background image

4 Energy saving tips

Operation manual

10

EABH/X16DA+9W + EAVH/9W

Daikin Altherma – Low temperature split

4P556068-1 – 2018.10

3.8

Installer settings: Tables to be
filled in by installer

3.8.1

Configuration wizard

Setting

Fill in…

System

Indoor unit type (read only)

Backup heater type [9.3.1]

Domestic hot water [9.2.1]

Emergency [9.5]

Number of zones [4.4]

Backup heater

Voltage [9.3.2]

Configuration [9.3.3]

Capacity step 1 [9.3.4]

Additional capacity step 2 [9.3.5]
(if applicable)

Main zone

Emitter type [2.7]

Control [2.9]

Setpoint mode [2.4]

Schedule [2.1]

Additional zone (only if [4.4] = 1)

Emitter type [3.7]

Control (read only) [3.9]

Setpoint mode [3.4]

Schedule [3.1]

Tank

Heat up mode [5.6]

Comfort setpoint [5.2]

Eco setpoint [5.3]

Reheat setpoint [5.4]

3.8.2

Settings menu

Setting

Fill in…

Main zone

Thermostat type [2.A]

Additional zone (if applicable)

Thermostat type [3.A]

Information

Dealer information [8.3]

4

Energy saving tips

Tips about room temperature

▪ Make  sure  the  desired  room  temperature  is  NEVER  too  high  (in

heating  mode)  or  too  low  (in  cooling  mode),  but  ALWAYS
according  to  your  actual  needs.  Each  saved  degree  can  save  up
to 6% of heating/cooling costs.

▪ Do  NOT  increase  the  desired  room  temperature  to  speed  up

space heating. The space will NOT heat up faster.

▪ When  your  system  layout  contains  slow  heat  emitters  (example:

under  floor  heating),  avoid  large  fluctuation  of  the  desired  room
temperature and do NOT let the room temperature drop too low. It
will take more time and energy to heat up the room again.

▪ Use  a  weekly  schedule  for  your  normal  space  heating  or  cooling

needs. If necessary, you can easily deviate from the schedule:

▪ For  shorter  periods:  You  can  overrule  the  scheduled  room

temperature  until  the  next  scheduled  action. 

Example: 

When

you have a party, or when you are leaving for a couple of hours.

▪ For longer periods: You can use the holiday mode.

Tips about DHW tank temperature

▪ Use a weekly schedule for your normal domestic hot water needs

(only in scheduled mode).

▪ Program  to  heat  up  the  DHW  tank  to  a  preset  value  (Storage

comfort  =  higher  DHW  tank  temperature)  during  the  night,
because then space heating demand is lower.

▪ If  heating  up  the  DHW  tank  once  at  night  is  not  sufficient,

program to additionally heat up the DHW tank to a preset value
(Storage eco = lower DHW tank temperature) during the day.

▪ Make  sure  the  desired  DHW  tank  temperature  is  NOT  too  high.

Example: 

After installation, lower the DHW tank temperature daily

by 1°C and check if you still have enough hot water.

▪ Program  to  turn  ON  the  domestic  hot  water  pump  only  during

periods of the day when instant hot water is necessary. 

Example:

In the morning and evening.

5

Maintenance and service

5.1

Overview: Maintenance and
service

The installer has to perform a yearly maintenance. You can find the
contact/helpdesk number via the user interface.

As end user, you have to:

▪ Keep the area around the unit clean.

▪ Keep the user interface clean with a soft damp cloth. Do NOT use

any detergents.

▪ Regularly check if the water pressure is above 1 bar.

Refrigerant

This  product  contains  fluorinated  greenhouse  gases.  Do  NOT  vent
gases into the atmosphere.

Refrigerant type: R32

Global warming potential (GWP) value: 675

NOTICE

In  Europe,  the 

greenhouse  gas  emissions

  of  the  total

refrigerant charge in the system (expressed as tonnes CO

2

equivalent) is used to determine the maintenance intervals.
Follow the applicable legislation.

Formula  to  calculate  the  greenhouse  gas  emissions:

GWP value of the refrigerant × Total refrigerant charge [in
kg] / 1000

Please contact your installer for more information.

WARNING: FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

WARNING

The  appliance  shall  be  stored  in  a  room  without
continuously  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater).

Summary of Contents for Altherma EAVH16S23DA6V(G)

Page 1: ...ture split English Operation manual Daikin Altherma Low temperature split EABH16DA6V EABH16DA9W EABX16DA6V EABX16DA9W EAVH16S18DA6V G EAVH16S23DA6V G EAVH16S18DA9W G EAVH16S23DA9W G EAVX16S18DA6V G EAVX16S23DA6V G EAVX16S18DA9W G EAVX16S23DA9W G ...

Page 2: ...the settings that he used to configure your system Check if he has filled in the installer settings tables If not request him to do so Keep the documentation for future reference Target audience End users Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you must read before operating your system Format P...

Page 3: ... 11 for more information LCD screen The LCD screen has a sleeping function After a certain time of non interaction with the user interface the screen darkens Pressing any button or rotating any dial awakens the display The time of non interaction differs depending on the user permission level User or Advanced user 15 min Installer 1 h Dials and buttons You use the dials and buttons To navigate thr...

Page 4: ...iption Space operation mode c Cooling Heating Disinfection Powerful d Disinfection mode active Powerful operation active Date time e Current date and time Holiday f Holiday mode active Main zone g3 g1 g4 g2 g1 Heat emitter type Underfloor heating Fancoil unit Radiator g2 Leaving water temperature setpoint g3 Room thermostat type Daikin user interface used as room thermostat External control Hidden...

Page 5: ...2 Possible actions on this screen Go through the list of the submenu Go to the submenu Adjust and automatically apply the desired temperature Item Description Minimum temperature limit a1 Fixed by the unit a2 Restricted by the installer Item Description Maximum temperature limit b1 Fixed by the unit b2 Restricted by the installer Current temperature c Measured by the unit Desired temperature d Tur...

Page 6: ... desired leaving water temperature 1 Go to 2 Main zone or 3 Additional zone You can read out the desired and actual leaving water temperature in the center of the setpoint screen 2 Adjust the desired leaving water temperature 3 4 Domestic hot water control 3 4 1 Reheat mode In reheat mode the DHW tank continuously heats up to the temperature shown on the home screen example 50 C t 60 C 00 00 07 00...

Page 7: ...om left to right Browse through the list of digits and change the selected digit Confirm the pincode and proceed User pin code The User pin code is 0000 Advanced user pin code The Advanced user pin code is 1234 Additional menu items for the user are now visible 3 6 Schedule screen Example This example shows how to set a room temperature schedule in heating mode for the main zone INFORMATION The pr...

Page 8: ...kdays Mon Sat Wed Fri Thu Tue Sun User defined 1 C To program the schedule for Saturday and copy it to Sunday 1 Select Saturday 2 Select Edit 3 Use the left dial to select an entry and edit the entry with the right dial 0 8 00 23 00 21 C 18 C 12 24 Sat 4 Confirm the changes 5 Select Saturday 6 Select Copy 7 Select Sunday 8 Select Paste Result Mon Sat Wed Fri Thu Tue Sun User defined 1 C To rename ...

Page 9: ...tings Language Time date Holiday Quiet Electricity price Gas price C Operation Room Space heating cooling Tank B User profile 7 3 Holiday Activation From Till 7 4 Quiet Activation Schedule 7 5 Electricity price High Medium Low Schedule 7 2 Time date Hours Minutes Year Month Day Daylight savings time Format 8 1 Energy data Electricity input Produced heat 1 Room Room sensor offset Setpoint range Ant...

Page 10: ...r longer periods You can use the holiday mode Tips about DHW tank temperature Use a weekly schedule for your normal domestic hot water needs only in scheduled mode Program to heat up the DHW tank to a preset value Storage comfort higher DHW tank temperature during the night because then space heating demand is lower If heating up the DHW tank once at night is not sufficient program to additionally...

Page 11: ... desired leaving water temperature in accordance with the heat emitter type 6 3 Symptom The water at the tap is too cold Possible cause Corrective action You ran out of domestic hot water because of unusual high consumption If you immediately need domestic hot water activate the DHW tank Powerful operation However this consumes extra energy If you can wait overrule increase the active or next sche...

Page 12: ...rging heat emitters or collectors Before you purge air from heat emitters or collectors check if or is displayed on the home screen of the user interface If not you can purge air immediately If yes make sure that the room where you want to purge air is sufficiently ventilated Reason Refrigerant might leak into the water circuit and subsequently into the room when you purge air from the heat emitte...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...4P556068 1 2018 10 Copyright 2018 Daikin 4P556068 1 0000000S ...

Reviews: