In this section, set the following parameters by using three digits (first and second digits, and first decimal place) of each parameter
on the control panel data display.
• “Temperature range warning temperature setting” (Use the first and second digits.)
• “Temperature range warning reset temperature setting” (Use the first decimal place. Active only when “Warning” has been set.)
∗
1: When the first digit of the “temperature range warning operation setting” parameter of
Group A
is “4” or “5”, this parameter is inactive because
the warning status will not be automatically reset. (Enter any number from 0 to 9.)
Description on parameter settings (Group B)
Temperature range warning temperature
(1)
Temperature range warning reset temperature
(Temperature difference for automatic reset)
∗
1
0 to 60 (˚C)
1 to 9 (˚C)
Second digit
n011
(2)
n013
(3)
n015
(4)
n017
n011
15.2
∗
2
n013
35.0
n015
5.1
∗
3
n017
5.2
∗
4
First digit
First decimal place
(1)
When the outlet oil temperature [Th2] (or inlet oil temperature [Th4]) is 15
˚
C or lower, the compressor stops. (Warning)
[When outlet oil temperature [Th2] becomes 17
˚
C, the warning status will be automatically reset.]
When the outlet oil temperature [Th2] (or inlet oil temperature [Th4]) is 35
˚
C or higher, the compressor stops
(FH alarm), and the 30W relay output turns ON or OFF.
When the outlet oil temperature [Th2] (or inlet oil temperature [Th4]) is at least 5
˚
C lower than the room temperature
[Th3] (or machine temperature [Th1]), the 30W relay output turns ON or OFF.
When the difference between room temperature [Th3] and outlet oil temperature [Th2] becomes 4
˚
C or less, the warning
status will be automatically reset.
When the outlet oil temperature [Th2] (or inlet oil temperature [Th4]) is at least 5
˚
C higher than the room temperature
[Th3] (or machine temperature [Th1]), the 30W relay output turns ON or OFF.
When the difference between room temperature [Th3] and outlet oil temperature [Th2] becomes 3
˚
C or less, the warning
status will be automatically reset.
(2)
(3)
(4)
∗
2: 17 (Temperature range warning reset temperature)
–
15 (Temperature range warning temperature) = 2
∗
3: 5 (Temperature range warning temperature)
–
4 (Temperature range warning reset temperature) = 1
∗
4: 5 (Temperature range warning temperature)
–
3 (Temperature range warning reset temperature) = 2
Example of parameter settings (for temperature range warning: See page .)
27
∗
Example of parameter settings