NOTICE

Overpressure bypass valve

 (delivered as accessory). We

recommend to install the overpressure bypass valve in the
space heating water circuit.

▪ Mind  the  minimum  water  volume  when  choosing  the

installation  location  of  the  overpressure  bypass  valve
(at  the  indoor  unit,  or  at  the  collector).  See 

"3.2.1  To

check the water volume and flow rate" on page 4

.

▪ Mind  the  minimum  flow  rate  when  adjusting  the

overpressure  bypass  valve  setting.  See 

"3.2.1  To

check  the  water  volume  and  flow  rate"  on  page  4

  and

"6.2.1 To check the minimum flow rate" on page 20

.

NOTICE

Install air purge valves at all local high points.

NOTICE

A  pressure  relief  valve  (field  supply)  with  an  opening
pressure  of  maximum  10  bar  must  be  installed  on  the
domestic  cold  water  inlet  connection  in  accordance  with
the applicable legislation.

4.3.2

To connect the recirculation piping

Prerequisite: 

Only required if you need recirculation in your system.

1

Remove  the  top  panel  from  the  unit,  see 

"4.1.1  To  open  the

indoor unit" on page 5

.

2

Cut out the rubber grommet on top of the unit, and remove the
stop. The recirculation connector is placed below the hole.

3

Route the recirculation piping through the grommet and connect
it to the recirculation connector.

4

Reattach the top panel.

4.3.3

To fill the water circuit

To  fill  the  water  circuit,  use  a  field  supply  filling  kit.  Make  sure  you
comply with the applicable legislation.

INFORMATION

Make sure both air purge valves (one on the magnetic filter
and one on the backup heater) are open.

4.3.4

To protect the water circuit against
freezing

About freeze protection

Frost can damage the system. To prevent the hydraulic components
from  freezing,  the  software  is  equipped  with  special  frost  protection
functions such as water pipe freeze prevention and drain prevention
(see installer reference guide) that include the activation of pump in
case of low temperatures.

However,  in  case  of  a  power  failure,  these  functions  cannot
guarantee protection.

Do one of the following to protect the water circuit against freezing:

▪ Add  glycol  to  the  water.  Glycol  lowers  the  freezing  point  of  the

water.

▪ Install freeze protection valves. Freeze protection valves drain the

water from the system before it can freeze.

NOTICE

If  you  add  glycol  to  the  water,  do  NOT  install  freeze
protection  valves. 

Possible  consequence: 

Glycol  leaking

out of the freeze protection valves.

Freeze protection by glycol

Adding glycol to the water lowers the freezing point of the water.

The required concentration depends on the lowest expected outdoor
temperature,  and  on  whether  you  want  to  protect  the  system  from
bursting or from freezing. To prevent the system from freezing, more
glycol is required. Add glycol according to the table below.

INFORMATION

▪ Protection  against  bursting:  the  glycol  will  prevent  the

piping  from  bursting,  but  NOT  the  liquid  inside  the
piping from freezing.

▪ Protection  against  freezing:  the  glycol  will  prevent  the

liquid inside the piping from freezing.

Lowest expected
outdoor
temperature

Prevent from
bursting

Prevent from
freezing

–5°C

10%

15%

–10°C

15%

25%

–15°C

20%

35%

–20°C

25%

–25°C

30%

NOTICE

▪ The  required  concentration  might  differ  depending  on

the type of glycol. ALWAYS compare the requirements
from the table above with the specifications provided by
the  glycol  manufacturer.  If  necessary,  meet  the
requirements set by the glycol manufacturer.

▪ The  added  concentration  of  glycol  should  NEVER

exceed 35%.

▪ If the liquid in the system is frozen, the pump will NOT

be  able  to  start.  Mind  that  if  you  only  prevent  the
system from bursting, the liquid inside might still freeze.

▪ When  water  is  at  standstill  inside  the  system,  the

system is very likely to freeze and get damaged.

The types of glycol that can be used depend on whether the system
contains a domestic hot water tank:

If…

Then…

The system contains a domestic
hot water tank

Only use propylene glycol

(a)

The system does NOT contain a
domestic hot water tank

You can use either propylene
glycol

(a)

 or ethylene glycol

(a)

Propylene glycol, including the necessary inhibitors,
classified as Category III according to EN1717.

WARNING

Ethylene glycol is toxic.

Summary of Contents for Altherma EAVH16S18DA6V

Page 1: ...n Altherma Low temperature split English Installation manual Daikin Altherma Low temperature split EAVH16S18DA6V G EAVH16S23DA6V G EAVH16S18DA9W G EAVH16S23DA9W G EAVX16S18DA6V G EAVX16S23DA6V G EAVX16S18DA9W G EAVX16S23DA9W G ...

Page 2: ...mme mukaisesti za předpokladu že jsou využívány v souladu s našimi pokyny odpovídají následujícím normám nebo normativním dokumentům u skladu sa slijedećim standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s našim uputama 16 17 18 19 20 21 22 23 24 25 megfelelnek az alábbi szabvány ok nak vagy egyéb irányadó dokumentum ok nak ha azokat előírás szerint használ...

Page 3: ...5 2 1 Configuration wizard Language 14 5 2 2 Configuration wizard Time and date 14 5 2 3 Configuration wizard System 15 5 2 4 Configuration wizard Backup heater 16 5 2 5 Configuration wizard Main zone 16 5 2 6 Configuration wizard Additional zone 17 5 2 7 Detailed screen with weather dependent curve 17 5 2 8 Configuration wizard Tank 17 5 3 Settings menu 18 5 3 1 Main zone 18 5 3 2 Additional zone...

Page 4: ... To connect the drain hose to the drain on page 7 It requires to remove one or both side panels 3 2 Preparing water piping NOTICE In case of plastic pipes make sure they are fully oxygen diffusion tight according to DIN 4726 The diffusion of oxygen into the piping can lead to excessive corrosion 3 2 1 To check the water volume and flow rate Minimum water volume Check that the total water volume in...

Page 5: ... control 2 b 16 Space cool heat operation control 2 b 17 Power consumption digital inputs 2 per input signal b 18 Safety thermostat 2 d a Refer to name plate on outdoor unit b Minimum cable section 0 75 mm c Cable section 2 5 mm d Cable section 0 75 mm till 1 25 mm maximum length 50 m Voltage free contact shall ensure the minimum applicable load of 15 V DC 10 mA e Cable section 0 75 mm till 1 25 m...

Page 6: ...ove the top panel that keeps the switch box into place at the top of the unit 2 Tilt the switch box to the front and lift it out of its hinges 1 2 2 T25 3 Place the switch box lower on the unit Use the 2 hinges located lower on the unit 3 3 4 2 Mounting the indoor unit 4 2 1 To install the indoor unit 1 Lift the indoor unit from the pallet and place it on the floor Also see 2 1 2 To handle the ind...

Page 7: ...25 3 2 Option 2 Through the right side panel 1 3 T25 3 2 4 3 Connecting the water piping 4 3 1 To connect the water piping NOTICE Do NOT use excessive force when connecting the piping Deformation of the piping can cause malfunctioning of the unit 1 Connect the O rings and shut off valves to the outdoor unit water connection pipes of the indoor unit 2 Connect the outdoor unit field piping to the sh...

Page 8: ... of a power failure these functions cannot guarantee protection Do one of the following to protect the water circuit against freezing Add glycol to the water Glycol lowers the freezing point of the water Install freeze protection valves Freeze protection valves drain the water from the system before it can freeze NOTICE If you add glycol to the water do NOT install freeze protection valves Possibl...

Page 9: ...s can prevent that all water from indoor piping is drained when the freeze protection valves open NOTICE When freeze protection valves are installed do NOT select a minimum cooling setpoint lower than 8 C 8 C default If lower freeze protection valves can open during cooling operation Consult the installer reference guide of the unit for more detailed information Heater tape field supply 1 Install ...

Page 10: ...hout low voltage cables With low voltage cables 4 4 3 To connect the main power supply 1 Connect the main power supply In case of normal kWh rate power supply X1M X2M X5M X11YB X1A X11Y X11YA 1 2 3 1 2 3 a 1 2 3 Legend see illustration below In case of preferential kWh rate power supply Connect X11Y to X11YB X1M X2M X5M X11Y X11YB X1A 1 2 3 1 N L N L 2 3 S1S a b c X11YA 5 1 2 3 6 9 10 a Interconne...

Page 11: ...mits for voltage changes voltage fluctuations and flicker in public low voltage supply systems for equipment with rated current 75 A provided that the system impedance Zsys is less than or equal to Zmax at the interface point between the user s supply and the public system It is the responsibility of the installer or user of the equipment to ensure by consultation with the distribution network ope...

Page 12: ...tic hot water pump cable to the appropriate terminals as shown in the illustration below X1M X2M X5M 1 M M2P 1 2 2 Fix the cable with cable ties to the cable tie mountings 4 4 8 To connect the alarm output 1 Connect the alarm output cable to the appropriate terminals as shown in the illustration below X1M X2M A4P X5M X1M YC Y1 Y2 Y3 Y4 Y1 YC a 7 9 b a Installation of EKRP1HB is required b Prewirin...

Page 13: ... and the 3 way valve INFORMATION After it is installed do NOT forget to configure the safety thermostat Without configuration the indoor unit will ignore the safety thermostat contact INFORMATION The preferential kWh rate power supply contact is connected to the same terminals X5M 9 10 as the safety thermostat It is only possible for the system to have EITHER preferential kWh rate power supply OR ...

Page 14: ...proceed Installer pin code The Installer pin code is 5678 Additional menu items and installer settings are now available 5678 Installer Advanced user pin code The Advanced user pin code is 1234 Additional menu items for the user are now visible User pin code The User pin code is 0000 To access the installer settings 1 Set the user permission level to Installer 2 Go to 9 Installer settings To modif...

Page 15: ...er interface To recover operation manually go to the Malfunctioning main menu screen where the user interface will then ask you to confirm whether the backup heater can take over the heat load or not We recommend to set Emergency to Automatic if the house is unattended for longer periods Code Description 9 5 N A 0 Manual 1 Automatic INFORMATION The auto emergency setting can be set in the menu str...

Page 16: ...tep of the backup heater at nominal voltage Additional capacity step 2 Code Description 9 3 5 6 04 The capacity difference between the second and first step of the backup heater at nominal voltage Nominal value depends on backup heater configuration 5 2 5 Configuration wizard Main zone The most important settings for the main leaving water zone can be set here Emitter type Depending on the system ...

Page 17: ...Underfloor heating 1 Fancoil unit 2 Radiator Control The control type is displayed here but cannot be adjusted It is determined by the control type of the main zone For more info about the functionality see 5 2 5 Configuration wizard Main zone on page 16 Code Description 3 9 N A 0 Leaving water if the control type of the main zone is Leaving water 1 External room thermostat if the control type of ...

Page 18: ...e reheat mode during reheat mode the guaranteed minimum tank temperature is set by the Reheat setpoint minus the reheat hysteresis If the tank temperature drops below this value the tank is heated up during storage comfort to prioritize the domestic hot water preparation When the tank temperature rises above this value domestic hot water preparation and space heating cooling are executed sequentia...

Page 19: ...efit kWh power supply Allow heater Allow pump 9 2 Domestic hot water Domestic hot water DHW pump DHW pump schedule Solar 9 9 Power consumption control Power consumption control Type Limit Limit 1 Limit 2 Limit 3 Limit 4 Priority heater Electricity meter 2 Electricity meter 1 9 A Energy metering 9 Installer settings Configuration wizard Domestic hot water Backup heater Emergency Balancing Water pip...

Page 20: ...switch box There are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units Backup heater circuit breaker F1B field supply is turned ON The correct pipe size is installed and the pipes are properly insulated There is NO water leak inside the indoor unit The shut off valves are properly installed and fully open The air purge valve is open at least 2 turns The pressure...

Page 21: ... avoid disturbances in the water circuit during the test run Shut off valve test Diverter valve test Bivalent signal test Alarm output test C H signal test DHW pump test 6 2 5 To perform an underfloor heating screed dryout Conditions Make sure all operation is disabled Go to the Operation menu and turn off Room Space heating cooling and Tank operation 1 Set the user permission level to Installer S...

Page 22: ...1L B f B f A Water side B Field installed a1 Space heating water IN a2 Space heating water OUT b1 Domestic hot water cold water IN b2 Domestic hot water hot water OUT c1 Water IN connection c2 Water OUT connection d Pump e Backup heater f Shut off valve for service if equipped g Expansion vessel h Magnetic filter dirt separator i Safety valve j Air purge k Drain valve B1L Flow sensor B1PW Space he...

Page 23: ...eaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translation Position in switch box Position in switch box Legend A1P Main PCB A2P On OFF thermostat PC power circuit A3P Heat pump convector A4P Digital I O PCB A8P De...

Page 24: ...ush Inrush current Max load Maximum load Normally closed Normally closed Normally open Normally open Safety thermostat contact 16 V DC detection voltage supplied by PCB Safety thermostat contact 16 V DC detection voltage supplied by PCB English Translation Shut off valve Shut off valve SWB Switch box 7 Option PCBs 7 Option PCBs Alarm output Alarm output Changeover to ext heat source Changeover to ...

Page 25: ...al signal 2 core 2 core 2 core signal 2 core 2 core External sensor floor or ambient Only for KRTETS signal 2 core 3m included A13P P1 P2 LAN adapter A14P P1 P2 user interface Only for EKRUDAS Only for KRTR wireless room thermostat Only for KRTW wired room thermostat 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H only operation communication 2 core commu...

Page 26: ......

Page 27: ......

Page 28: ...4P556067 1 2018 10 Copyright 2018 Daikin 4P556067 1 0000000R ...

Reviews: