9 Disposal

Operation manual

19

EWSAH/X06(U)D
Daikin Altherma 3 WS
4P675761-1C – 2023.02

8.4

Symptom: The water at the tap is
too cold

Possible cause

Corrective action

You ran out of domestic hot
water because of unusually high
consumption.

If you immediately need domestic
hot water, activate the DHW tank

Powerful operation

. However,

this consumes extra energy. See

"5.7.4 Using DHW powerful
operation"

 [

4

 13].

If the problems recurs daily, do
one of the following:

▪ Increase 

the 

DHW 

tank

temperature  preset  value.  See
the user reference guide.

▪ Adjust 

the 

DHW 

tank

temperature 

schedule.

Example: 

Program 

to

additionally 

heat 

up 

the

DHW  tank  to  a  preset  value
(

Eco  setpoint

  =  lower  tank

temperature)  during  the  day.
See 

"5.8  Schedule  screen:

Example"

 [

4

 13].

The desired DHW tank
temperature is too low.

8.5

Symptom: Heat pump failure

When  the  heat  pump  fails  to  operate,  the  backup  heater  can  serve
as  an  emergency  heater.  It  then  takes  over  the  heat  load  either
automatically or by manual interaction.

▪ When 

Emergency

  is  set  to 

Automatic

  and  a  heat  pump  failure

occurs,  the  backup  heater  automatically  takes  over  the  domestic
hot water production and space heating.

▪ When 

Emergency

  is  set  to 

Manual

  and  a  heat  pump  failure

occurs, the domestic hot water heating and space heating stops.

To  manually  recover  it  via  the  user  interface,  go  to  the

Malfunctioning

  main  menu  screen  and  confirm  whether  the

backup heater can take over the heat load or not.

▪ Alternatively, when 

Emergency

 is set to:

auto  SH  reduced/DHW  on

,  space  heating  is  reduced  but

domestic hot water is still available.

auto  SH  reduced/DHW  off

,  space  heating  is  reduced  and

domestic hot water is NOT available.

auto  SH  normal/DHW  off

,  space  heating  operates  as

normally but domestic hot water is NOT available.

Similarly  as  in 

Manual

  mode,  the  unit  can  take  the  full  load  with

the  backup  heater  if  the  user  activates  this  via  the

Malfunctioning

 main menu screen.

When  the  heat  pump  fails, 

  or 

  will  appear  on  the  user

interface.

Possible cause

Corrective action

Heat pump is damaged.

See 

"8.1 To display the help text

in case of a malfunction"

 [

4

 18].

INFORMATION

When  the  backup  heater  takes  over  the  heat  load,
electricity consumption will be considerably higher.

8.6

Symptom: The system is making
gurgling noises after
commissioning

Possible cause

Corrective action

There is air in the system.

Purge air from the system.

(a)

Incorrect hydraulic balance.

To be performed by the installer:

1

Perform  hydraulic  balancing
to  assure  that  the  flow  is
correctly 

distributed

between the emitters.

2

If  hydraulic  balancing  is  not
sufficient,  change  the  pump
limitation  settings  ([9-0D]
and [9-0E] if applicable).

Various malfunctions.

Check if 

 or 

 is displayed

on the home screen of the user
interface. See 

"8.1 To display the

help text in case of a
malfunction"

 [

4

 18] for more

information about the
malfunction.

(a)

We recommend to purge air with the air purge function of the unit
(to be performed by the installer). If you purge air from the heat
emitters or collectors, mind the following:

WARNING

Air  purging  heat  emitters  or  collectors.

  Before  you

purge  air  from  heat  emitters  or  collectors,  check  if 

  or

 is displayed on the home screen of the user interface.

▪ If not, you can purge air immediately.

▪ If  yes,  make  sure  that  the  room  where  you  want  to

purge air is sufficiently ventilated. 

Reason:

 Refrigerant

might leak into the water circuit, and subsequently into
the room when you purge air from the heat emitters or
collectors.

9

Disposal

NOTICE

Do  NOT  try  to  dismantle  the  system  yourself:  dismantling
of  the  system,  treatment  of  the  refrigerant,  oil  and  other
parts  MUST  comply  with  applicable  legislation.  Units
MUST  be  treated  at  a  specialised  treatment  facility  for
reuse, recycling and recovery.

10

Glossary

DHW = Domestic hot water

Hot  water  used,  in  any  type  of  building,  for  domestic
purposes.

LWT = Leaving water temperature

Water temperature at the water outlet of the unit.

Summary of Contents for Altherma 3 WS EWSAH06D 9W

Page 1: ...Operation manual Daikin Altherma 3 WS English Operation manual Daikin Altherma 3 WS EWSAH06D 9W EWSAH06UD 9W EWSAX06D 9W EWSAX06UD 9W 1 2 3 9 A B C Z 1 2 3 9...

Page 2: ...d in by installer 20 11 1 Configuration wizard 20 11 2 Settings menu 20 1 About this document Thank you for purchasing this product Please Read the documentation carefully before operating the user in...

Page 3: ...ace any objects containing water on the unit CAUTION Do NOT place any objects or equipment on top of the unit Do NOT sit climb or stand on the unit Units are marked with the following symbol This mean...

Page 4: ...If not you can purge air immediately If yes make sure that the room where you want to purge air is sufficiently ventilated Reason Refrigerant might leak into the water circuit and subsequently into th...

Page 5: ...l room thermostat control the protection is NOT guaranteed 1 Go to C 2 Operation Space heating cooling Operation Space heating cooling Tank Off On C 2 2 Set operation to On or Off To change the desire...

Page 6: ...ugh the temperatures Change the temperature Go to the next temperature Confirm changes and proceed More information For more information see also 5 4 Turning operation ON or OFF 411 5 6 Space heating...

Page 7: ...s and buttons To navigate through the screens menus and settings of the LCD screen To set values a b c d e Item Description a Left dial The LCD shows an arc on the left side of the display when you ca...

Page 8: ...tpoint Eco setpoint Reheat setpoint Schedule WD curve type 8 Information Energy data Malfunction history Dealer information Sensors Actuators Operation modes About Connection status Running hours B Us...

Page 9: ...off e Space operation mode Cooling Heating f Outdoor quiet mode f1 6 Measured outdoor temperature a f2 Quiet mode active f3 Central water loop circuit g Indoor unit domestic hot water tank g1 Floor s...

Page 10: ...ace heating cooling Shows the applicable symbol of your unit Put the unit in heating mode or cooling mode You cannot change the mode on heating only models 5 Tank Set the domestic hot water tank tempe...

Page 11: ...ain active However if you turn it OFF while disinfection is running an AH error occurs 1 Go to C 3 Operation Tank Operation Tank Off On Space heating cooling C 3 2 Set operation to On or Off 5 5 Readi...

Page 12: ...esired room temperature The temperature will stay the same as long as there is no scheduled action The desired room temperature will return to its scheduled value whenever a scheduled action occurs Yo...

Page 13: ...About powerful operation Powerful operation allows the domestic hot water to be heated by the backup heater Use this mode on days when there is more hot water usage than usual To check if powerful ope...

Page 14: ...entry with the right dial You can program up to 6 actions each day On the bar a high temperature has a darker colour than a low temperature 0 6 00 8 30 17 30 20 C 18 C 22 00 18 C 21 C 12 24 Mon Note...

Page 15: ...or on the North wall of the building If the outdoor temperature drops or rises the unit compensates instantly Thus the unit does not have to wait for feedback by the thermostat to increase or decrease...

Page 16: ...temperature for all ambient temperatures Examples Weather dependent curve when slope is selected X1 X2 c d e Y1 Y2 Y3 Y4 a b Weather dependent curve when offset is selected Y1 Y2 Y3 Y4 X1 X2 a b c d...

Page 17: ...s Y2 a Y1 a X1 a X2 a OK Cold OK Hot Cold OK Cold Cold Cold Hot Hot OK Hot Cold Hot Hot a See 5 9 2 2 points curve 415 6 Energy saving tips Tips about room temperature Make sure the desired room tempe...

Page 18: ...ierce or burn refrigerant cycle parts Do NOT use cleaning materials or means to accelerate the defrosting process other than those recommended by the manufacturer Be aware that the refrigerant inside...

Page 19: ...er activates this via the Malfunctioning main menu screen When the heat pump fails or will appear on the user interface Possible cause Corrective action Heat pump is damaged See 8 1 To display the hel...

Page 20: ...ncy 9 5 Number of zones 4 4 Backup heater Voltage 9 3 2 Maximum capacity 9 3 9 Main zone Emitter type 2 7 Control 2 9 Setpoint mode 2 4 Schedule 2 1 WD curve type 2 E Additional zone only if 4 4 1 dua...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...4P675761 1C 2023 02 Copyright 2021 Daikin 4P675761 1 C 00000004 Verantwortung f r Energie und Umwelt...

Reviews: