4 Installation

Installation manual

8

EBLQ+07CAV3

Daikin Altherma low temperature monobloc

4P403578-1C – 2016.02

4.3

Connecting the water piping

4.3.1

To connect the water piping

NOTICE

Do  NOT  use  excessive  force  when  connecting  the  piping.
Deformation of the piping can cause malfunctioning of the
unit.  Make  sure  that  the  tightening  torque  does  NOT
exceed 30 N•m.

To facilitate service and maintenance, 2 shut-off valves are provided.
Mount  the  valves  on  the  water  inlet  and  on  the  water  outlet.  Mind
their  position:  the  integrated  drain  valves  will  only  drain  the  side  of
the  circuit  on  which  they  are  located.  To  be  able  to  only  drain  the
unit, make sure the drain valves are positioned between the shut‑off
valves and the unit.

a

b

a

Water inlet

b

Water outlet

1

Screw the outdoor unit nuts on the shut-off valves.

2

Connect the field piping on the shut-off valves.

3

In case of connection with the optional domestic hot water tank,
see the installation manual of the domestic hot water tank.

NOTICE

▪ Install a manometer in the system.

▪ Install air purge valves at all local high points.

4.3.2

To protect the water circuit against
freezing

Frost can damage the system. To prevent the hydraulic components
from  freezing,  the  software  is  equipped  with  special  frost  protection
functions, that include the activation of pump, internal heaters, and/
or backup heater operation in case of low temperatures.

However,  in  case  of  a  power  failure,  these  functions  cannot
guarantee  protection.  It  is  therefore  recommended  to  add  glycol  to
the water circuit. The required concentration depends on the lowest
expected  outdoor  temperature,  and  on  whether  you  want  to  protect
the  system  from  bursting  or  from  freezing.  To  prevent  the  system
from  freezing,  more  glycol  is  required.  Add  glycol  according  to  the
table below.

INFORMATION

▪ Protection  against  bursting:  the  glycol  will  prevent  the

piping  from  bursting,  but  NOT  the  liquid  inside  the
piping from freezing.

▪ Protection  against  freezing:  the  glycol  will  prevent  the

liquid inside the piping from freezing.

Lowest expected
outdoor
temperature

Prevent from
bursting

Prevent from
freezing

–5°C

10%

15%

–10°C

15%

25%

–15°C

20%

35%

–20°C

25%

–25°C

30%

NOTICE

▪ The  required  concentration  might  differ  depending  on

the type of glycol. ALWAYS compare the requirements
from the table above with the specifications provided by
the  glycol  manufacturer.  If  necessary,  meet  the
requirements set by the glycol manufacturer.

▪ The  added  concentration  of  glycol  should  NEVER

exceed 35%.

▪ If the liquid in the system is frozen, the pump will NOT

be  able  to  start.  Mind  that  if  you  only  prevent  the
system from bursting, the liquid inside might still freeze.

▪ In  case  of  a  power  supply  failure  or  pump  failure,  and

NO glycol was added to the system, drain the system.

▪ When  water  is  at  standstill  inside  the  system,  the

system is very likely to freeze and get damaged.

The types of glycol that can be used depend on whether the system
contains a domestic hot water tank:

If…

Then…

The system contains a domestic
hot water tank

Only use propylene glycol

(a)

The system does NOT contain a
domestic hot water tank

You can use either propylene
glycol

(a)

 or ethylene glycol

(a)

Propylene glycol, including the necessary inhibitors,
classified as Category III according to EN1717.

WARNING

Ethylene glycol is toxic.

NOTICE

Glycol  absorbs  water  from  its  environment.  Therefore  do
NOT add glycol that has been exposed to air. Leaving the
cap  off  the  glycol  container  causes  the  concentration  of
water  to  increase.  The  glycol  concentration  is  then  lower
than  assumed.  As  a  result,  the  hydraulic  components
might freeze up after all. Take preventive actions to ensure
a minimal exposure of the glycol to air.

NOTICE

▪ If overpressure occurs, the system will release some of

the liquid through the pressure relief valve. If glycol was
added to the system, take adequate measures so as to
safely recover it.

▪ In  any  case,  make  sure  that  the  flexible  hose  of  the

pressure  relief  valve  is  ALWAYS  free  to  release
pressure.  Prevent  water  from  staying  and/or  freezing
up inside the hose.

Summary of Contents for Altherma EDLQ05CAV3

Page 1: ...Installation manual Daikin Altherma low temperature monobloc English Installation manual Daikin Altherma low temperature monobloc EBLQ05CAV3 EBLQ07CAV3 EDLQ05CAV3 EDLQ07CAV3...

Page 2: ...mi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputama 16 1...

Page 3: ...ture Overview installer settings 17 6 Commissioning 18 6 1 Checklist before commissioning 18 6 2 Checklist during commissioning 18 6 2 1 To perform an air purge 18 6 2 2 To perform a test run 19 6 2 3...

Page 4: ...o check the water volume and flow rate Minimum water volume If Then The system contains a backup heater The minimum water volume is 10 l a The system does NOT contain a backup heater The minimum water...

Page 5: ...75 mm d Cable section 0 75 mm till 1 25 mm maximum length 20 m e If valve kit EKMBHBP1 is part of the system then the required cable section is 0 75 mm If valve kit EKMBHBP1 is NOT part of the system...

Page 6: ...e unit Additionally make sure the unit is positioned at least 100 mm above the maximum expected level of snow mm 1 5 0 1 5 0 a 330 300 283 7 4 0 0 mm 100 a Maximum snowfall height It is possible to in...

Page 7: ...condensate may also form in the hydro part When providing drainage therefore make sure to cover the entire unit NOTICE If the unit is installed in a cold climate take adequate measures so that the eva...

Page 8: ...e piping from freezing Protection against freezing the glycol will prevent the liquid inside the piping from freezing Lowest expected outdoor temperature Prevent from bursting Prevent from freezing 5...

Page 9: ...ter circuit For instructions see 6 Commissioning on page 18 6 Refill the circuit until the pressure is 2 0 bar 7 Repeat steps 5 and 6 until no more air is purged and there are no more pressure drops 8...

Page 10: ...power supply 1 Connect the main power supply 1 2 3 X4M 2 3 1 1 GND 2 L 3 N 4 4 3 To connect the user interface INFORMATION If control box EKCB07CAV3 is NOT part of the system connect the user interfa...

Page 11: ...ted to the outdoor unit However if control box EKCB07CAV3 is present in the system you can also connect it to the control box To do this connect outdoor unit terminals X3M 1 2 to control box terminals...

Page 12: ...r more than 1 hour or press again for more than 4 seconds the installer permission level switches back to End user To set the user permission level to Advanced end user 1 Go to the main menu or any of...

Page 13: ...See also illustrations below Domestic hot water pump installed for Instant hot water Disinfection c f a g h b c h b a d f e g a Outdoor unit b Tank c Domestic hot water pump d Heater element e Non ret...

Page 14: ...nction between the detection of an alarm and the detection of a power failure See also table below Alarm output logic A 2 2 F 3 D 08 Optional external kWh meter 1 0 No NOT installed 1 Installed 0 1 pu...

Page 15: ...g water In case a minimum temperature difference is required for the good operation of the heat emitters in heating mode A 3 1 3 2 9 0A Cooling required temperature difference between entering and lea...

Page 16: ...cool down cycle 5 2 6 Domestic hot water control Code Description A 4 1 6 0D Domestic hot water Type 0 Reheat only Only reheat operation is allowed 1 Reheat sched Same as 2 but between the scheduled h...

Page 17: ...ones Pump operation mode Power saving possible User interface location Options DHW pump External sensor Control box Option box Leaving water Main Additional Delta T source Room thermostat Room temp ra...

Page 18: ...r heater Booster heater circuit breaker F2B on the switch box of the control box is turned ON The correct pipe size is installed and the pipes are properly insulated There are no water leaks inside th...

Page 19: ...eaving water temperature home page room temperature home page and domestic hot water home page are turned OFF 1 Set the user permission level to Installer See To set the user permission level to Insta...

Page 20: ...lation to maintaining the unit Explain the user about energy saving tips as described in the operation manual 7 1 About locking and unlocking If required it is possible to lock the buttons of the main...

Page 21: ...door unit See the internal wiring diagram supplied with the unit on the inside of the outdoor unit switch box cover The abbreviations used are listed below Position in switch box hydro switch box A1P...

Page 22: ...M L PCB3 PCB2 PCB1 GRN GRN GRN RED RED RED RED 1 S502 2 3 4 5 6 7 8 9 10 11 S503 1 2 3 4 5 S501 1 2 3 4 5 SW5 SW2 SW1 SW3 A 1 2 3 4 DB1 DB2 HL402 HN402 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 1 2 3 4 5 6 7...

Page 23: ...L1 HN1 30A V3 S10 3 2 1 MR30_A MR30_B 1 2 S20 S50 1 2 3 4 5 1 2 3 4 DP2 DP1 MR307 MR306 FU1 T3 15A V401 DB401 1 2 3 4 5 6 1 2 3 4 1 2 3 4 5 6 7 WHT YLW ORG BLU RED Y1E M S1NPH S60 S90 S40 R3T t R2T t...

Page 24: ...A X7A X21A K4R K6R X10A X14A X15A X18A 1 2 3 4 5 3 1 1 3 1 2 A1P TR1 M1P S1L N L GND PWM PE MS 3 t t t R3T R4T R1T X10A X1A X5M X3M X5Y A2P 4 3 4 3 2 1 2 1 X2M 23 X2M 22 X2M 21 X2M 20 X8M 9 X8M 8 X8M...

Page 25: ...onvector only for wireless On OFF thermostat 4D094176 1C_Page 8 User interface Remote user interface Option box DHW pump output Max load 2 A inrush 230 V AC 1 A continuous DHW pump Dual setpoint appli...

Page 26: ...PCB A3P On OFF thermostat PC power circuit A3P Heat pump convector A4P Extension PCB control optional A5P User interface PCB A7P Receiver PCB wireless On OFF thermostat B1L Flow sensor C110 C112 Capac...

Page 27: ...mistor air R1H A3P Humidity sensor R4T A1P Inlet water thermistor R5T Domestic hot water thermistor R6T A1P External outdoor ambient thermistor R6T A4P External indoor ambient thermistor S1L Flow swit...

Page 28: ...a 2 Only for heat pump convector Only for KRTR wireless room thermostat Only for KRTW wired room thermostat 2 core 3m included signal R2T External sensor floor or ambient Only for KRTETS External indo...

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ...4P403578 1C 2016 02 Copyright 2015 Daikin...

Reviews: