background image

5 Configuration

Installation manual

15

EAVH/9W
Daikin Altherma – Low temperature split
4P556067-1 – 2018.10

INFORMATION

By  default,  daylight  savings  time  is  enabled  and  clock
format  is  set  to  24  hours.  If  you  want  to  change  these
settings,  you  can  do  this  in  the  menu  structure  (User
settings > Time/date) once the unit is initialised.

5.2.3

Configuration wizard: System

Indoor unit type

The indoor unit type is displayed, but cannot be adjusted.

Backup heater type

The  backup  heater  is  adapted  to  be  connected  to  most  common
European electricity grids. The type of backup heater must be set on
the user interface. For units with a built-in backup heater, the type of
heater can be viewed but not changed.

#

Code

Description

[9.3.1]

[E‑03]

▪ 3: 6V

▪ 4: 9W

Domestic hot water

The following setting determines if the system can prepare domestic
hot water or not, and which tank is used. This setting is read only.

#

Code

Description

[9.2.1]

[E‑05]

(*)

[E‑06]

(*)

[E‑07]

(*)

▪ Integrated

The  backup  heater  will  also  be  used
for domestic hot water heating.

(*)

Menu structure setting [9.2.1] replaces the following 3
overview settings:

[E-05]

Can the system prepare domestic hot water?

[E-06]

Is a domestic hot water tank installed in the system?

[E-07]

What kind of domestic hot water tank is installed?

Emergency

When  the  heat  pump  fails  to  operate,  the  backup  heater  can  serve
as  an  emergency  heater  and  either  automatically  or  non-
automatically take over the heat load.

▪ When auto emergency is set to Automatic and a heat pump failure

occurs,  the  backup  heater  will  automatically  take  over  the  heat
load and the domestic hot water production.

▪ When  auto  emergency  is  set  to  Manual  and  a  heat  pump  failure

occurs,  the  domestic  hot  water  and  space  heating  operation  will
stop and need to be recovered manually via the user interface. To
recover  operation  manually,  go  to  the  Malfunctioning  main  menu
screen,  where  the  user  interface  will  then  ask  you  to  confirm
whether the backup heater can take over the heat load or not.

We  recommend  to  set  Emergency  to  Automatic  if  the  house  is
unattended for longer periods.

#

Code

Description

[9.5]

N/A

▪ 0: Manual

▪ 1: Automatic

INFORMATION

The  auto  emergency  setting  can  be  set  in  the  menu
structure of the user interface only.

INFORMATION

If  a  heat  pump  failure  occurs  and  Emergency  is  set  to
Manual,  the  room  frost  protection  function,  the  underfloor
heating  screed  dryout  function,  and  the  water  pipe
antifreeze function will remain active even if the user does
NOT confirm emergency operation.

Number of zones

The  system  can  supply  leaving  water  to  up  to  2  water  temperature
zones. During configuration, the number of water zones must be set.

#

Code

Description

[4.4]

[7‑02]

▪ 0: Single zone

Only  one  leaving  water  temperature
zone:

a

▪ a: Main LWT zone

[4.4]

[7‑02]

▪ 1: Dual zone

Two leaving water temperature zones.
The  main  leaving  water  temperature
zone  consists  of  the  higher  load  heat
emitters  and  a  mixing  station  to
achieve  the  desired  leaving  water
temperature. In heating:

▪ a:  Additional  LWT  zone:  Highest

temperature

▪ b: 

Main 

LWT 

zone: 

Lowest

temperature

CAUTION

If  there  are  2  zones,  it  is  important  that  the  zone  with  the
lowest  water  temperature  is  configured  as  the  main  zone,
and  the  zone  with  the  highest  water  temperature  is
configured  as  the  additional  zone.  Not  configuring  the
system  in  this  way  could  cause  damage  to  the  heat
emitters.

CAUTION

If  there  are  2  zones  and  the  emitter  types  are  wrongly
configured, water of high temperature can be sent towards
a  low  temperature  emitter  (underfloor  heating).  To  avoid
this:

▪ Install an aquastat/thermostatic valve to avoid too high

temperatures towards a low temperature emitter.

▪ Make sure you set the emitter types for the main zone

[2.7]  and  for  the  additional  zone  [3.7]  correctly  in
accordance with the connected emitter.

Summary of Contents for Altherma EAVH16S18DA6V

Page 1: ...n Altherma Low temperature split English Installation manual Daikin Altherma Low temperature split EAVH16S18DA6V G EAVH16S23DA6V G EAVH16S18DA9W G EAVH16S23DA9W G EAVX16S18DA6V G EAVX16S23DA6V G EAVX16S18DA9W G EAVX16S23DA9W G ...

Page 2: ...mme mukaisesti za předpokladu že jsou využívány v souladu s našimi pokyny odpovídají následujícím normám nebo normativním dokumentům u skladu sa slijedećim standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s našim uputama 16 17 18 19 20 21 22 23 24 25 megfelelnek az alábbi szabvány ok nak vagy egyéb irányadó dokumentum ok nak ha azokat előírás szerint használ...

Page 3: ...5 2 1 Configuration wizard Language 14 5 2 2 Configuration wizard Time and date 14 5 2 3 Configuration wizard System 15 5 2 4 Configuration wizard Backup heater 16 5 2 5 Configuration wizard Main zone 16 5 2 6 Configuration wizard Additional zone 17 5 2 7 Detailed screen with weather dependent curve 17 5 2 8 Configuration wizard Tank 17 5 3 Settings menu 18 5 3 1 Main zone 18 5 3 2 Additional zone...

Page 4: ... To connect the drain hose to the drain on page 7 It requires to remove one or both side panels 3 2 Preparing water piping NOTICE In case of plastic pipes make sure they are fully oxygen diffusion tight according to DIN 4726 The diffusion of oxygen into the piping can lead to excessive corrosion 3 2 1 To check the water volume and flow rate Minimum water volume Check that the total water volume in...

Page 5: ... control 2 b 16 Space cool heat operation control 2 b 17 Power consumption digital inputs 2 per input signal b 18 Safety thermostat 2 d a Refer to name plate on outdoor unit b Minimum cable section 0 75 mm c Cable section 2 5 mm d Cable section 0 75 mm till 1 25 mm maximum length 50 m Voltage free contact shall ensure the minimum applicable load of 15 V DC 10 mA e Cable section 0 75 mm till 1 25 m...

Page 6: ...ove the top panel that keeps the switch box into place at the top of the unit 2 Tilt the switch box to the front and lift it out of its hinges 1 2 2 T25 3 Place the switch box lower on the unit Use the 2 hinges located lower on the unit 3 3 4 2 Mounting the indoor unit 4 2 1 To install the indoor unit 1 Lift the indoor unit from the pallet and place it on the floor Also see 2 1 2 To handle the ind...

Page 7: ...25 3 2 Option 2 Through the right side panel 1 3 T25 3 2 4 3 Connecting the water piping 4 3 1 To connect the water piping NOTICE Do NOT use excessive force when connecting the piping Deformation of the piping can cause malfunctioning of the unit 1 Connect the O rings and shut off valves to the outdoor unit water connection pipes of the indoor unit 2 Connect the outdoor unit field piping to the sh...

Page 8: ... of a power failure these functions cannot guarantee protection Do one of the following to protect the water circuit against freezing Add glycol to the water Glycol lowers the freezing point of the water Install freeze protection valves Freeze protection valves drain the water from the system before it can freeze NOTICE If you add glycol to the water do NOT install freeze protection valves Possibl...

Page 9: ...s can prevent that all water from indoor piping is drained when the freeze protection valves open NOTICE When freeze protection valves are installed do NOT select a minimum cooling setpoint lower than 8 C 8 C default If lower freeze protection valves can open during cooling operation Consult the installer reference guide of the unit for more detailed information Heater tape field supply 1 Install ...

Page 10: ...hout low voltage cables With low voltage cables 4 4 3 To connect the main power supply 1 Connect the main power supply In case of normal kWh rate power supply X1M X2M X5M X11YB X1A X11Y X11YA 1 2 3 1 2 3 a 1 2 3 Legend see illustration below In case of preferential kWh rate power supply Connect X11Y to X11YB X1M X2M X5M X11Y X11YB X1A 1 2 3 1 N L N L 2 3 S1S a b c X11YA 5 1 2 3 6 9 10 a Interconne...

Page 11: ...mits for voltage changes voltage fluctuations and flicker in public low voltage supply systems for equipment with rated current 75 A provided that the system impedance Zsys is less than or equal to Zmax at the interface point between the user s supply and the public system It is the responsibility of the installer or user of the equipment to ensure by consultation with the distribution network ope...

Page 12: ...tic hot water pump cable to the appropriate terminals as shown in the illustration below X1M X2M X5M 1 M M2P 1 2 2 Fix the cable with cable ties to the cable tie mountings 4 4 8 To connect the alarm output 1 Connect the alarm output cable to the appropriate terminals as shown in the illustration below X1M X2M A4P X5M X1M YC Y1 Y2 Y3 Y4 Y1 YC a 7 9 b a Installation of EKRP1HB is required b Prewirin...

Page 13: ... and the 3 way valve INFORMATION After it is installed do NOT forget to configure the safety thermostat Without configuration the indoor unit will ignore the safety thermostat contact INFORMATION The preferential kWh rate power supply contact is connected to the same terminals X5M 9 10 as the safety thermostat It is only possible for the system to have EITHER preferential kWh rate power supply OR ...

Page 14: ...proceed Installer pin code The Installer pin code is 5678 Additional menu items and installer settings are now available 5678 Installer Advanced user pin code The Advanced user pin code is 1234 Additional menu items for the user are now visible User pin code The User pin code is 0000 To access the installer settings 1 Set the user permission level to Installer 2 Go to 9 Installer settings To modif...

Page 15: ...er interface To recover operation manually go to the Malfunctioning main menu screen where the user interface will then ask you to confirm whether the backup heater can take over the heat load or not We recommend to set Emergency to Automatic if the house is unattended for longer periods Code Description 9 5 N A 0 Manual 1 Automatic INFORMATION The auto emergency setting can be set in the menu str...

Page 16: ...tep of the backup heater at nominal voltage Additional capacity step 2 Code Description 9 3 5 6 04 The capacity difference between the second and first step of the backup heater at nominal voltage Nominal value depends on backup heater configuration 5 2 5 Configuration wizard Main zone The most important settings for the main leaving water zone can be set here Emitter type Depending on the system ...

Page 17: ...Underfloor heating 1 Fancoil unit 2 Radiator Control The control type is displayed here but cannot be adjusted It is determined by the control type of the main zone For more info about the functionality see 5 2 5 Configuration wizard Main zone on page 16 Code Description 3 9 N A 0 Leaving water if the control type of the main zone is Leaving water 1 External room thermostat if the control type of ...

Page 18: ...e reheat mode during reheat mode the guaranteed minimum tank temperature is set by the Reheat setpoint minus the reheat hysteresis If the tank temperature drops below this value the tank is heated up during storage comfort to prioritize the domestic hot water preparation When the tank temperature rises above this value domestic hot water preparation and space heating cooling are executed sequentia...

Page 19: ...efit kWh power supply Allow heater Allow pump 9 2 Domestic hot water Domestic hot water DHW pump DHW pump schedule Solar 9 9 Power consumption control Power consumption control Type Limit Limit 1 Limit 2 Limit 3 Limit 4 Priority heater Electricity meter 2 Electricity meter 1 9 A Energy metering 9 Installer settings Configuration wizard Domestic hot water Backup heater Emergency Balancing Water pip...

Page 20: ...switch box There are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units Backup heater circuit breaker F1B field supply is turned ON The correct pipe size is installed and the pipes are properly insulated There is NO water leak inside the indoor unit The shut off valves are properly installed and fully open The air purge valve is open at least 2 turns The pressure...

Page 21: ... avoid disturbances in the water circuit during the test run Shut off valve test Diverter valve test Bivalent signal test Alarm output test C H signal test DHW pump test 6 2 5 To perform an underfloor heating screed dryout Conditions Make sure all operation is disabled Go to the Operation menu and turn off Room Space heating cooling and Tank operation 1 Set the user permission level to Installer S...

Page 22: ...1L B f B f A Water side B Field installed a1 Space heating water IN a2 Space heating water OUT b1 Domestic hot water cold water IN b2 Domestic hot water hot water OUT c1 Water IN connection c2 Water OUT connection d Pump e Backup heater f Shut off valve for service if equipped g Expansion vessel h Magnetic filter dirt separator i Safety valve j Air purge k Drain valve B1L Flow sensor B1PW Space he...

Page 23: ...eaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translation Position in switch box Position in switch box Legend A1P Main PCB A2P On OFF thermostat PC power circuit A3P Heat pump convector A4P Digital I O PCB A8P De...

Page 24: ...ush Inrush current Max load Maximum load Normally closed Normally closed Normally open Normally open Safety thermostat contact 16 V DC detection voltage supplied by PCB Safety thermostat contact 16 V DC detection voltage supplied by PCB English Translation Shut off valve Shut off valve SWB Switch box 7 Option PCBs 7 Option PCBs Alarm output Alarm output Changeover to ext heat source Changeover to ...

Page 25: ...al signal 2 core 2 core 2 core signal 2 core 2 core External sensor floor or ambient Only for KRTETS signal 2 core 3m included A13P P1 P2 LAN adapter A14P P1 P2 user interface Only for EKRUDAS Only for KRTR wireless room thermostat Only for KRTW wired room thermostat 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H only operation communication 2 core commu...

Page 26: ......

Page 27: ......

Page 28: ...4P556067 1 2018 10 Copyright 2018 Daikin 4P556067 1 0000000R ...

Reviews: