5 Installation

Installation manual

9

FBA35~14FBA35~7ADEA35~125A2VEB
Split system air conditioners
4P456962-1D – 2018.08

Rising  piping

.  If  necessary  to  make  the  slope  possible,  you  can

install rising piping.

▪ Drain  hose  inclination:  0~75  mm  to  avoid  stress  on  the  piping

and to avoid air bubbles.

▪ Rising  piping:  ≤300  mm  from  the  unit,  ≤625  mm  perpendicular

to the unit.

≤625

≤300

0~75

1000~1500

(mm)

b

a

b

a

d

d

c

a

Metal clamp (accessory)

b

Drain hose (accessory)

c

Rising drain piping (vinyl pipe of 25 mm nominal diameter
and 32 mm outer diameter) (field supply)

d

Hanging bars (field supply)

Combining  drain  pipes.

  You  can  combine  drain  pipes.  Make

sure to use drain pipes and T-joints with the correct gauge for the
operating capacity of the units.

≥100

≤625

(mm)

a

a

T-joint

To connect the drain piping to the indoor unit

NOTICE

Incorrect  connection  of  the  drain  hose  might  cause  leaks,
and damage the installation space and surroundings.

1

Push  the  drain  hose  as  far  as  possible  over  the  drain  pipe
connection.

2

Tighten the metal clamp until the screw head is less than 4 mm
from the metal clamp part.

3

Check  for  water  leaks  (see 

"To  check  for  water  leaks"  on

page 9

).

4

Install the insulation piece (drain pipe).

5

Wind  the  large  sealing  pad  (=  insulation)  around  the  metal
clamp and drain hose, and fix it with cable ties.

6

Connect the drain piping to the drain hose.

≤4 mm

A

A'

A-A'

A

A'

f

6

5

2

c

e

4

b

a

d

b

a

d

c

3

1

2~6

1

a

Drain pipe connection (attached to the unit)

b

Drain hose (accessory)

c

Metal clamp (accessory)

d

Large sealing pad (accessory)

e

Insulation piece (drain pipe) (accessory)

f

Drain piping (field supply)

NOTICE

▪ Do NOT remove the drain pipe plug. Water might leak

out.

▪ Use  the  drain  outlet  only  to  discharge  the  water  if  the

drain pump is not used or before maintenance.

▪ Insert  and  remove  the  drain  plug  gently.  Excessive

force may deform the drain socket of the drain pan.

Pull out the plug.

▪ Do NOT wiggle the plug up and down.

a

Push in the plug.

▪ Set the plug and push it in using a Phillips screwdriver.

a

b

a

Drain plug

b

Phillips screwdriver

To check for water leaks

The  procedure  differs  depending  on  whether  electrical  wiring  is
already finished. When electrical wiring is not finished yet, you need
to  temporarily  connect  the  user  interface  and  power  supply  to  the
unit.

When electrical wiring is not finished yet

1

Temporarily connect electrical wiring.

2

Remove the switch box cover (a).

3

Connect  the  single-phase  power  supply  (50  Hz,  230  V)  to
connections  No.  1  and  No.  2  on  the  terminal  block  for  power
supply and earth.

4

Reattach the switch box cover (a).

Summary of Contents for ADEA100A2VEB

Page 1: ...ish Installation manual Split system air conditioners FBA35A2VEB FBA50A2VEB FBA60A2VEB FBA71A2VEB FBA100A2VEB FBA125A2VEB FBA140A2VEB FBA35A2VEB9 FBA50A2VEB9 FBA60A2VEB9 FBA71A2VEB9 ADEA35A2VEB ADEA50A2VEB ADEA60A2VEB ADEA71A2VEB ADEA100A2VEB ADEA125A2VEB ...

Page 2: ...ilizate în conformitate cu instrucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите и...

Page 3: ...ate cu instrucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka ž...

Page 4: ...e în conformitate cu instrucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструк...

Page 5: ... users in shops in light industry and on farms or for commercial and household use by lay persons Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you MUST read before installing Format Paper in the box of the indoor unit Indoor unit installation manual Installation instructions Format Paper in the box o...

Page 6: ...any place where flammable gas may leak out If the gas leaks out and stays around the air conditioner a fire may break out 4 1 1 Installation site requirements of the indoor unit INFORMATION The sound pressure level is less than 70 dBA Use suspension bolts for installation Spacing Mind the following requirements 500 a e d b c f g a Service space b Drain pipe c Power supply wiring port d Transmissio...

Page 7: ...the flange c Fixing screw Ceiling strength Check whether the ceiling is strong enough to support the weight of the unit If there is a risk reinforce the ceiling before installing the unit Installation options a c e b 125 460 160 160 300 375 a c b 460 d d f f 125 300 A B Class f mm 35 50 760 60 71 1060 Class f mm 100 140 1460 A Mounting the air inlet with a canvas connection B Mounting the air inle...

Page 8: ...room by ducting Do NOT use spaces such as a false ceiling as a duct for the air inlet or outlet WARNING Do NOT install operating ignition sources example open flames an operating gas appliance or an operating electric heater in the duct work The ducting is to be field supplied Air inlet side Attach the duct and intake side flange field supply For connecting the flange use 7 accessory screws a b b ...

Page 9: ... insulation piece drain pipe 5 Wind the large sealing pad insulation around the metal clamp and drain hose and fix it with cable ties 6 Connect the drain piping to the drain hose 4 mm A A A A A A f 6 5 2 c e 4 b a d b a d c 3 1 2 6 1 a Drain pipe connection attached to the unit b Drain hose accessory c Metal clamp accessory d Large sealing pad accessory e Insulation piece drain pipe accessory f Dr...

Page 10: ...ntly resistant to corrosion or are suitably protected against corrosion WARNING FLAMMABLE MATERIAL The R32 refrigerant if applicable in this unit is mildly flammable Refer to the outdoor unit specifications for the type of refrigerant to be used Pipe length Keep refrigerant piping as short as possible Flare connections Connect refrigerant piping to the unit using flare connections Insulation Insul...

Page 11: ...e electrical wiring does NOT obstruct proper reattachment of the service cover It is important to keep the power supply and the transmission wiring separated from each other In order to avoid any electrical interference the distance between both wirings should ALWAYS be at least 50 mm NOTICE Be sure to keep the power line and transmission line apart from each other Transmission wiring and power su...

Page 12: ...t the equipment is connected only to a supply with a short circuit power Ssc greater than or equal to the minimum Ssc value Ensure that equipment is connected only to a supply with a short circuit power Ssc greater than or equal to Ssc in table below Combination FBA35A FBA50A FBA60A FBA71A RZAG71M 2 1 RZQG71L RZAG100M 3 2 31 2 1 30 RZQG100L RZAG125M 4 3 33 3 2 32 2 2 05 RZQG125L RZAG140M 4 3 33 3 ...

Page 13: ...ICE NEVER operate the unit without thermistors and or pressure sensors switches Burning of the compressor might result 7 1 Checklist before commissioning After the installation of the unit first check the following items Once all below checks are fulfilled the unit MUST be closed ONLY then can the unit be powered up You read the complete installation instructions as described in the installer refe...

Page 14: ...door unit has NOT been done correctly the following error codes may be displayed on the user interface Error code Possible cause Nothing displayed the currently set temperature is not displayed The wiring is disconnected or there is a wiring error between power supply and outdoor unit between outdoor unit and indoor units between indoor unit and user interface The fuse on the outdoor or indoor uni...

Page 15: ...ND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MAGNETIC RELAY L LIVE L COIL L R REACTOR M STEPPER MOTOR M C COMPRESSOR MOTOR M F FAN MOTOR M P DRAIN PUMP MOTOR M S SWING MOTOR MR MRCW MRM MRN MAGNETIC RELAY N NEUTRAL n N NUMBER OF PASSES TH...

Page 16: ...4P456962 1D 2018 08 Copyright 2017 Daikin ...

Reviews: