2.6
Domestic hot water control
#
Code
Description
[A.4.1]
[6-0D]
Domestic hot water Type:
▪ 0 (Reheat only): Only reheat operation
is allowed.
▪ 1 (Reheat + sched.): Same as 2, but
between the scheduled heatup cycles,
reheat operation is allowed.
▪ 2 (Scheduled only): The domestic hot
water tank can ONLY be heated
according to a schedule.
[A.4.5]
[6-0E]
The maximum temperature that users
can select for the domestic hot water.
You can use this setting to limit the
temperature at the hot water taps.
INFORMATION
There is a risk of space heating (cooling) capacity
shortage/comfort problem (in case of frequent domestic hot
water operation, frequent and long space heating/cooling
interruption will happen) when selecting [6‑0D]=0 ([A.4.1]
Domestic hot water Type=Reheat only) in case of a
domestic hot water tank without an internal booster heater.
5.2.7
Contact/helpdesk number
#
Code
Description
[6.3.2]
N/A
Number that users can call in case of
problems.