8 Configuration
Installer reference guide
59
EPGA11~ EAVH/9W
Daikin Altherma – Low temperature split
4P556070-1 – 2019.02
t
[6-00]
HP
5
10
20
30
40
43
45
T
U
=T
HP OFF
T
HP MAX
T
DHW
T
HP ON
50
HP
Heat pump. If heating up time by the heat pump takes too
long, auxiliary heating by the backup heater can take place
T
HP MAX
Maximum heat pump temperature at sensor in domestic
hot water tank
T
HP OFF
Heat pump OFF temperature (T
HP MAX
−[6-01])
T
HP ON
Heat pump ON temperature (T
HP OFF
−[6-00])
T
DHW
Domestic hot water temperature
T
U
User set point temperature (as set on the user interface)
t
Time
INFORMATION
The maximum heat pump temperature depends on the
ambient temperature. For more information, see the
operation range.
8.4.7
User settings
Language
#
Code
Description
[7.1]
N/A
Language
Time/date
#
Code
Description
[7.2]
N/A
Set the local time and date
INFORMATION
By default, daylight savings time is enabled and clock
format is set to 24 hours. If you want to change these
settings, you can do this in the menu structure (User
settings > Time/date) once the unit is initialised.
Holiday
About holiday mode
During your holiday, you can use the holiday mode to deviate from
your normal schedules without having to change them. While holiday
mode is active, space heating/cooling operation and domestic hot
water operation will be turned off. Room frost protection and anti-
legionella operation will remain active.
Typical workflow
Using holiday mode typically consists of the following stages:
1
Setting the starting date and ending date of your holiday.
2
Activating the holiday mode.
To check if holiday mode is activated and/or running
If
is activated on the home screen, holiday mode is active.
To configure the holiday
1
Activate the holiday mode.
—
▪ Go to [7.3.1]: User settings > Holiday > Activation.
▪ Select On.
2
Set the first day of your holiday.
—
▪ Go to [7.3.2]: From.
▪ Select a date.
▪ Confirm the changes.
3
Set the last day of your holiday.
—
▪ Go to [7.3.3]: Till.
▪ Select a date.
▪ Confirm the changes.
Quiet
About quiet mode
You can use quiet mode to decrease the sound of the outdoor unit.
However, this also decreases the heating/cooling capacity of the
system. There are multiple quiet mode levels.
You can:
▪ Completely deactivate quiet mode
▪ Manually activate a quiet mode level until the next scheduled
action
▪ Use and program a quiet mode schedule
INFORMATION
If the outdoor temperature is below zero, we recommend to
NOT use the most quiet level.
To check if quiet mode is active
If
is displayed on the home screen, quiet mode is active.
To use quiet mode
1
Go to [7.4.1]: User settings > Quiet > Activation.
2
Do one of the following:
—
If you want to…
Then…
Completely deactivate
quiet mode
Select Off.
Manually activate a quiet
mode level
Select the applicable quiet
mode level.
Example:
Most
quiet.
Use and program a quiet
mode schedule
Select Automatic.
Go to [7.4.2] Schedule and
program the schedule. For
more information about
scheduling, see
"8.3.8 Schedule screen:
Example" on page 44
.
Usage example: Baby is sleeping in the afternoon
If you are in the following situation:
▪ You have programmed a quiet mode schedule:
▪ During the night: Most quiet.
▪ During the day: Off to ensure the heating/cooling capacity of the
system.
▪ However, during the afternoon the baby is sleeping and you want
it to be quiet.
Then you can do the following:
1
Go to [7.4.1]: User settings > Quiet > Activation.
2
Select Most quiet.
Advantage: