4.5.13 Connecting switching contacts (AUX outputs)
The switching contacts (AUX outputs) can be used for various
parameterisable functions.
When the Daikin Altherma M ECH
2
O is in [Cooling] operating
mode, switching contact B-B1 closes. Switching contact B-B1 is
used e.g. to connect an external status display ("Cooling mode
active") or as a switchover contact (heating/cooling), e.g. on the
basic module of the floor heating controller.
Switchover contact A-A1-A2 switches under the conditions set in
the parameter [AUX Fct] (see controller operating instructions).
3J
&
0
%
Q
R
&
R
5
3J
&
0
%
Q
R
&
R
5
$8;
B
B
1
A
A
1
A
2
$8;
B
B
1
A
A
1
A
2
L
L
L / +
L / +
N / -
N / -
N
N
250V, max. 63 mA
250V, max. 63 mA
250V, max. 63 mA
250V, max. 63 mA
≤ 15 W
> 15 W
max.1A
max.1A
'& ื9
$&
Fig.
4-43 Connection of switching contact (AUX output)
The relays to be used according to variant 2 (switched output
>
15
W) must be suitable for a 100% on time.
Switchover contact A-A1-A2 can be used e.g. to control the heat
generators in bivalent heating systems consisting of a Daikin
Altherma M ECH
2
O and an oil-or gas-fired boiler. Examples of
hydraulic system integration are described in chapter
If an A1 or G-plus condensing boiler is connected, the
parameter [AUX Fct] and the parameter [AUX time]
must be set according to the desired function.
See "Daikin RoCon
mb controller" operating instructions >
Parameter settings chapter.
Precise information on the electrical connection and the
required parameter settings for such bivalent heating systems
are available on the Internet (www.daikin.com) or from your ser-
vice partner.
4.5.14 Off-peak mains connection (HT/NT)
If the outdoor unit is connected to an off-peak mains connection,
potential-free switching contact S2S
of the receiver, which
evaluates the off-peak input signal output by the electricity com-
pany (EVU), must be connected to
connector J8
, EVU connec-
tion on the RoCon
BM2C
printed circuit board
If
parameter [HT/NT Function] >
0
is set, certain system com-
ponents are shut off during peak periods (see controller operating
instructions).
The following types of off-peak mains connection are common:
– Type 1: with this type of off-peak mains connection, the
power supply to the heat pump outdoor unit is not inter-
rupted.
– Type 2: with this type of off-peak mains connection, the
power supply to the heat pump outdoor unit is interrupted
after a certain period of time.
– Type 3: with this type of off-peak mains connection, the
power supply to the heat pump outdoor unit is interrupted
immediately.
Potential-free switching contact
S2S
can be implemented as a
normally closed or normally open switching contact
.
a)
If
implemented as a normally closed
switching contact,
parameter [HT/NT Contact] = 1
must be set.
When the EVU sends the off-peak signal, switching contact
S2S is opened. The system switches to "Mandatory OFF". If
the signal is sent again, potential-free switching contact S2S
closes and the system resumes operation.
b)
If
implemented as a normally open
switching contact,
parameter [HT/NT Contact] = 0
must be set.
When the EVU sends the off-peak signal, switching contact
S2S is closed. The system switches to "Mandatory OFF". If
the signal is sent again, potential-free switching contact S2S
opens and the system resumes operation.