background image

5 Electrical installation

Installation manual

11

ETVH/9W(G)
Daikin Altherma 3 H HT F
4P586454-1C – 2020.12

Item

Description

WLAN adapter

See:

▪ Installation  manual  of  the  WLAN

adapter

▪ Addendum 

book 

for 

optional

equipment

Use the cable delivered with the
WLAN adapter.

[D] 

Wireless gateway

LAN adapter

See:

▪ Installation  manual  of  the  LAN

adapter

▪ Addendum 

book 

for 

optional

equipment

Wires: 2×(0.75~1.25 mm²). Must be
sheathed.

Maximum length: 200 m

See below ("LAN adapter – System
requirements").

LAN adapter – System requirements

The requirements posed on the system depend on the LAN adapter
application/system layout (app control, or Smart Grid application).

App control:

Item

Requirement

LAN adapter software It is recommended to ALWAYS keep the

LAN adapter software up-to-date.

Unit control method

On the user interface, make sure to set
[2.9]=2 (

Control

 = 

Room thermostat

)

Smart Grid application:

Item

Requirement

LAN adapter software It is recommended to ALWAYS keep the

LAN adapter software up-to-date.

Unit control method

On the user interface, make sure to set
[2.9]=2 (

Control

 = 

Room thermostat

)

Domestic hot water
settings

To allow for energy buffering in the domestic
hot water tank, on the user interface, make
sure to set [9.2.1]=4 (

Domestic hot water

Integrated

).

Power consumption
control settings

On the user interface, make sure to set:

▪ [9.9.1]=1  (

Power  consumption  control

Continuous

)

▪ [9.9.2]=1 (

Type

 = 

kW

)

5.3.1

To connect the main power supply

1

Open the following (see 

"To open the indoor unit"

 [

4

 5]):

1

Top panel

1

2

3

2

User interface panel

3

Upper switch box cover

2

Connect the main power supply.

In case of normal kWh rate power supply

Interconnection
cable (= main
power supply)

Wires: (3+GND)×1.5 mm²

A

1 2 3

a

B

A

B

1 2 3

X2M

X1A

X11YA

X11YB

X11Y

X1M

a

a

Interconnection cable (=main power supply)

In case of preferential kWh rate power supply

Interconnection
cable (= main
power supply)

Wires: (3+GND)×1.5 mm²

Normal kWh rate
power supply

Wires: 1N

Maximum running current: 6.3 A

Preferential kWh
rate power supply
contact

Wires: 2×(0.75~1.25 mm²)

Maximum length: 50 m.

Preferential kWh rate power supply
contact: 16 V DC detection (voltage
supplied by PCB). The voltage-free
contact shall ensure the minimum
applicable load of 15 V DC, 10 mA.

[9.8] 

Benefit kWh power supply

Connect X11Y to X11YB.

Summary of Contents for Altherma 3 H HT F ETVH16S18DA6VG

Page 1: ...therma 3 H HT F English https daikintechnicaldatahub eu Installation manual Daikin Altherma 3 H HT F ETVH16S18DA6V G ETVH16S23DA6V G ETVH16S18DA9W G ETVH16S23DA9W G ETVX16S18DA6V G ETVX16S23DA6V G ETV...

Page 2: ...ou vyu v ny v souladu s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u...

Page 3: ...ckup heater 20 6 2 5 Configuration wizard Main zone 20 6 2 6 Configuration wizard Additional zone 21 6 2 7 Configuration wizard Tank 22 6 3 Weather dependent curve 22 6 3 1 What is a weather dependent...

Page 4: ...ddendum book for optional equipment e Indoor unit installation manual f Operation manual g Sealing rings for shut off valves space heating water circuit h Sealing rings for field supplied shut off val...

Page 5: ...the hinges at the top and slide the top panel upwards NOTICE If you remove the user interface panel also disconnect the cables from the back of the user interface panel to prevent damage 2 1 1 3 3 Re...

Page 6: ...t from the pallet and place it on the floor Also see To handle the indoor unit 44 2 Connect the drain hose to the drain See To connect the drain hose to the drain 46 3 Slide the indoor unit into posit...

Page 7: ...pump test check that the user interface does NOT display error 7H NOTICE When circulation in each or certain space heating loops is controlled by remotely controlled valves it is important that the mi...

Page 8: ...nclude the activation of pump in case of low temperatures However in case of a power failure these functions cannot guarantee protection Do one of the following to protect the water circuit against fr...

Page 9: ...set correctly the liquid inside the piping can freeze Freeze protection by freeze protection valves About freeze protection valves When no glycol is added to the water you can use freeze protection va...

Page 10: ...ndum book for optional equipment Wires 0 75 mm Maximum running current 100 mA For the main zone 2 9 Control 2 A Thermostat type For the additional zone 3 A Thermostat type 3 9 read only Control Item D...

Page 11: ...interface make sure to set 2 9 2 Control Room thermostat Domestic hot water settings To allow for energy buffering in the domestic hot water tank on the user interface make sure to set 9 2 1 4 Domesti...

Page 12: ...rthed always connect the backup heater power supply and the earth cable The backup heater capacity can vary depending on the indoor unit model Make sure that the power supply is in accordance with the...

Page 13: ...itch box X6M Terminal field supply NOTICE Do NOT cut or remove the backup heater power supply cable 5 3 3 To connect the shut off valve INFORMATION Shut off valve usage example In case of one LWT zone...

Page 14: ...o the cable tie mountings 5 3 5 To connect the domestic hot water pump Wires 2 GND 0 75 mm DHW pump output Maximum load 2 A inrush 230 V AC 1 A continuous 9 2 2 DHW pump 9 2 3 DHW pump schedule 1 Open...

Page 15: ...2 Connect the space cooling heating ON OFF output cable to the appropriate terminals as shown in the illustration below 7 9 YC Y2 X2M 1 2 3 A4P 1 2 Wires connected to the space cooling heating ON OFF...

Page 16: ...nsumption digital inputs cable to the appropriate terminals as shown in the illustration below A 1 2 4 5 S6S S7S S8S S9S 3 B A B A8P X801M a 1 2 3 4 5 a Installation of EKRP1AHTA is required 3 Fix the...

Page 17: ...NV2 6 1 Overview Configuration This chapter describes what you have to do and know to configure the system after it is installed NOTICE This chapter explains only the basic configuration For more deta...

Page 18: ...t settings can be configured via the menu structure If for any reason it is required to change a setting using the overview settings then the overview settings can be accessed as follows 1 Set the use...

Page 19: ...to the Malfunctioning main menu screen and confirm whether the backup heater can take over the heat load or not Alternatively when Emergency is set to auto SH reduced DHW on space heating is reduced...

Page 20: ...30V 3ph 2 400V 3ph Configuration The backup heater can be configured in different ways It can be chosen to have a 1 step only backup heater or a backup heater with 2 steps If 2 steps the capacity of t...

Page 21: ...pend on the outdoor ambient temperature for cooling In Weather dependent mode the desired leaving water temperature depends on the outdoor ambient temperature Code Description 2 4 N A Setpoint mode Fi...

Page 22: ...is If the tank temperature drops below this value the tank is heated up during storage comfort to prioritize the domestic hot water preparation When the tank temperature rises above this value domesti...

Page 23: ...different ambient temperatures For example if leaving water temperature is always a bit too cold at different ambient temperatures shift the offset up to equally increase the leaving water temperature...

Page 24: ...oint is reached the curve flattens out To fine tune the weather dependent curve slope offset curve The following table describes how to fine tune the weather dependent curve of a zone or tank You feel...

Page 25: ...F 4P586454 1C 2020 12 Code Description 3 A C 06 External room thermostat type for the additional zone 1 1 contact 2 2 contacts 6 4 3 Information Dealer information The installer can fill in his contac...

Page 26: ...g 9 B Sensors External sensor Ext amb sensor offset Averaging time 9 C Bivalent Bivalent Boiler efficiency Temperature Hysteresis 9 9 Power consumption control Power consumption control Type Limit Lim...

Page 27: ...the local supply panel and the outdoor unit Between indoor unit and outdoor unit Between the local supply panel and the indoor unit Between the indoor unit and the valves if applicable Between the ind...

Page 28: ...fferent actuators For example when you select Pump a test run of the pump will start 1 Set the user permission level to Installer See To change the user permission level 418 2 Go to A 2 Commissioning...

Page 29: ...sure the following is clear for the user Fill in the installer setting table in the operation manual with the actual settings Make sure that the user has the printed documentation and ask him her to...

Page 30: ...ating cooling Water IN screw connection 1 a2 Space heating cooling Water OUT screw connection 1 b1 DHW Cold water IN screw connection 3 4 b2 DHW Hot water OUT screw connection 3 4 c1 Water IN from out...

Page 31: ...ired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translation...

Page 32: ...rmostat For safety thermostat Inrush Inrush current Max load Maximum load Normally closed Normally closed Normally open Normally open Safety thermostat contact 16 V DC detection voltage supplied by PC...

Page 33: ...core signal 2 core 2 core 2 core 2 core 2 core 3 core R2T External sensor floor or ambient Only for KRTETS signal 2 core 3m included A13P P1 P2 LAN adapter A14P P1 P2 user interface Only for Human Co...

Page 34: ......

Page 35: ......

Page 36: ...4P586454 1C 2020 12 Copyright 2019 Daikin 4P586454 1 C 00000004 Verantwortung f r Energie und Umwelt...

Reviews: