8 Configuration
Installer reference guide
60
EBLQ+EDLQ011~0W1 + EK(2)CB07CAV3
Daikin Altherma low temperature monobloc
4P538847-1 – 2018.05
#
Code
Description
N/A
[8-01]
Maximum running time for domestic hot
water operation. Domestic hot water
heating stops even when the target
domestic hot water temperature is NOT
reached. The actual maximum running
time also depends on setting [8-04].
▪ When
system
layout
=
Room
thermostat control: This preset value is
only taken into account if there is a
request for space heating or cooling. If
there is NO request for space heating/
cooling, the tank is heated until the
setpoint has been reached.
▪ When
system
layout
≠
Room
thermostat control: This preset value is
always taken into account.
Range: 5~95 minutes (default: 30)
N/A
[8-02]
Anti-recycling time.
Minimum time between two cycles for
domestic hot water. The actual anti-
recycling time also depends on setting
[8-04].
Range: 0~10 hours (default: 3) (step:
0.5).
Remark:
The minimum time is 1/2 hour
even when the selected value is 0.
N/A
[8-03]
Booster heater delay timer.
Only for EKHW
Start-up delay time for the booster heater
when domestic hot water mode is active.
▪ When domestic hot water mode is
NOT active, the delay time is
20 minutes.
▪ The delay time starts from booster
heater ON temperature.
▪ By adapting the booster heater delay
time versus the maximum running
time, you can find an optimal balance
between the energy efficiency and the
heat up time.
▪ If the booster heater delay time is set
too high, it might take a long time
before the domestic hot water reaches
its set temperature.
▪ The setting [8-03] is only meaningful if
setting [4-03]=1. Setting [4-03]=0/2/3/4
limits the booster heater automatically
in relation to heat pump operation time
in domestic water heating mode.
▪ Make sure that [8-03] is always in
relation with the maximum running
time [8-01].
Range: 20~95 (default: 50).
N/A
[8-04]
Additional running time for the maximum
running time depending on the outdoor
temperature [4-02] or [F-01].
Range: 20~95 minutes (default: 50).
[8-02]: Anti-recycling time
t
1
0
1
0
[8-01]
[8-02]
[8-00]
1
Heat pump domestic water heating mode (1=active, 0=not
active)
2
Hot water request for heat pump (1=request, 0=no request)
t
Time
[8-03]: Booster heater delay timer
t
1
0
1
0
1
0
[8-03]
3
4
1
0
1
Booster heater operation (1=active, 0=not active)
2
Heat pump domestic water heating mode (1=active, 0=not
active)
3
Hot water request for booster heater (1=request, 0=no
request)
4
Hot water request for heat pump (1=request, 0=no request)
t
Time
[8-04]: Additional running time at [4-02]/[F-01]
t
T
A
t
T
A
0
[8-01]
[5-03]
[4-02]
[8-02]
[8-01]+
[8-04]
0
[8-01]
[F-01]
35°C
[8-02]
[8-01]+
[8-04]
T
A
Ambient (outdoor) temperature
t
Time
Anti-recycle time
Maximum running time domestic hot water
Disinfection
Applies only to installations with a domestic hot water tank.
The disinfection function disinfects the domestic hot water tank by
periodically heating the domestic hot water to a specific temperature.
CAUTION
The disinfection function settings MUST be configured by
the installer according to the applicable legislation.