5 Installation

Installation manual

11

FBA35~14FBA35~7ADEA35~125A2VEB
Split system air conditioners
4P456962-1D – 2018.08

2

Check  for  leaks  by  applying  the  bubble  test  solution  to  all
connections.

3

Discharge all nitrogen gas.

5.3

Connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

5.3.1

Specifications of standard wiring
components

Component

Class

35+50 60+71

100

125+140

Power supply
cable

MCA

(a)

1.4 A

1.3 A

3.5 A

3.9 A

Voltage

220~240 V

Phase

1~

Frequency

50/60 Hz

Wire sizes

Must comply with applicable

legislation

Interconnection cable

Minimum cable section of

2.5 mm² and applicable for

220~240 V

User interface cable

Vinyl cord with 0.75 to 1.25 mm

2

sheath or cables (2 core wires)

Maximum 500 m

Recommended field fuse

16 A

Earth leakage circuit breaker

Must comply with applicable

legislation

(a)

MCA=Minimum circuit ampacity. Stated values are
maximum values (see electrical data of combination with
indoor units for exact values).

5.3.2

To connect the electrical wiring on the
indoor unit

NOTICE

▪ Follow  the  wiring  diagram  (delivered  with  the  unit,

located on the switch box cover).

▪ Make  sure  the  electrical  wiring  does  NOT  obstruct

proper reattachment of the service cover.

It is important to keep the power supply and the transmission wiring
separated  from  each  other.  In  order  to  avoid  any  electrical
interference  the  distance  between  both  wirings  should  ALWAYS  be
at least 50 mm.

NOTICE

Be sure to keep the power line and transmission line apart
from  each  other.  Transmission  wiring  and  power  supply
wiring may cross, but may NOT run parallel.

1

Remove the service cover.

2

User  interface  cable

:  Route  the  cable  through  the  frame,

connect the cable to the terminal block, and fix the cable with a
cable tie.

3

Interconnection  cable

  (indoor↔outdoor):  Route  the  cable

through  the  frame,  connect  the  cable  to  the  terminal  block
(make  sure  the  numbers  match  with  the  numbers  on  the
outdoor unit, and connect the earth wire), and fix the cable with
a cable tie.

4

Divide  the  small  sealing  (accessory)  and  wrap  it  around  the
cables to prevent water from entering the unit. Seal all gaps to
prevent small animals from entering the system.

WARNING

Provide adequate measures to prevent that the unit can be
used  as  a  shelter  by  small  animals.  Small  animals  that
make contact with electrical parts can cause malfunctions,
smoke or fire.

5

Reattach the service cover.

When using 1 user interface with 1 indoor unit.

1 2 3

a

a

a

b

c

1 2 3

P

1

P

2

P

1

P

2

d

1 2

L N

3

b

c

b

c

1 2 3

P

1

P

2

P

1

P

2

d

L N

L N

L N

When using 2 user interfaces

2

1 2 3

b

c

1 2 3

P

1

P

2

P

1

P

2

P

1

P

2

d

d

a

L N

b

c

a

L N

When using group control

2

(2)

Dashed line represents separate power supply.

Summary of Contents for ADEA100A2VEB

Page 1: ...ish Installation manual Split system air conditioners FBA35A2VEB FBA50A2VEB FBA60A2VEB FBA71A2VEB FBA100A2VEB FBA125A2VEB FBA140A2VEB FBA35A2VEB9 FBA50A2VEB9 FBA60A2VEB9 FBA71A2VEB9 ADEA35A2VEB ADEA50A2VEB ADEA60A2VEB ADEA71A2VEB ADEA100A2VEB ADEA125A2VEB ...

Page 2: ...ilizate în conformitate cu instrucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите и...

Page 3: ...ate cu instrucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka ž...

Page 4: ...e în conformitate cu instrucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструк...

Page 5: ... users in shops in light industry and on farms or for commercial and household use by lay persons Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you MUST read before installing Format Paper in the box of the indoor unit Indoor unit installation manual Installation instructions Format Paper in the box o...

Page 6: ...any place where flammable gas may leak out If the gas leaks out and stays around the air conditioner a fire may break out 4 1 1 Installation site requirements of the indoor unit INFORMATION The sound pressure level is less than 70 dBA Use suspension bolts for installation Spacing Mind the following requirements 500 a e d b c f g a Service space b Drain pipe c Power supply wiring port d Transmissio...

Page 7: ...the flange c Fixing screw Ceiling strength Check whether the ceiling is strong enough to support the weight of the unit If there is a risk reinforce the ceiling before installing the unit Installation options a c e b 125 460 160 160 300 375 a c b 460 d d f f 125 300 A B Class f mm 35 50 760 60 71 1060 Class f mm 100 140 1460 A Mounting the air inlet with a canvas connection B Mounting the air inle...

Page 8: ...room by ducting Do NOT use spaces such as a false ceiling as a duct for the air inlet or outlet WARNING Do NOT install operating ignition sources example open flames an operating gas appliance or an operating electric heater in the duct work The ducting is to be field supplied Air inlet side Attach the duct and intake side flange field supply For connecting the flange use 7 accessory screws a b b ...

Page 9: ... insulation piece drain pipe 5 Wind the large sealing pad insulation around the metal clamp and drain hose and fix it with cable ties 6 Connect the drain piping to the drain hose 4 mm A A A A A A f 6 5 2 c e 4 b a d b a d c 3 1 2 6 1 a Drain pipe connection attached to the unit b Drain hose accessory c Metal clamp accessory d Large sealing pad accessory e Insulation piece drain pipe accessory f Dr...

Page 10: ...ntly resistant to corrosion or are suitably protected against corrosion WARNING FLAMMABLE MATERIAL The R32 refrigerant if applicable in this unit is mildly flammable Refer to the outdoor unit specifications for the type of refrigerant to be used Pipe length Keep refrigerant piping as short as possible Flare connections Connect refrigerant piping to the unit using flare connections Insulation Insul...

Page 11: ...e electrical wiring does NOT obstruct proper reattachment of the service cover It is important to keep the power supply and the transmission wiring separated from each other In order to avoid any electrical interference the distance between both wirings should ALWAYS be at least 50 mm NOTICE Be sure to keep the power line and transmission line apart from each other Transmission wiring and power su...

Page 12: ...t the equipment is connected only to a supply with a short circuit power Ssc greater than or equal to the minimum Ssc value Ensure that equipment is connected only to a supply with a short circuit power Ssc greater than or equal to Ssc in table below Combination FBA35A FBA50A FBA60A FBA71A RZAG71M 2 1 RZQG71L RZAG100M 3 2 31 2 1 30 RZQG100L RZAG125M 4 3 33 3 2 32 2 2 05 RZQG125L RZAG140M 4 3 33 3 ...

Page 13: ...ICE NEVER operate the unit without thermistors and or pressure sensors switches Burning of the compressor might result 7 1 Checklist before commissioning After the installation of the unit first check the following items Once all below checks are fulfilled the unit MUST be closed ONLY then can the unit be powered up You read the complete installation instructions as described in the installer refe...

Page 14: ...door unit has NOT been done correctly the following error codes may be displayed on the user interface Error code Possible cause Nothing displayed the currently set temperature is not displayed The wiring is disconnected or there is a wiring error between power supply and outdoor unit between outdoor unit and indoor units between indoor unit and user interface The fuse on the outdoor or indoor uni...

Page 15: ...ND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MAGNETIC RELAY L LIVE L COIL L R REACTOR M STEPPER MOTOR M C COMPRESSOR MOTOR M F FAN MOTOR M P DRAIN PUMP MOTOR M S SWING MOTOR MR MRCW MRM MRN MAGNETIC RELAY N NEUTRAL n N NUMBER OF PASSES TH...

Page 16: ...4P456962 1D 2018 08 Copyright 2017 Daikin ...

Reviews: