2 About the box

Installation manual

4

ETVH/9W(G)

Daikin Altherma 3 H HT F

4P586454-1C – 2020.12

Technical engineering data

▪ A 

subset

  of  the  latest  technical  data  is  available  on  the  regional

Daikin website (publicly accessible).

▪ The 

full  set

  of  latest  technical  data  is  available  on  the  Daikin

Business Portal (authentication required).

Online tools

In addition to the documentation set, some online tools are available
for installers:

Daikin Technical Data Hub

▪ Central hub for technical specifications of the unit, useful tools,

digital resources, and more.

▪ Publicly accessible via 

https://daikintechnicaldatahub.eu

.

Heating Solutions Navigator

▪ Digital  toolbox  that  offers  a  variety  of  tools  to  facilitate  the

installation and configuration of heating systems.

▪ To  access  Heating  Solutions  Navigator,  registration  to  the

Stand  By  Me  platform  is  required.  For  more  information,  see

https://professional.standbyme.daikin.eu

.

Daikin e-Care

▪ Mobile app for installers and service technicians that allows you

to register, configure and troubleshoot heating systems.

▪ The  mobile  app  can  be  downloaded  for  iOS  and  Android

devices  using  the  QR  codes  below.  Registration  to  the  Stand
By Me platform is required to access the app.

App Store

Google Play

2

About the box

2.1

Indoor unit

2.1.1

To remove the accessories from the
indoor unit

a

b

g

h

i

c

d

e

f

a

Shut-off valves for water circuit

b

Overpressure bypass valve

c

General safety precautions

d

Addendum book for optional equipment

e

Indoor unit installation manual

f

Operation manual

g

Sealing rings for shut-off valves (space heating water
circuit)

h

Sealing rings for field-supplied shut-off valves (domestic
hot water circuit)

i

Sealing tape for low voltage wiring intake

2.1.2

To handle the indoor unit

Use the handles at the back and at the bottom to carry the unit.

b

a

a

b

a

Handles at the back of the unit

b

Handles at the bottom of the unit. Carefully tilt the unit to
the back so that the handles become visible.

3

Unit installation

3.1

Preparing the installation site

WARNING

The  appliance  shall  be  stored  in  a  room  without
continuously  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater).

3.1.1

Installation site requirements of the
indoor unit

▪ The indoor unit is designed for indoor installation only and for the

following ambient temperatures:

▪ Space heating operation: 5~30°C

▪ Space cooling operation: 5~35°C

▪ Domestic hot water production: 5~35°C

INFORMATION

Cooling is only applicable in case of:

▪ Reversible models

▪ Heating only conversion kit (EKHVCONV2)

▪ Mind the measurement guidelines:

Maximum height difference between indoor unit and
outdoor unit

10 m

Maximum total water piping length

50 m

(a)

(a)

Precise water piping length can be determined using the Hydronic
Piping Calculation tool. The Hydronic Piping Calculation tool is
part of the Heating Solutions Navigator which can be reached via

https://professional.standbyme.daikin.eu

. Please contact your

dealer if you have no access to Heating Solutions Navigator.

▪ Mind the following spacing installation guidelines:

≥300

≥600

≥500

(mm)

Summary of Contents for Altherma 3 H HT F ETVH16S18DA6VG

Page 1: ...therma 3 H HT F English https daikintechnicaldatahub eu Installation manual Daikin Altherma 3 H HT F ETVH16S18DA6V G ETVH16S23DA6V G ETVH16S18DA9W G ETVH16S23DA9W G ETVX16S18DA6V G ETVX16S23DA6V G ETV...

Page 2: ...ou vyu v ny v souladu s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u...

Page 3: ...ckup heater 20 6 2 5 Configuration wizard Main zone 20 6 2 6 Configuration wizard Additional zone 21 6 2 7 Configuration wizard Tank 22 6 3 Weather dependent curve 22 6 3 1 What is a weather dependent...

Page 4: ...ddendum book for optional equipment e Indoor unit installation manual f Operation manual g Sealing rings for shut off valves space heating water circuit h Sealing rings for field supplied shut off val...

Page 5: ...the hinges at the top and slide the top panel upwards NOTICE If you remove the user interface panel also disconnect the cables from the back of the user interface panel to prevent damage 2 1 1 3 3 Re...

Page 6: ...t from the pallet and place it on the floor Also see To handle the indoor unit 44 2 Connect the drain hose to the drain See To connect the drain hose to the drain 46 3 Slide the indoor unit into posit...

Page 7: ...pump test check that the user interface does NOT display error 7H NOTICE When circulation in each or certain space heating loops is controlled by remotely controlled valves it is important that the mi...

Page 8: ...nclude the activation of pump in case of low temperatures However in case of a power failure these functions cannot guarantee protection Do one of the following to protect the water circuit against fr...

Page 9: ...set correctly the liquid inside the piping can freeze Freeze protection by freeze protection valves About freeze protection valves When no glycol is added to the water you can use freeze protection va...

Page 10: ...ndum book for optional equipment Wires 0 75 mm Maximum running current 100 mA For the main zone 2 9 Control 2 A Thermostat type For the additional zone 3 A Thermostat type 3 9 read only Control Item D...

Page 11: ...interface make sure to set 2 9 2 Control Room thermostat Domestic hot water settings To allow for energy buffering in the domestic hot water tank on the user interface make sure to set 9 2 1 4 Domesti...

Page 12: ...rthed always connect the backup heater power supply and the earth cable The backup heater capacity can vary depending on the indoor unit model Make sure that the power supply is in accordance with the...

Page 13: ...itch box X6M Terminal field supply NOTICE Do NOT cut or remove the backup heater power supply cable 5 3 3 To connect the shut off valve INFORMATION Shut off valve usage example In case of one LWT zone...

Page 14: ...o the cable tie mountings 5 3 5 To connect the domestic hot water pump Wires 2 GND 0 75 mm DHW pump output Maximum load 2 A inrush 230 V AC 1 A continuous 9 2 2 DHW pump 9 2 3 DHW pump schedule 1 Open...

Page 15: ...2 Connect the space cooling heating ON OFF output cable to the appropriate terminals as shown in the illustration below 7 9 YC Y2 X2M 1 2 3 A4P 1 2 Wires connected to the space cooling heating ON OFF...

Page 16: ...nsumption digital inputs cable to the appropriate terminals as shown in the illustration below A 1 2 4 5 S6S S7S S8S S9S 3 B A B A8P X801M a 1 2 3 4 5 a Installation of EKRP1AHTA is required 3 Fix the...

Page 17: ...NV2 6 1 Overview Configuration This chapter describes what you have to do and know to configure the system after it is installed NOTICE This chapter explains only the basic configuration For more deta...

Page 18: ...t settings can be configured via the menu structure If for any reason it is required to change a setting using the overview settings then the overview settings can be accessed as follows 1 Set the use...

Page 19: ...to the Malfunctioning main menu screen and confirm whether the backup heater can take over the heat load or not Alternatively when Emergency is set to auto SH reduced DHW on space heating is reduced...

Page 20: ...30V 3ph 2 400V 3ph Configuration The backup heater can be configured in different ways It can be chosen to have a 1 step only backup heater or a backup heater with 2 steps If 2 steps the capacity of t...

Page 21: ...pend on the outdoor ambient temperature for cooling In Weather dependent mode the desired leaving water temperature depends on the outdoor ambient temperature Code Description 2 4 N A Setpoint mode Fi...

Page 22: ...is If the tank temperature drops below this value the tank is heated up during storage comfort to prioritize the domestic hot water preparation When the tank temperature rises above this value domesti...

Page 23: ...different ambient temperatures For example if leaving water temperature is always a bit too cold at different ambient temperatures shift the offset up to equally increase the leaving water temperature...

Page 24: ...oint is reached the curve flattens out To fine tune the weather dependent curve slope offset curve The following table describes how to fine tune the weather dependent curve of a zone or tank You feel...

Page 25: ...F 4P586454 1C 2020 12 Code Description 3 A C 06 External room thermostat type for the additional zone 1 1 contact 2 2 contacts 6 4 3 Information Dealer information The installer can fill in his contac...

Page 26: ...g 9 B Sensors External sensor Ext amb sensor offset Averaging time 9 C Bivalent Bivalent Boiler efficiency Temperature Hysteresis 9 9 Power consumption control Power consumption control Type Limit Lim...

Page 27: ...the local supply panel and the outdoor unit Between indoor unit and outdoor unit Between the local supply panel and the indoor unit Between the indoor unit and the valves if applicable Between the ind...

Page 28: ...fferent actuators For example when you select Pump a test run of the pump will start 1 Set the user permission level to Installer See To change the user permission level 418 2 Go to A 2 Commissioning...

Page 29: ...sure the following is clear for the user Fill in the installer setting table in the operation manual with the actual settings Make sure that the user has the printed documentation and ask him her to...

Page 30: ...ating cooling Water IN screw connection 1 a2 Space heating cooling Water OUT screw connection 1 b1 DHW Cold water IN screw connection 3 4 b2 DHW Hot water OUT screw connection 3 4 c1 Water IN from out...

Page 31: ...ired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translation...

Page 32: ...rmostat For safety thermostat Inrush Inrush current Max load Maximum load Normally closed Normally closed Normally open Normally open Safety thermostat contact 16 V DC detection voltage supplied by PC...

Page 33: ...core signal 2 core 2 core 2 core 2 core 2 core 3 core R2T External sensor floor or ambient Only for KRTETS signal 2 core 3m included A13P P1 P2 LAN adapter A14P P1 P2 user interface Only for Human Co...

Page 34: ......

Page 35: ......

Page 36: ...4P586454 1C 2020 12 Copyright 2019 Daikin 4P586454 1 C 00000004 Verantwortung f r Energie und Umwelt...

Reviews: