41
Warning
code
Description
Cause
Corrective action
Check the wiring of the relevant thermistor.
Check the wiring of the relevant thermistor.
Check the wiring of the relevant thermistor.
Check the wiring of the relevant thermistor.
Use the unit within the specified operating range.
Inlet oil temperature thermistor error
Discharge pipe temperature
thermistor error
EV valve outlet temperature
thermistor error
Condenser temperature thermistor error
Radiator fin temperature thermistor error
High pressure error
JH
J3
J4
J6
Check the wiring of the relevant thermistor.
Check the wiring of the relevant thermistor.
Room temperature thermistor error
H1
P4
F6
1) There is an obstacle near the air intake/
exhaust port.
2) Operation outside the high temperature
range.
When a warning is activated
A warning is generated when the status of OILCON is not normal or the oil temperature to be
monitored exceeds the setting temperature range.
If you continue operation without a change, OILCON may break down. Be sure to take measures.
Warning list
Temperature range warning 1
Temperature range warning 5
1E
Temperature range warning 2
2E
Temperature range warning 3
3E
Temperature range warning 4
4E
5E
Check the preset warning condition.
1) The monitor temperature has exceeded
the preset temperature. (It does not mean
a fault of the Oil Cooling Unit.)
1) The discharge pipe temperature thermis-
tor is disconnected or short-circuited.
The system will be stopped to protect OIL-
CON by upgrading the state to an alarm
after operation for 150 hours.
1) Room temperature thermistor is discon-
nected or short-circuited.
(Only if it is not used for control)
1) Inlet oil temperature thermistor is discon-
nected or short-circuited. (When it is not
used for control)
1) The EV valve outlet temperature thermis-
tor is disconnected or short-circuited.
The system will be stopped to protect OIL-
CON by upgrading the state to an alarm
after operation for 150 hours.
1) The condenser temperature thermistor is
disconnected or short-circuited.
The system will be stopped to protect OIL-
CON by upgrading the state to an alarm
after operation for 150 hours.
1) The radiator fin temperature thermistor is
disconnected or short-circuited.
• Clean the air filter and condenser.
• Do not place any object that blocks ventilation at 500 mm or
shorter distance from the air intake/exhaust port.
Maintenance
Tr
oub
leshooting