3 Operation

Operation manual

6

EABH/X16DA+9W + EAVH/9W

Daikin Altherma – Low temperature split

4P556068-1 – 2018.10

To restrict automatic changeover according to a schedule

Conditions: 

You set the space operation mode to Automatic.

1

Go to [4.2]: Space heating/cooling > Operation mode
schedule.

2

Select a month.

3

For each month, select an option:

▪ Reversible: Not restricted

▪ Heating only: Restricted

▪ Cooling only: Restricted

4

Confirm the changes.

3.3.2

To change the desired room temperature

During room temperature control, you can use the room temperature
setpoint screen to read out and adjust the desired room temperature.

1

Go to [1]: Room.

You can read out the desired and actual room
temperature in the center of the setpoint screen.

2

Adjust the desired room temperature.

If scheduling is on after changing the desired room temperature

▪ The  temperature  will  stay  the  same  as  long  as  there  is  no

scheduled action.

▪ The  desired  room  temperature  will  return  to  its  scheduled  value

whenever a scheduled action occurs.

You  can  avoid  scheduled  behaviour  by  (temporarily)  turning  off
scheduling.

To turn off room temperature scheduling

1

Go to [1.1]: Room > Schedule.

2

Select No.

3.3.3

To change the desired leaving water
temperature

INFORMATION

The  leaving  water  is  the  water  that  is  sent  to  the  heat
emitters.  The  desired  leaving  water  temperature  is  set  by
your  installer  in  accordance  with  the  heat  emitter  type.
Only adjust the leaving water temperature settings in case
of problems.

You  can  use  the  leaving  water  temperature  setpoint  screen  to  read
out and adjust the desired leaving water temperature.

1

Go to [2]: Main zone or [3]: Additional zone.

You can read out the desired and actual leaving
water temperature in the center of the setpoint
screen.

2

Adjust the desired leaving water temperature.

3.4

Domestic hot water control

3.4.1

Reheat mode

In  reheat  mode  the  DHW  tank  continuously  heats  up  to  the
temperature shown on the home screen (example: 50°C).

t

60°C

00:00

07:00

50°C

15°C

40°C

14:00

21:00

1

2

3

4

Tt

T

t

DHW tank temperature

t

Time

INFORMATION

Risk  of  space  heating  capacity  shortage  for  domestic  hot
water  tank  without  internal  booster  heater:  In  case  of
frequent  domestic  hot  water  operation,  frequent  and  long
space  heating/cooling  interruption  will  happen  when
selecting the following:

Tank > Heat up mode > Reheat only.

INFORMATION

When  the  DHW  tank  mode  is  reheat,  the  risk  for  capacity
shortage  and  comfort  problem  is  significant.  In  case  of
frequent  reheat  operation,  space  heating/cooling  function
is regularly interrupted.

3.4.2

Scheduled mode

In scheduled mode the DHW tank produces hot water corresponding
to a schedule. The best time to allow the tank to produce hot water is
at night, because the space heating demand is lower.

Example: 

t

60°C

00:00

07:00

50°C

15°C

40°C

14:00

21:00

1

2

3

4

5

Tt

T

t

DHW tank temperature

t

Time

3.4.3

Sch reheat mode

In  scheduled  +  reheat  mode,  the  domestic  hot  water  control  is  the
same  as  in  scheduled  mode.  However,  when  the  DHW  tank
temperature drops below a preset value (=reheat tank temperature –
hysteresis  value;  example:  35°C),  the  DHW  tank  heats  up  until  it
reaches  the  reheat  set  point  (example:  45°C).  This  ensures  that  a
minimum amount of hot water is available at all times.

Example: 

t

Tt

60°C

00:00

07:00

50°C

45°C

15°C

14:00

21:00

35°C

1

2

4

5

3

T

t

DHW tank temperature

t

Time

Summary of Contents for Altherma EAVH16S23DA6V(G)

Page 1: ...ture split English Operation manual Daikin Altherma Low temperature split EABH16DA6V EABH16DA9W EABX16DA6V EABX16DA9W EAVH16S18DA6V G EAVH16S23DA6V G EAVH16S18DA9W G EAVH16S23DA9W G EAVX16S18DA6V G EAVX16S23DA6V G EAVX16S18DA9W G EAVX16S23DA9W G ...

Page 2: ...the settings that he used to configure your system Check if he has filled in the installer settings tables If not request him to do so Keep the documentation for future reference Target audience End users Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you must read before operating your system Format P...

Page 3: ... 11 for more information LCD screen The LCD screen has a sleeping function After a certain time of non interaction with the user interface the screen darkens Pressing any button or rotating any dial awakens the display The time of non interaction differs depending on the user permission level User or Advanced user 15 min Installer 1 h Dials and buttons You use the dials and buttons To navigate thr...

Page 4: ...iption Space operation mode c Cooling Heating Disinfection Powerful d Disinfection mode active Powerful operation active Date time e Current date and time Holiday f Holiday mode active Main zone g3 g1 g4 g2 g1 Heat emitter type Underfloor heating Fancoil unit Radiator g2 Leaving water temperature setpoint g3 Room thermostat type Daikin user interface used as room thermostat External control Hidden...

Page 5: ...2 Possible actions on this screen Go through the list of the submenu Go to the submenu Adjust and automatically apply the desired temperature Item Description Minimum temperature limit a1 Fixed by the unit a2 Restricted by the installer Item Description Maximum temperature limit b1 Fixed by the unit b2 Restricted by the installer Current temperature c Measured by the unit Desired temperature d Tur...

Page 6: ... desired leaving water temperature 1 Go to 2 Main zone or 3 Additional zone You can read out the desired and actual leaving water temperature in the center of the setpoint screen 2 Adjust the desired leaving water temperature 3 4 Domestic hot water control 3 4 1 Reheat mode In reheat mode the DHW tank continuously heats up to the temperature shown on the home screen example 50 C t 60 C 00 00 07 00...

Page 7: ...om left to right Browse through the list of digits and change the selected digit Confirm the pincode and proceed User pin code The User pin code is 0000 Advanced user pin code The Advanced user pin code is 1234 Additional menu items for the user are now visible 3 6 Schedule screen Example This example shows how to set a room temperature schedule in heating mode for the main zone INFORMATION The pr...

Page 8: ...kdays Mon Sat Wed Fri Thu Tue Sun User defined 1 C To program the schedule for Saturday and copy it to Sunday 1 Select Saturday 2 Select Edit 3 Use the left dial to select an entry and edit the entry with the right dial 0 8 00 23 00 21 C 18 C 12 24 Sat 4 Confirm the changes 5 Select Saturday 6 Select Copy 7 Select Sunday 8 Select Paste Result Mon Sat Wed Fri Thu Tue Sun User defined 1 C To rename ...

Page 9: ...tings Language Time date Holiday Quiet Electricity price Gas price C Operation Room Space heating cooling Tank B User profile 7 3 Holiday Activation From Till 7 4 Quiet Activation Schedule 7 5 Electricity price High Medium Low Schedule 7 2 Time date Hours Minutes Year Month Day Daylight savings time Format 8 1 Energy data Electricity input Produced heat 1 Room Room sensor offset Setpoint range Ant...

Page 10: ...r longer periods You can use the holiday mode Tips about DHW tank temperature Use a weekly schedule for your normal domestic hot water needs only in scheduled mode Program to heat up the DHW tank to a preset value Storage comfort higher DHW tank temperature during the night because then space heating demand is lower If heating up the DHW tank once at night is not sufficient program to additionally...

Page 11: ... desired leaving water temperature in accordance with the heat emitter type 6 3 Symptom The water at the tap is too cold Possible cause Corrective action You ran out of domestic hot water because of unusual high consumption If you immediately need domestic hot water activate the DHW tank Powerful operation However this consumes extra energy If you can wait overrule increase the active or next sche...

Page 12: ...rging heat emitters or collectors Before you purge air from heat emitters or collectors check if or is displayed on the home screen of the user interface If not you can purge air immediately If yes make sure that the room where you want to purge air is sufficiently ventilated Reason Refrigerant might leak into the water circuit and subsequently into the room when you purge air from the heat emitte...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...4P556068 1 2018 10 Copyright 2018 Daikin 4P556068 1 0000000S ...

Reviews: